Bryan Boilers CLM Series manual True flexible water tube

Page 3

Low initial cost, high operating efficiency deliver substantial return on investment

True “flexible water tube”

design guaranteed shock free

Longer service life with

superior performance

G

Full five sq ft of heating

surface per BHP

Quality Construction Features

L

I

A. Heavy steel boiler frame, built and stamped in accor- dance with the appropriate ASME Boiler Code.

B. Large volume water leg downcomers promote rapid internal circulation, temperature equalization and efficient heat transfer.

C. Bryan bent water tubes are flexible, individually re- placeable without welding or rolling. Never more than two tube configurations.

D. Boiler tube and furnace area access panel: heavy gauge steel casing with 2" high temperature ceramic fiber and insulation, bolted and tightly sealed to boiler frame.

E. Jacket access panels make the interior of the boiler easily accessible for service and inspection.

F. Heavy gauge steel boiler jacket with rust-resistant zinc coating and attractive enamel finish, insulated with 1½" fiberglass to insure exceptionally cool outer surface.

G. Minimum sized flue vent.

H. Forced draft, flame retention head type burner. Effi- cient combustion of oil or gas, quiet operation.

I. All controls, gauges, relief valve(s) are factory installed and wired and easily accessible for servicing.

J. Electrical box: all controls installed and connected to terminal strip.

K.Water side or steam side interior accessible for cleanout

B

J

C

D

K

EF

A

MH

and inspection, front and rear openings, upper and lower drums.

L. Steam boilers with extra large drum with high steam release area ensure stable water level and dry steam.

M. Steel plate boiler base with lightweight, high tempera- ture insulating firebrick combustion chamber, designed for maximum combustion efficiency.

Bryan CLM Series Boilers Standard and Optional Equipment

STANDARD EQUIPMENT FURNISHED

OPTIONAL EQUIPMENT:

Hot water boiler

Water Boiler

Combination thermometer and pres- sure gauge, ASME-rated boiler relief valve,watertemperaturecontrol(240°F max std.), high limit control, probe LWCO.

Steam Boiler

Steam pressure gauge, steam pres- sure control, combination low water cutoff and pump control, auxiliary low water cutoff, high limit pressure con- trol, ASME-rated boiler relief valve, water glass set.

Straight gas fired unit

Electronic combustion safety control, automatic operating gas valve, safety gas valve, pilot solenoid valve, pilot ignition assembly, main manual gas shut-off valve, pilot cock, pilot and maingaspressureregulators,airsafety

switch, control panel, all controls in- stalled and wired.

Straight oil fired unit

Electronic combustion safety control, dual oil valves, oil ignition transformer, two-stage fuel unit, direct spark ignition of oil, oil nozzle assembly, control panel, all controls installed and wired.

Combination gas-oil unit

Electronic combustion safety control, automatic operating gas valve, safety gas valve, pilot solenoid valve, pilot ignition assembly, main manual gas shut-off valve, pilot cock, pilot and main gas pressure regulators, air safety switch, manual fuel selector switch, dual oil valves, gas pilot for both fuels, two-stage fuel unit, nozzle assembly, control panel, all controls installed and wired.

1.Manual reset high limit control

2.Manual reset low water cutoff

3.Auxiliary low water cutoff

4.Combination low water cutoff and feeder

5.Alarm bells or horns

6.UL, CUL, CSD-1, FM, IRI or other insur-ance approved control systems

7.Control panel mounted on boiler

8.Indicating lights, as desired

9.Lead-lag systems for two or more boilers with or without outdoor reset control

10.Draft control system

11.Special construction: left hand, Knocked Down.

OPTIONAL CONSTRUCTION:

Steam boiler

Optional construction to ASME Power Boiler Code requirements for pressure exceeding 150 psi to maximum of 300 psi design pressure.

Optional construction to ASME Power BoilerCoderequirementsfortempera- turesexceeding240°Fand/orpressure exceeding 160 psi to maximum of 285° Foperatingand300°F designtempera- ture and 250 psi.

When ordering, please specify:

1.Boiler size

2.Supply and return tempera- tures required

3.Boiler relief valve setting

4.Type of fuel: natural, LP, or other gas and/or No. 2 oil

5.If gas, type, BTU content, specific gravity and pressure available

6.Electric power voltage, phase and frequency

7.Optional extra equipment or construction

8.Special approvals required (UL, CUL, CSD-1, FM, or IRI)

9.Altitude

Image 3
Contents Bryan Boilers Bryan CLM Series Boiler Specifications True flexible water tube Bryan CLM Series Steam & Hot Water Boilers

CLM Series specifications

The Bryan Boilers CLM Series represents a cutting-edge advancement in the realm of commercial water-tube boilers, designed to meet the rigorous demands of various industrial applications. Known for its reliability and efficiency, this series is particularly well-suited for those seeking a high-performance, compact boiler solution.

One of the main features of the CLM Series is its modular design, which allows for easy transportation and installation. The compact structure provides flexibility in space-constrained environments while ensuring optimal performance. This modularity also enables quick scalability, accommodating the changing needs of a business without the hassle of extensive modifications.

Another standout characteristic of the CLM Series is its enhanced efficiency. The series employs a unique combustion process that maximizes fuel utilization. This efficiency translates into significant cost savings for users, as the reduced fuel consumption leads to lower operating expenses. Moreover, the CLM boilers are designed to operate effectively with a range of fuel types, including natural gas, propane, and biofuels, making them versatile for diverse operational contexts.

The CLM Series also employs advanced control technologies. The integrated microprocessor controls enhance operational precision, allowing for adaptive response to varying load conditions. These intelligent controls ensure optimal combustion efficiency, precise temperature management, and minimized emissions. This aligns with increasingly stringent environmental regulations, allowing businesses to operate sustainably without sacrificing performance.

In terms of safety and reliability, the CLM Series is equipped with multiple safety features, including flame monitoring systems and pressure controls. These safety mechanisms work in concert to provide peace of mind for operators while minimizing the risks associated with boiler operations.

Another notable characteristic of the CLM Series is its impressive lifespan. Built with high-quality materials and robust engineering, these boilers are designed to endure heavy-duty usage across various applications. This durability not only reduces the frequency of replacement but also enhances overall system reliability.

In summary, the Bryan Boilers CLM Series stands out in the market as an efficient, reliable, and versatile solution for commercial and industrial heating needs. With its modular design, advanced control technologies, fuel flexibility, and a strong emphasis on safety and durability, the CLM Series is positioned as a leading choice for businesses seeking sustainable and high-performance boiler solutions.