2Maintenance schedule

Check automatic air vents

1.

Reference FIG. 3 below.

2.

Remove the caps (FIG. 3 – “A”) from the automatic air

 

vents in the system and check operation by slightly

 

depressing valve “B” (FIG. 3) with the tip of a

 

screwdriver.

3.

If the air vent valve appears to be working freely and not

 

leaking, replace cap “A”, twisting the cap all the way on.

User’s Information Manual

￿WARNING Have leaks fixed at once by a qualified service technician. Failure to comply could

result in severe personal injury, death, or substantial property damage.

3.Replace the front access door.

Operate relief valve

1.Before proceeding, verify that the relief valve outlet has been piped to a safe place of discharge, avoiding any possibility of scalding from hot water.

4.

Loosen cap “A” one turn to allow vent to operate.

5.

Have the automatic air vent(s) replaced if it does not

 

operate correctly.

Figure 3 Automatic Air Vent

￿WARNING

To avoid water damage or scalding due to valve operation, a metal discharge line must be connected to the relief valve outlet and run to a safe place of disposal. This discharge line must be installed by a qualified heating installer or service technician in accordance with the instructions in the Knight Boiler Installation and Operation Manual. The discharge line must be terminated so as to eliminate possibility of severe burns or property damage should the valve discharge.

Test low water cutoff (if installed)

1.If the system is equipped with a low water cutoff, test the low water cutoff periodically during the heating season, following the low water cutoff manufacturer’s instructions.

Reset button (low water cutoff)

1.Testing the low water cutoff shuts the unit off. Press the RESET button on the low water cutoff to turn the unit back on.

Check boiler piping (gas and water)

1.Remove the boiler front access door and perform a gas leak inspection per steps 1 through 7 of the Operating Instructions on page 9. If gas odor or leak is detected, immediately shut down the boiler following the procedures on page 9. Call a qualified service technician.

2.Visually inspect for leaks around water piping. Also inspect the circulators, relief valve, and fittings. Immediately call a qualified service technician to repair any leaks.

8

2.Read the boiler pressure/temperature gauge to make sure the system is pressurized. Lift the relief valve top lever slightly, allowing water to relieve through the valve and discharge piping.

3.If water flows freely, release the lever and allow the valve to seat. Watch the end of the relief valve discharge pipe to ensure that the valve does not weep after the line has had time to drain. If the valve weeps, lift the seat again to attempt to clean the valve seat. If the valve continues to weep afterwards, contact your qualified service technician to inspect the valve and system.

4.If water does not flow from the valve when you lift the lever completely, the valve or discharge line may be blocked. Immediately shut down the boiler, following the operating instructions on page 9 of this manual. Call your qualified service technician to inspect the boiler and system.

Shut boiler down (unless boiler is used for Domestic Water)

1.Follow “To Turn Off Gas to Appliance” on page 9 of this manual.

2.Do not drain the system unless exposure to freezing temperatures will occur.

3.Do not drain the system if it is filled with an antifreeze solution.

4.DO NOT shut down boilers used for domestic water heating, they must operate year-round.

Image 8
Contents User’s Information Manual Models 80 Save this manual for future referenceContents Boiler service and maintenance Please read before proceedingAreas likely to have contaminants Prevent combustion air contaminationProducts to avoid See pages 6 8 for detailed instructions Maintenance schedule Service technicianOwner maintenance Maintenance schedule Condensate Trap Condensate disposalTest low water cutoff if installed Reset button low water cutoffCheck automatic air vents Operate relief valveOperating instructions Smart System control module Knight boiler control moduleAccess modes InstallerUser To save parameters and exit programmingParameter table Data logging Temperature settingsGeneral DHW settings Outdoor air resetService StandbySet Point Met PrepurgeSYS ***.*F Control will display the actual fan motor RPMDelay 10V in **.VdcOperation of the cascade User’s Information Manual

80 - 285 specifications

The Lochinvar 80 - 285 is a well-regarded series of high-efficiency boilers that has established itself as a leading option for both residential and commercial applications. Known for its robust performance and innovative technologies, this range is designed to meet the diverse heating needs of modern buildings.

One of the standout features of the Lochinvar 80 - 285 series is its advanced condensing technology. This allows the boiler to extract a greater amount of heat from the combustion gases, resulting in higher energy efficiency. With an annual fuel utilization efficiency (AFUE) rating that can exceed 95%, users can expect significant savings on energy costs while reducing their carbon footprint.

Another important characteristic of the Lochinvar 80 - 285 is its stainless steel heat exchanger. The use of stainless steel not only enhances durability but also ensures longer life expectancy and resistance to corrosion. This makes it an excellent choice for harsh environments or areas with hard water. Furthermore, the design of the heat exchanger promotes optimal thermal performance and efficient heat transfer, ensuring that the system operates at peak efficiency.

The Lochinvar 80 - 285 series also incorporates intelligent controls, allowing for enhanced operation and management of heating systems. The intuitive user interface provides easy access to critical system information, allowing users to monitor performance and make adjustments as needed. The built-in diagnostic tools help in troubleshooting and maintaining optimal performance, minimizing downtime and service costs.

Moreover, the boiler is designed with a flexible venting system. It can be vented vertically or horizontally, offering installation versatility for various building configurations. This adaptability makes it a favorite among contractors and engineers, simplifying the installation process and reducing labor costs.

The Lochinvar 80 - 285 series prioritizes safety as well. It comes equipped with multiple safety features, including flame monitoring and automatic shut-off valves, ensuring that the system operates safely under all conditions. Additionally, its low emissions design contributes to a cleaner environment by complying with stringent emission standards.

In summary, the Lochinvar 80 - 285 series stands out for its high efficiency, durability, and user-friendly technology. With its advanced condensing technology, stainless steel heat exchanger, intelligent controls, and versatile installation options, it is a dependable choice for anyone seeking a reliable heating solution that prioritizes performance and sustainability.