Lochinvar 80 - 285 manual Maintenance schedule

Page 6

User’s Information Manual

2Maintenance schedule

Maintenance procedures

Boiler must be serviced and maintained

Read the list of potential materials listed in Table 1 on page 4 of this manual. If any of these products are in the room from which the boiler takes its combustion air, they must be removed immediately or the boiler combustion air (and vent termination) must be relocated to another

￿WARNING

NOTICE

The boiler must be inspected and started annually at the beginning of the heating season by a qualified service technician. In addition, the maintenance and care of the boiler designated on page 5 of this manual and explained on pages 6 through 8 must be performed to assure maximum boiler efficiency and reliability. Failure to service and maintain the boiler and system could result in equipment failure, causing possible severe personal injury, death, or substantial property damage.

The following information provides detailed instructions for completing the maintenance items listed in the maintenance schedule on page 5. In addition to this maintenance, the boiler must be serviced and started up at the beginning of each heating season by a qualified service technician.

area.

Check pressure/temperature gauge

1.Make sure the pressure reading on the boiler pressure/ temperature gauge does not exceed 24 psi. Higher pressure may indicate a problem with the expansion tank.

2.Contact a qualified service technician if problem persists.

Check vent piping

1.Visually inspect the flue gas vent piping for any signs of blockage, leakage, or deterioration of the piping. Notify your qualified service technician at once if you find any problems.

￿WARNING Failure to inspect the vent system as noted above and have it repaired by a qualified

service technician can result in vent system failure, causing severe personal injury or

Check boiler area

death.

￿WARNING

To prevent potential of severe personal injury, death, or substantial property damage, eliminate all materials discussed below from the boiler vicinity and the vicinity of the boiler combustion air inlet. If contaminants are found:

Remove products immediately from the area. If they have been there for an extended period, call a qualified service technician to inspect the boiler for possible damage from acid corrosion.

If products cannot be removed, immediately call a qualified service technician to re-pipe vent and air piping and locate vent termination/air intake away from contaminated areas.

Check air piping

1.Visually inspect the air inlet termination to be sure it is unobstructed. Inspect the entire length of air piping to ensure piping is intact and all joints are properly sealed.

2.Call your qualified service technician if you notice any problems.

Check relief valve

1.Inspect the boiler relief valve and the relief valve discharge pipe for signs of weeping or leakage.

2.If the relief valve often weeps, the expansion tank may not be working properly. Immediately contact your qualified service technician to inspect the boiler and system.

1.Combustible/flammable materials -- Do not store combustible materials, gasoline or any other flammable vapors or liquids near the boiler. Remove immediately if found.

2.Air contaminants -- Products containing chlorine or fluorine, if allowed to contaminate the boiler intake air, will cause acidic condensate in the boiler. This will cause significant damage to the boiler if allowed to continue.

6

Check condensate drain system

1.Inspect the condensate drain line, condensate PVC fittings and condensate trap.

Fill condensate trap with water

1.Remove the PVC cap retaining screw from the PVC cap (FIG. 1).

2.Remove the 2" PVC cap with the switch located at the top of the trap (FIG. 1).

Image 6
Contents User’s Information Manual Models 80 Save this manual for future referenceContents Boiler service and maintenance Please read before proceedingPrevent combustion air contamination Products to avoidAreas likely to have contaminants Maintenance schedule Service technician Owner maintenanceSee pages 6 8 for detailed instructions Maintenance schedule Condensate Trap Condensate disposalCheck automatic air vents Test low water cutoff if installedReset button low water cutoff Operate relief valveOperating instructions Smart System control module Knight boiler control moduleUser Access modesInstaller To save parameters and exit programmingParameter table Temperature settings GeneralData logging DHW settings Outdoor air resetSet Point Met ServiceStandby PrepurgeSYS ***.*F Control will display the actual fan motor RPMDelay 10V in **.VdcOperation of the cascade User’s Information Manual

80 - 285 specifications

The Lochinvar 80 - 285 is a well-regarded series of high-efficiency boilers that has established itself as a leading option for both residential and commercial applications. Known for its robust performance and innovative technologies, this range is designed to meet the diverse heating needs of modern buildings.

One of the standout features of the Lochinvar 80 - 285 series is its advanced condensing technology. This allows the boiler to extract a greater amount of heat from the combustion gases, resulting in higher energy efficiency. With an annual fuel utilization efficiency (AFUE) rating that can exceed 95%, users can expect significant savings on energy costs while reducing their carbon footprint.

Another important characteristic of the Lochinvar 80 - 285 is its stainless steel heat exchanger. The use of stainless steel not only enhances durability but also ensures longer life expectancy and resistance to corrosion. This makes it an excellent choice for harsh environments or areas with hard water. Furthermore, the design of the heat exchanger promotes optimal thermal performance and efficient heat transfer, ensuring that the system operates at peak efficiency.

The Lochinvar 80 - 285 series also incorporates intelligent controls, allowing for enhanced operation and management of heating systems. The intuitive user interface provides easy access to critical system information, allowing users to monitor performance and make adjustments as needed. The built-in diagnostic tools help in troubleshooting and maintaining optimal performance, minimizing downtime and service costs.

Moreover, the boiler is designed with a flexible venting system. It can be vented vertically or horizontally, offering installation versatility for various building configurations. This adaptability makes it a favorite among contractors and engineers, simplifying the installation process and reducing labor costs.

The Lochinvar 80 - 285 series prioritizes safety as well. It comes equipped with multiple safety features, including flame monitoring and automatic shut-off valves, ensuring that the system operates safely under all conditions. Additionally, its low emissions design contributes to a cleaner environment by complying with stringent emission standards.

In summary, the Lochinvar 80 - 285 series stands out for its high efficiency, durability, and user-friendly technology. With its advanced condensing technology, stainless steel heat exchanger, intelligent controls, and versatile installation options, it is a dependable choice for anyone seeking a reliable heating solution that prioritizes performance and sustainability.