Raypak 0090B 0135B installation instructions Electrical Wiring

Models: 0090B 0135B

1 38
Download 38 pages 58.42 Kb
Page 14
Image 14
ELECTRICAL WIRING

ELECTRICAL WIRING

The electrical power supply requirement for these boilers is 115 volts, 60 Hz. Field wiring connections and electrical grounding must comply with the local codes, or in the absence of local codes, with the National Electrical Code, ANSI/NFPA 70-1987.Provide a sepa- rate fused circuit from the main electrical panel to the boiler, and a disconnecting means within sight of the boiler.

Remove the control box cover and make the power supply connections in the field wiring compartment. (See general location of controls drawing on page 18). The pump is supplied and factory wired to operate with the boiler. The "TH" wire leads are for the room thermostat or zone valve connections.

The room thermostat should be installed in accordance with the manufacturer's instructions. The thermostat heat anticipator should be set at 1.0 ampere (automatic ignition) and 0.60 ampere (standing pilot) for single zone installations. For multi-zone applications, the heat anticipator setting should be based on the ampere load in the thermostat circuit.

NOTE: If it is necessary to replace any of the original wiring, it must be replaced with 105°C wire or its equivalent, except 150° black wire must be replaced with 150°C wire or its equivalent. See wiring diagram key for 150°C wire indication.

WIRING DIAGRAM KEY

Fig.# 8096.2

14

Page 14
Image 14
Raypak 0090B 0135B installation instructions Electrical Wiring