Crown Boiler BWC150/225 installation instructions Assembly of Crown Concentric Venting

Page 13

C. Assembly of Crown Concentric Venting

WARNING

Failure to follow the instructions could result in flue gas leakage into the combustion air or indoor air, resulting in unsafe or unreliable operation.

Do not lubricate concentric gaskets with anything other than water.

Do not attempt to cut any piping except as permitted in this section. When cutting these sections, make sure all cuts are square and allow for proper insertion.

Do not attempt to try to mix this concentric pipe with other venting systems.

1)The components listed in Table 1.6 are required for 80/125mm and 100/150mm installations and are not supplied with the BWC150/225 boilers. Before starting assembly of the vent system, make sure that the planned installation is in accordance with the “Vent System Design” section of this manual and that all required vent components are on hand. These components are available through Crown distributors.

2)Cutting Straight Pipe - The following straight pipe sections may be cut:

80/125 Part #

100/150 Part #

Description

 

 

 

230517

230560

19 1/2” Straight

230515

230562

39” Straight

 

 

 

These sections have a plain male end (without beads - see Figure 1.9a). They are always cut from the male end. Sections not shown on the above list may not be cut. These sections have beads on the male end (Figure 1.9b).

To cut the straight sections listed above refer to Figure 1.10 and the following instructions:

FIGURE 1.9a: CUTTABLE STRAIGHT SECTION

FIGURE 1.9b: NON CUTTABLE STRAIGHT SECTION

11

Image 13 Contents
BWC Series Page Page Concentric Venting For BWC150 and BWC225 Page Summary of Horizontal Venting Options Horizontal Concentric Venting Vent Option 3,4 3c Positioning Vent Terminal Under Overhangs VENT/ AIR Intake Fitting Equivalent Length Vent Options 3,8 Concentric Vent Adapter Kit Installation Concentric Vent Adapter Assembly Assembly of Crown Concentric Venting 10 Cutting Straight Pipe 11a Joining Cuttable Pipe 12a Dimension L, Horizontal Terminal 12c Cutting Inner Pipe of Horizontal Terminal 13a Dimension H 13b Cutting Vertical Terminal 14 Chimney Chase Installation 15 Condensate Drain Line Assembly PN 980241 Rev BWC 12/07