GAS SUPPLY CONNECTIONS

GAS SUPPLY CONNECTIONS

The inlet gas connection of the boiler gas valve is 1/2". Provide an adequate gas piping supply line no smaller than 1/2", according to the chart below:

Maximum Equivalent Pipe Length (Feet)

1/2" Pipe 3/4" Pipe 1" Pipe 1 1/4" Pipe

MODEL NAT

PRO NAT

PRO NAT

PRO NAT

PRO

0030 &

 

 

 

 

 

 

 

 

0042

125

350

500

-

-

-

-

-

0066

60

160

175

460

-

-

-

-

0090

30

80

125

325

400

-

-

-

0135

15

40

60

155

200

500

-

-

0180

-

20

35

90

115

300

425

-

Gas piping must have a sediment trap ahead of the boiler gas controls, and a manual shutoff valve located outside the jacket. All gas piping should be tested after installation in accordance with local codes.

ManualUnion

Valve

Sediment Trap

Gas Valve

 

Fig. # 8192.0

CAUTION: The boiler and its manual shut off valve must be disconnected from the gas supply during any pres- sure testing of that system at test pressures in excess of 1/2 psig (3.45 KPA). Dissipate test pressure in the gas supply line before reconnecting the boiler and its manual shut off valve to gas supply line. FAILURE TO FOLLOW THIS PROCEDURE MAY DAMAGE THE GAS VALVE. OVER PRESSURED GAS VALVES ARE NOT COVERED BY WARRANTY. The boiler and its gas connections shall be leak tested before placing the appliance in operation. Use soapy water for leak test. DO NOT use open flame.

NOTE: Do not use teflon tape on gas line pipe thread.

Aflexible sealant suitable for use with Natural and Propane gases is recommended.

GAS PRESSURE-SPECIFICATIONS

Inches W.C. Regulator

Min. Max. Setting

Natural 7.0 14.0 3.5

Propane 12.0 14.0 11.0

The gas valve is provided with pressure taps to measure gas pressure upstream of the gas valve and downstream which is the same as the manifold pres- sure.

WATER CONNECTIONS & SYSTEM PIPING

The pipe size for water connections is shown on page 3. Typical piping systems are shown on pages 11 to 13.

The boiler is supplied as standard with a circulator and a built -in by-pass to insure the required minimum water flow in the boiler. The by-pass on models H-0135 and H-0180 is provided with an adjustable valve that is factory set in the full open position. The handle is shipped loose. The full open position is appropriate for most systems, and insures adequate flow through the boiler. If system flow is inadequate, (indicated by excessive temperature drop through the system) the by- pass valve can be throttled slightly. Care must be taken against over throttling which may lead to inadequate flow through the boiler and boiler harmonics (a humming sound from the heat exchanger). If adequate system flow cannot be obtained without causing harmonics, an additional pump is required. The factory mounted circulator will provide adequate water flow for systems designed at a 20°F temperature drop, and system pressure drop or head not exceeding that is shown below.

 

System

Maximum

Models

Flow

System Head

 

(GPM)

(Ft/Wtr)

H-0030

2.5

9.0

H-0042

3.5

8.0

H-0066

5.3

8.5

H-0090

7.3

6.5

H-0135

11.0

10.0

H-0180

14.6

7.0

When the total system head exceeds the available head pressures, a primary/secondary pumping system is recommended.

The minimum boiler operating temperature should be 105°F. When operating at low tempera- ture applications, ÐT (temperature rise) must be 20°F or less.

Propylene glycol solution is commonly used in the heating system when freeze protection is required. This will affect the system design and pump performance. As a "rule of thumb", 50% solution of propylene glycol will require the system flow (GPM) to increase by 14%, and the system head (Ft/Wtr) by 23% in order to maintain the same heat transfer load.

10