White Rodgers 1F80-24 specifications Description, Precautions, Specifications

Page 1

 

1F80-24

WHITE-RODGERS

Programmable Electronic Digital Thermostat

INSTALLATION AND

 

 

OPERATION INSTRUCTIONS

 

 

Operator: Save these instructions for future use!

FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE.

DESCRIPTION

Your new White-Rodgers Digital Thermostat uses the technol- ogy of a solid-state microcomputer to provide precise time/ temperature control. This thermostat offers you the flexibility to design heating and cooling programs that fit your needs.

Features:

Battery powered (3 “AA” Energizer® alkaline batteries in- cluded)

Same program for all days of the week

Simultaneous heat and cool program storage

Four separate time/temperature settings per program

Preprogrammed temperature control

LCD continuously displays set point, and alternately dis- plays time and room temperature

Temperature override until next program period

Manual program override (HOLD temperature)

User may select either 12- or 24-hour clock display

°F/°C convertibility

Temperature range 45° to 90°F

Standard five terminals for single or dual transformer systems

B & O terminals for single stage heat pumps or damper operation

This thermostat is intended for use with a low voltage system; do not use this thermostat with a line voltage system. If in doubt about whether your wiring is millivolt, line, or low voltage, have it inspected by a qualified heating and air conditioning contractor or electrician.

Do not exceed the specification ratings.

All wiring must conform to local and national electrical codes and ordinances.

This control is a precision instrument, and should be handled carefully. Rough handling or distorting components could cause the control to malfunction.

PRECAUTIONS

!CAUTION

To prevent electrical shock and/or equipment dam- age, disconnect electric power to system at main fuse or circuit breaker box until installation is complete.

!WARNING

Do not use on circuits exceeding specified voltage. Higher voltage will damage control and could cause shock or fire hazard.

Do not short out terminals on gas valve or primary control to test. Short or incorrect wiring will damage thermostat and could cause personal injury and/or property damage.

ELECTRICAL DATA

Electrical Rating:

8 to 30 VAC 50/60 Hz. or D.C.

0.05 to 1.5 Amps (Load per terminal)

1.5Amps Maximum Total Load (All terminals combined)

THERMAL DATA

Setpoint Temperature Range:

45°F to 90°F (7°C to 32°C)

Operating Ambient Temperature Range:

32°F to 105°F

Operating Humidity Range:

0 to 90% RH (non-condensing)

Shipping Temperature Range:

-40°F to 150°F

SPECIFICATIONS

APPLICATIONS

For use with:

Standard heat/cool or heat only systems

Electric heat systems

Gas or oil fired systems

Gas systems with intermittent ignition devices (I.I.D.) and/ or vent dampers

Hydronic (hot water or steam) systems

Single-stage heat pump systems

Millivolt systems

DO NOT USE WITH:

Multi-stage systems

Systems exceeding 30 VAC and 1.5 amps

3-wire zoned hydronic heating systems

WHITE-RODGERS DIVISION

 

PART NO. 37-5287E

EMERSON ELECTRIC CO.

Printed in U.S.A.

Replaces 37-5287D

9797 REAVIS ROAD

 

9901

ST. LOUIS, MISSOURI 63123-5398

 

 

 

Image 1
Contents Specifications PrecautionsDescription Remove OLD Thermostat InstallationAttach Thermostat Base to Wall Check Thermostat Operation Turn on power to the systemFan Operation Heating SystemOperation Thermostat Buttons and SwitchesThermostat Base Cooling SystemProgramming Your Thermostat Operating FeaturesCheck Your Programming Entering Your ProgramPress SET Time once the programmed time will flash