4. SERVICING PROCEDURES

GENERAL LOCATION OF CONTROLS

CIRCULATOR

CONTROL BOX COMPONENT LOCATIONS MODELS 135 & 180

2-Staged Controller

Relay

Fast

Response Ignition Module

Temperature (Auto Ignition Only)

Sensor

Fig.#8195.1

VENT SENSOR

BYPASS VALVE

(MODELS 135 & 180 ONLY)

BYPASS LINE

TEMPERATURE

AND PRESSURE GAUGE

2-STAGED CONTROLLER

(MODEL 90 ONLY)

PRESSURE

RELIEF VALVE

RELAY

ADJUSTABLE

HIGH LIMIT

FIELD WIRING

COMPARTMENT

FAST RESPONSE TEMPERATURE SENSOR

IGNITION MODULE

(AUTO IGNITION ONLY)

TRANSFORMER

ROLL-OUT SENSOR

GAS VALVE

Fig.#8195.4

SEQUENCE OF OPERATION INTERMITTENT IGNITION DEVICE (IID)

Boilers equipped with the IID system will automatically light the pilot burner first and then the main burner, each time there is a call for heat from the room thermostat. Whenever the room thermostat is calling for heat, the circulator supplied with the boiler, will be energized and should be running. The ignition control module will also be energized to initiate the pilot ignition by opening the first main valve (pilot). At the same time, the electronic spark generator in the module produces a high voltage spark pulse output that lights the pilot burner. If the pilot burner does not light, the module will not energize the second main valve and the burners will not light. Ignition spark continues only until the timed trial for ignition period ends. Then, the module goes into safety shutdown or lockout. Lockout de-energizes the first main valve operator and closes the first main (pilot) valve in the gas control, stopping pilot gas flow. The ignition control system must be reset by setting the thermostat below room temperature for one minute or by turning off power to the module for one minute. When the pilot flame is established, flame rectification circuit is completed between the sensor and burner ground. The flame sensing circuit in the module detects the flame current, shuts off the spark generator and energizes the second main valve operator which opens the second main valve. This allows gas to flow to the burners where it is ignited by the pilot burner flame. When the thermostat is satisfied, the valve operators are de-energized shutting off the pilot and main burners, and also the circulator.

22

Page 22
Image 22
Raypak 0090B 0135B Servicing Procedures, General Location of Controls, Control BOX Component Locations Models 135