Crown Boiler CWD138, CWD083, CWD220, CWD060, CWD165 III Before Installing, IV Locating the Boiler

Page 4

IIIBefore Installing

1)Safe, reliable operation of this boiler depends upon installation by a professional heating contractor in strict accordance with this manual and the authority having jurisdiction.

In the absence of an authority having jurisdiction, installation must be in accordance with this manual and the National Fuel Gas Code, ANSI Z223.1.

Where required by the authority having jurisdiction, this installation must conform to the Standard for Controls and Safety Devices for Automatically Fired Boilers (ANSI/ASME CSD-1).

2)Read Section VI to verify that the maximum combustion air and exhaust pipe lengths will not be exceeded in the planned installation. Also verify that the vent terminal can be located in accordance with Section VI.

3)Make sure that the boiler is correctly sized:

For heating systems employing convection radiation (baseboard or radiators), use an industry accepted sizing method such as the I=B=R Heat Loss Calculation Guide (Pub. #H21 or #H22) published by the Hydronics Institute in Berkely Heights, NJ.

For new radiant heating systems, refer to the radiant tubing manufacturer’s boiler sizing guidelines.

For systems including a Crown Mega-Stor indirect water heater, size the boiler to have either the DOE Heating Capacity required for the Mega-Stor or the net rating required for the heating system, whichever results in the larger boiler.

For systems that incorporate other indirect water heaters, refer to the indirect water heater manufacturer’s instructions for boiler output requirements.

4)Make sure that the boiler received is configured for the correct gas (natural or LP).

5)This boiler is not designed for use with return temperatures under 120F for a sustained period of time. Some systems, such as those having large water contents, may require a return water bypass or other special provisions to protect the boiler against low return temperatures. Failure to provide such provisions if needed could result in severe corrosion damage to the boiler. For more information on when low water temperatures protection is required, and appropriate protection, see Part VIII.

6)For installations at altitudes above 2000ft, special orifice and pressure switches are required. Make sure that the boiler is configured for use at the correct altitude.

NOTICE

This product must be installed by a licensed plumber or gas fitter when installed within the Commonwealth of Massachusetts. See Appendix A for additional important information about installing this product within the Commonwealth of Massachusetts.

IV Locating the Boiler

1)Boiler clearances are shown in Figure 2. Figure 2a shows clearances from the boiler when outdoor combustion air is used. Figure 2b shows clearances from the boiler when combustion air is obtained from the boiler room. These minimum clearances apply to all types of combustible construction as well as noncombustible walls, ceilings and doors. At least 24” must be provided for servicing at the front of the boiler. This front clearance may be provided through a door, such as a closet door. Boiler will be much easier to service if at least 12” is provided from the sides and rear of the boiler to walls.

2)Clearances from venting to combustible material depends upon the type of venting, whether the vent pipe is enclosed, and whether the venting is vertical or horizontal. See Table 2 for vent clearance information.

3)Boiler may be installed on a non-carpeted combustible surface.

4)The relief valve must not be moved from the location shown in Figure 1.

5)When combustion air is obtained from the boiler room, a 10” clearance is required from the side of the boiler having the air inlet collar to combustible or non-combustible obstruction (Figure 2b).

6)The boiler should be located so as to minimize the length of the vent system.

7)Do not install this boiler in a location where gasoline or other flammable vapors or liquids will be stored or used. Do

not install this boiler in an area where large amounts of airborne dust will be present, such as a workshop. When indoor combustion air is used, do not install in a location where sources of hydrocarbons will be stored or used. Some common sources of hydrocarbons include bleaches, fabric softeners, paints, cleaners, refrigerants, and cat boxes. Traces of these substances can be drawn into the boiler causing severe corrosion damage to the boiler and /or objectionable odors.

2

Image 4
Contents CWD Series Table of Contents Product Description II SpecificationsIII Before Installing IV Locating the BoilerClearances When Combustion AIR is Obtained from Boiler Room Air for Combustion and Ventilation Clearances from Vent Piping to Combustible ConstructionPage If Indoor Combustion Air is Used, Provide Air as Follows ALL AIR from Outside Using Ventilated Crawl Space and Attic ALL AIR from Outside Using Openings Into Boiler Room VI Venting Vent System DesignSummary of Horizontal Venting Options Page Horizontal Direct Exhaust Vent System Vent Options 4,5 Page Summary of Vertical Venting Options Vertical NON-COAXIAL Direct Vent System Vent Options 6 Summary of Vertical Coaxial Venting Options Page Permissible Vent Systems and Principle Vent Components Vent Fitting Removing an Existing Boiler From a Common ChimneyAIR Intake Fitting Horizontal Terminal Offsets Positioning Vent Terminal Under Overhangs Vent / Intake System Assembly USE of Condensate TrapsFAN Outlet Orifice Crown Coaxial Terminal Exploded View CORR/GUARD Connection to Vent Collar Vent III Connection to Vent Collar SAF-T Vent Ezseal Connection to Vent Collar Fasnseal Connection to Vent Collar FSA-SWDW3 Page Condensate TRAP/DRAIN Detail VII Gas Piping GAS Connection to BoilerViii System Piping Standard PipingPiping for Special Situations Basic Piping Bypass Piping Chiller Piping IX Wiring CB502 System Single Zone WiringCB502 Control System Single Zone Field Wiring CB502 System Wiring Variations CB502 Control System Sequence of OperationCB502 Control System Field Wiring for TWO Circulator Zones CB502 Control System Internal Ladder Diagram CB502 Control System Internal Connection Diagram R8285 Control System Wiring Variations R8285 Control System Single Zone WiringR8285 Control System Sequence of Operation R8285 Control System Single Zone Field Wiring R8285 Control System Zone Valve Field Wiring R8285 Control System Internal Connection Diagram Start-up and Checkout For Your Safety Read Before Operating Pilot Burner Flame GAS Valve XI Service and Maintenance Heat Exchanger Cleaning Procedure Service Notes Pressure Switch Settings Measuring Pressure Across Pressure Switch XII Troubleshooting PWR DHW Limit 24V GND on ign. module? Thermostat calls for heat Circulator Pilot Main Start Xiii Parts BLOCK, BASE, Flue Collector Components Page Burner Tray Components Page Jacket Components Page Common Controls & Trim Page Page Page Crown

CWD193, CWD165, CWD245, CWD220, CWD110 specifications

Crown Boiler Company is well-known for its commitment to quality and performance in the heating industry. Among its extensive range of products, the Crown Boiler CWD series stands out for its reliability and efficiency. This series includes models CWD060, CWD083, CWD110, CWD138, and CWD220, each designed to meet diverse heating needs in residential and commercial applications.

One of the main features of the CWD series is its durable construction. Made with high-quality materials, these boilers are built to withstand the test of time. The cast iron heat exchanger delivers exceptional heat retention and efficiency, ensuring optimal performance even in demanding conditions. Additionally, the CWD models are equipped with a reliable standing pilot ignition system, which enhances user safety and operational reliability.

Another important characteristic of the Crown CWD series is its versatility in fuel options. These boilers can operate on either natural gas or propane, providing flexibility to homeowners and businesses depending on their preferred energy source. The ability to easily switch fuels makes these units adaptable to various heating applications, maximizing convenience for users.

Efficiency is a cornerstone of the Crown Boiler CWD series. With an AFUE rating of up to 85%, these boilers deliver substantial cost savings over the heating season. Their efficient operation not only lowers energy bills but also contributes to a reduced environmental impact, which is increasingly important in today’s energy-conscious world.

Crown’s innovative design features also include a low water cut-off and a built-in draft hood. The low water cut-off ensures safe operation by preventing the boiler from running dry, while the draft hood allows for optimal venting capabilities, minimizing the risk of dangerous flue gas build-up.

Maintenance is straightforward with the CWD series, thanks to its easy-access design. Routine service and inspections can be performed with minimal disruption, ensuring that the units maintain peak performance over their lifespan.

The Crown Boiler CWD060, CWD083, CWD110, CWD138, and CWD220 models exemplify the brand’s dedication to delivering high-quality heating solutions. With their impressive efficiency ratings, durable construction, versatile fuel options, and user-friendly features, these boilers represent a smart investment for anyone looking to enhance heating reliability and comfort in their space.