Bosch Appliances 100 Combi Boiler manual System 5 Greenstar Heating Boiler in a single zone system

Page 29

Applications Manual

Bosch Greenstar 29

 

 

2.5System 5: Greenstar Heating Boiler in a single zone system

Summary:

Single boiler with primary/secondary piping configuration supplying one heating zone. Outdoor reset with FW200 controller with built-in room sensor mounted in the living space for room feedback.

Use this design where System 1 cannot be used due to too great a system pressure drop. Primary/secondary piping is also required for radiant floor and panel radiator applica- tions.

Primary/secondary piping isolates the system flow from the boiler flow and prevents the system from influencing boiler performance.

In detail:

The FW200 is an outdoor temperature based controller with room temperature influence. The controller adjusts the heating curve (boiler supply temperature) according to outdoor temperature. When the FW200 is wall mounted as a room sensor, it uses room temperature to adjust the heating curve and modify boiler supply temperature ac- cordingly.

FW200 provides warm weather shutdown.

For temperature sensitive radiant floor applications, install a thermostatic tempering valve for overheat protection.

Required components:

Greenstar heating boiler.

FW200 controller in the room.

Primary/secondary piping and system pump.

Thermostatic mixing valve (optional - overheat protection for temperature sensitive floors).

Additional instructions:

See manufacturer’s installation and operating instructions.

Bosch Thermotechnology Corp.

Data subject to change

Image 29 Contents
Bosch Bosch Greenstar Applications Manual Table of Contents Greenstar Combi-boilers Boiler types and sizesGreenstar Heating boilers DHW FW200 Boiler Energy Management SystemFB100 Remote Control & Room Sensor Combination overview IPM2 Space Heating ModuleCombination overview ISM2 Solar ModuleBasic solar thermal systems System expansionsApplications List of most common applications GPM Boiler pump capacity in single zone systemsPump curve of heating boiler Summary System 1 Greenstar Heating Boiler in a single zone systemDetail Required componentsSystem 1 Piping Diagram System 1 Wiring Diagram Additional information System 1 Setup and ProgrammingInitial setup System 2 Greenstar Combi Boiler in a single zone system System 2 Piping diagram System 2 Wiring diagram System 2 Setup and Programming Summary System 3 Piping diagram System 3 Wiring diagram System 3 Setup and Programming Summary System 4 Piping diagram System 4 Wiring diagram System 4 Setup and Programming System 5 Greenstar Heating Boiler in a single zone system System 5 Piping diagram System 5 Wiring diagram System 5 Setup and Programming System 6 Greenstar Combi Boiler in a single zone system System 6 Piping diagram System 6 Wiring diagram System 6 Setup and Programming Summary System 7 Piping diagram System 7 Wiring diagram System 7 Setup and Programming Summary System 8 Piping diagram System 8 Wiring diagram Boiler and FW200 programming System 8 Setup and ProgrammingSummary System 9 Piping diagram System 9 Wiring diagram System 9 Setup and Programming Summary System 10 Piping diagram System 10 Wiring diagram System 10 Setup and Programming Summary System 11 Piping diagram System 11 Wiring diagram System 11 Setup and Programming Summary System 12 Piping diagram System 12 Wiring diagram System 12 Setup and Programming Applications Manual Bosch Greenstar Bosch Greenstar Applications Manual Applications Manual Bosch Greenstar