Page 6

Outdoor Knight Boiler User’s Information Manual

2 Maintenance schedule

Maintenance procedures

Boiler must be serviced and maintained

Read the list of potential materials listed in Table 1 on page 4 of this manual. If any of these products are in the room from which the boiler takes its combustion air, they must be removed immediately or the boiler combustion air (and vent termination) must be relocated to another

￿WARNING

NOTICE

The boiler must be inspected and started annually at the beginning of the heating season by a qualified service technician. In addition, the maintenance and care of the boiler designated on page 5 of this manual and explained on pages 6 through 8 must be performed to assure maximum boiler efficiency and reliability. Failure to service and maintain the boiler and system could result in equipment failure, causing possible severe personal injury, death, or substantial property damage.

The following information provides detailed instructions for completing the maintenance items listed in the maintenance schedule on page 5. In addition to this maintenance, the boiler must be serviced and started up at the beginning of each heating season by a qualified service technician.

area.

Check pressure/temperature gauge

1.Make sure the pressure reading on the boiler pressure/ temperature gauge does not exceed 24 psi. Higher pressure may indicate a problem with the expansion tank.

2.Contact a qualified service technician if problem persists.

Check vent piping

1.Visually inspect the flue gas vent piping for any signs of blockage, leakage, or deterioration of the piping. Notify your qualified service technician at once if you find any problems.

￿WARNING Failure to inspect the vent system as noted above and have it repaired by a qualified

service technician can result in vent system failure, causing severe personal injury or

Check boiler area

death.

￿WARNING

To prevent potential of severe personal injury, death, or substantial property damage, eliminate all materials discussed below from the boiler vicinity and the vicinity of the boiler combustion air inlet. If contaminants are found:

Remove products immediately from the area. If they have been there for an extended period, call a qualified service technician to inspect the boiler for possible damage from acid corrosion.

If products cannot be removed, immediately call a qualified service technician to re-pipe vent and air piping and locate vent termination/air intake away from contaminated areas.

Check air piping

1.Visually inspect the air inlet termination to be sure it is unobstructed. Inspect the entire length of air piping to ensure piping is intact and all joints are properly sealed.

2.Call your qualified service technician if you notice any problems.

Check relief valve

1.Inspect the boiler relief valve and the relief valve discharge pipe for signs of weeping or leakage.

2.If the relief valve often weeps, the expansion tank may not be working properly. Immediately contact your qualified service technician to inspect the boiler and system.

Check condensate drain system

1.Combustible/flammable materials -- Do not store combustible materials, gasoline or any other flammable vapors or liquids near the boiler. Remove immediately if found.

2.Air contaminants -- Products containing chlorine or fluorine, if allowed to contaminate the boiler intake air, will cause acidic condensate in the boiler. This will cause significant damage to the boiler if allowed to continue.

6

1.Inspect the condensate drain line, condensate PVC fittings and condensate trap.

Fill condensate trap with water

1.Remove the PVC cap retaining screw from the PVC cap (FIG. 1).

2.Remove the 2" PVC cap with the switch located at the top of the trap (FIG. 1).

Image 6
Contents Outdoor Knight Boiler User’s Information Manual Models 151 Contents Boiler service and maintenance Please read before proceedingPrevent combustion air contamination Products to avoidAreas likely to have contaminants Maintenance schedule Service technician GeneralMaintenance schedule Fill condensate trap with waterCondensate Trap Condensate disposalCheck air vents Operating instructions Installer Smart System control moduleUser Temperature Units Night Setback OverrideSpace heating SH1, SH2, SH3 and tank set points Call for Heat Smart System control module Dial Function Outdoor Knight Boiler User’s Information Manual
Related manuals
Manual 76 pages 1.76 Kb

286, 151 specifications

Lochinvar 151,286 is a notable model in the realm of commercial water heating solutions, designed primarily for large-scale applications. This model incorporates advanced technologies and features that set it apart in terms of efficiency, usability, and reliability.

One of the hallmark features of Lochinvar 151,286 is its high-efficiency system that leverages condensing technology. This technology enables the unit to extract additional heat from exhaust gases, allowing it to operate at an impressive annual fuel utilization efficiency (AFUE) rating. This not only reduces energy consumption, but it also significantly lowers operational costs.

The Lochinvar 151,286 is equipped with a robust stainless steel heat exchanger, which provides both durability and enhanced thermal efficiency. This design withstands the rigors of high-demand environments, making it ideal for restaurants, schools, hospitals, or any facility requiring consistent hot water supply. Its compact footprint allows it to be installed in tight spaces without sacrificing performance.

Another standout characteristic is its intelligent control system. The built-in touchscreen interface offers users an intuitive way to manage settings, monitor performance, and troubleshoot issues. This smart technology aids in simplifying maintenance and improves overall system reliability. The unit also features advanced safety protocols, including multiple sensors that monitor operation and provide alerts in case of irregular performance.

In terms of capacity, the Lochinvar 151,286 can deliver an impressive output, accommodating varying demands with ease. Its innovative modulation capabilities allow the unit to adjust its heating output based on real-time hot water needs, ensuring unmatched comfort and efficiency.

Supporting the model’s performance are versatile connectivity options. Lochinvar 151,286 can integrate seamlessly with building management systems, allowing facility managers to monitor and control heating processes remotely. This level of connectivity not only enhances control but also supports energy-saving strategies across the facility.

In conclusion, Lochinvar 151,286 stands out as a premium choice for commercial water heating needs. With its high-efficiency ratings, durable construction, intelligent control system, impressive capacity, and versatile connectivity, it ensures that hot water is delivered reliably and efficiently, meeting the demands of modern businesses while reducing energy costs. This combination of technology and design makes it an essential component for any large-scale facility focused on performance and sustainability.