5. GAS ADJUSTMENTS

TABLE 5.1

CATEGORY II2H3+

Lower Wobbe Index (15°C;1013mbar)

Nominal Delivery Pressure

Minimum Delivery Pressure

15 RFFI

Main Burner: n. 8 jets (ø ) Restrictor

Consumption (15°C; 1013mbar) Consumption (15°C; 1013mbar) Gas Burner Pressure:

max - min

MJ/m3h mbar mbar

mm

ø

m3/h Kg/h

mbar

Methane Gas

G20

45.67

20

17

1.30

---

1.62

----

8.5

Liquid Butane Gas

Liquid Propane Gas

G30

G31

80.58

80.58

29

37

20

25

0.77

0.77

3.3

3.3

----

----

1.21

1.19

22.1

28.8

 

 

[1 mbar = 10,197 mmc.a.]

5.1CHANGING THE TYPE OF GAS

FIG. 5.1

VG002Ab

6.MAINTENANCE

The outlet pressure of the gas cock is obtained by completely loosening the screw on the solenoid. The maximum pressure of the gas to the burner will be equal to the nominal delivery pressure minus the head loss within the gas valve.

The boiler can be converted to use either methane (natural) gas (G20) or LPG (G30 - G31) by an Authorised Service Centre.

The operations that must be performed are the following:

1.Replace the jets on the main burner (see table in section 5);

2.Pay attention to put the gas restrictor if convert the boiler from NG to GPL and to take it out when pass from LPG to NG;

2.Adjust the maximum and minimum thermal capacity values for the boiler (see table in section 5);

3.Replace the gas rating plate;

4.Adjust the maximum thermal power setting;

5.Adjust the soft-light feature (open the cover of the regulation screw on the gas valve (see FIG. 5.1). Rotate clockwise from min. to max. as per installation requirements).

It is recommended that the following inspections be carried out on the boiler at least once a year:

1 - Check the seals for the water connections; replace any faulty seals.

2 - Check the gas seals; replace any faulty gas seals.

3 - Visual check of the entire unit.

4 - Visual check of the combustion process or analysis of combustion by-products (see section 4.5) and cleaning of the burner if needed.

5 - If called for by point. 3, dismantling and cleaning of the combustion chamber.

6 - If called for by point. 4, dismantling and cleaning of the burner jets.

7 - Visual check of the primary heat exchanger:

-check for overheating in the blade assembly;

-clean the exhaust fan if needed.

8 - Adjustment of the flow rate of the gas: flow rate for lighting, partial load and full load.

9 - Check of the heating safety systems:

-safety device for maximum temperature (overheat thermostat);

-safety device for maximum pressure (safety valve).

10- Check of the gas safety systems:

-safety device for lack of gas or flame ionisation (detection electrode);

-safety device for gas cock.

11- Check of the electrical connection (make sure it complies with the instructions in the manual).

12- General check of the combustion by-products of the discharge/ventilation system.

13- Check of the general performance of the unit.

19

Image 19
Contents Installation Instructions Type C Boilers Table of Contents General Instructions Overall View InstallationReference Standards Mounting the Appliance Electrical Connection Overall DimensionsSiting the Appliance ClearancesWater Connections GAS ConnectionResidual Head of the Boiler Tower Flue Components Flue Connections80 mm Room Thermostat Connection RffiOn/Off Switch Electrical DiagramGAS and Water Circuits H.W. Storage Cylinder 2 Port and 3 Port Valve InstallationsModel Domestic HOT Water Priority KIT CommissioningInitial Preparation Removing the Front Panel Control PanelFume Discharge Monitoring Initial START-UP Combustion AnalysisBoiler Safety Systems Draining the System Changing the Type of GAS GAS AdjustmentsMaintenance RffiNumber 41-116-05 Technical Information

41-116-05 specifications

The Ariston 41-116-05 is an innovative and efficient appliance designed to meet modern home heating and comfort needs. As part of Ariston's extensive portfolio, this model embodies the brand's commitment to quality and sustainability.

One of the main features of the Ariston 41-116-05 is its advanced energy efficiency rating. It incorporates cutting-edge technology to optimize energy consumption, helping homeowners reduce their utility bills while minimizing their environmental impact. This aligns with the growing demand for eco-friendly heating solutions in today's market.

The heater is equipped with a powerful heating element, capable of quickly generating warmth even in larger spaces. Its robust performance ensures that rooms reach the desired temperature rapidly, providing comfort during cold weather conditions. The unit is designed with multiple heat settings, allowing users to customize the warmth level according to their preferences and specific needs.

Moreover, the Ariston 41-116-05 features an intuitive digital control panel. This user-friendly interface makes it easy for individuals to adjust settings, monitor energy consumption, and set timers for automatic operation. Some models also offer Wi-Fi connectivity, enabling users to control their heating remotely via a smartphone app. This feature is particularly beneficial for those who want to maintain a comfortable environment in their homes while controlling energy use.

Safety is another cornerstone of the Ariston 41-116-05’s design. The appliance is equipped with multiple safety mechanisms, including overheat protection and a tip-over switch. These features ensure that the unit operates safely and securely, providing peace of mind for homeowners.

In summary, the Ariston 41-116-05 is a modern appliance that combines efficiency, performance, and safety. Its exceptional energy-saving capabilities, user-friendly controls, and robust heating power make it an ideal choice for anyone seeking reliable home heating solutions. With its range of features and commitment to sustainability, the Ariston 41-116-05 stands out as a valuable addition to contemporary households, enhancing comfort while being mindful of the environment.