Jotul GF 600 DV manual Gas Connection, Gas Pressure, Leak test

Page 17

Gas Connection

NOTE: IF THE OPTIONAL BLOWER KIT (# 129161) IS TO BE INSTALLED ON THE STOVE AT THE TIME OF THE INSTALLATION OR IN THE FUTURE, THE GAS SUPPLY LINE SHOULD BE INSTALLED AS CLOSE TO THE FLOOR AS POSSIBLE. USE OF A 90° ELBOW DIRECTLY OFF THE VALVE TO ALLOW FOR ADEQUATE CLEARANCE FOR THE BLOWER. See Figure 15.

The gas supply line connection is made to the valve just inside the left rear leg. The Gas supply line should be 3/8" or 1/2" diameter, or the appropriate size to provide sufficient gas pressure to the valve regardless of the input setting.

The use of Flexible Gas Appliance Connectors is acceptable in many areas in the U.S., however, Canadian methods vary depending on local code.

ALL INSTALLATIONS MUST COMPLY WITH LOCAL CODE OR IN THE ABSENCE OF LOCAL CODE, MUST COMPLY WITH THE MOST RECENT EDITION OF THE NATIONAL FUEL GAS CODE ANSI Z223.1/NFPA 54 OR CAN-B149.

All codes require a gas shutoff valve (gas cock) and union to be installed in the supply line and in the same room as the appliance for servicing and maintenance. See Figure 17.

T-handle gas cocks are required in Massachu- setts in compliance with Code 248 CMR.

Secure all joints tightly using appropriate tools and sealing compounds (for propane units be sure to use compounds that are propane resistant). Turn on gas supply and test for gas leaks using a soapy water solution. Never use an open flame to check for leaks.

Figure 17. Gas supply valve types and fittings.

Leak test:

1.Mix a 50-50 solution of water and dish soap.

2.Light appliance- see lighting instructions on page 22 of this manual or on the stove’s rating plate.

3.Brush or spray all joints and connections with the soapy water solution.

4.If bubbles appear at any connection or seam or a gas odor is detected immediately turn gas control knob to the OFF position.

5.Tighten or reconnect the leaking joint and retest for any gas leaks.

Gas Pressure

It is important that the correct pressure is estab- lished at the time of the installation. Proper gas pressure provides a consistent flow of gas to the appliance and is instrumental in checking for gas leaks. The gas control valve on the stove is equipped with pressure test points for gauge connections. The gauge connections are located on the front of the valve under the On/Off/Pilot- knob. See Fig. 18. Gauge connections are identified by:

E for inlet or supply pressure ( the amount of gas coming to the valve.)

A for manifold pressure (the amount of gas that is coming out of the valve to the burner.)

ALWAYS TEST PRESSURES WITH VALVE CONTROL KNOB SET ON HIGH.

Control Valve

E A

Figure 18. Inlet and Manifold pressure test points.

INLET GAS PRESSURES (inches water column)

 

MIN

MAX

NATURAL GAS

5.0 WC

7.0 WC

PROPANE

11.0 WC

13.5 WC

17

Image 17
Contents Jøtul GF 600 DV Firelight Direct Vent Gas Heater Installation and Operation InstructionsWelcome to Jøtul Table of Contents Input Rates GF 600 DV Firelight SpecificationsSuggested Tools for Installation and Service General Information Safety InformationGlass Front Optional Forced Air Blower KitHearth Requirements Installation RequirementsLocation Alcove Minimum Clearances from the Stove to Combustibles See FigsVertical Run Air Inlet Restrictor Plate Installation Exhaust Restrictor Plate InstallationVent Requirements Vent RestrictionCO-LINEAR Installations Co-linear Hearthmount InstallationExhaust Restrictors Required on ALL Always Maintain the ProperGF600 DV, the maximum horizontal Simpson Dura-Vent Chimney Conversion KitMin Vertical Venting and TerminationSnorkel Cap Horizontal TerminationStove must terminate only with a Horizontal Termination Clearance Conversion Kit Contents Mobile Home InstallationFuel Conversion Conversion Kit LPG #154391,NG #Mm for NG #48 for LP Gas Conversion ProcedureNever USE AN Open Flame to Check for GAS Leaks Remove the valve skirt for better accessGas Pressure Gas ConnectionLeak test Always Test Pressures with Valve Control Knob SET on HighU.S High Altitude AdjustmentCanada Manifold PressuresHigh Altitude Orifice Chart Air Shutter Adjustment / Flame AppearanceDerating Procedure Pin Install the Log SetPlacement of the Embers Optional Controls Remote ControlSystem Check Wall ThermostatSnapstat / Blower Mounting Bracket assembly Optional Blower Kit InstallationOperation Connect the Wiring HarnessName of Installer MaintenanceModel Name Date of PurchaseFirelight GF 600 DV Parts Identification Accessories Jøtul GF 600 DV Firelight Replacement PartsHardware Bag Contents Lighting Instructions Jøtul North America

GF 600 DV specifications

The Jotul GF 600 DV is a distinctive gas fireplace that seamlessly combines luxury with functionality, making it a popular choice for homeowners seeking both style and warmth. As part of the well-regarded Jotul line, this model is designed with an emphasis on efficiency and aesthetic appeal, catering to varied interior designs from contemporary to traditional.

One of the main features of the Jotul GF 600 DV is its impressive heating capacity. With the ability to produce up to 30,000 BTUs, it efficiently warms spaces up to 1,500 square feet, making it ideal for living rooms, dens, or any area in need of supplemental heat. The fireplace operates on natural gas or propane, allowing homeowners flexibility in fuel choice based on availability and preference.

The GF 600 DV boasts a striking design, featuring a large glass front that offers an unobstructed view of the mesmerizing flames. This model is available in several finishes, including cast iron, which not only enhances durability but also retains heat longer, thus improving heating efficiency. The realistic gas logs add to the authenticity of the fire experience, while the flame control allows users to adjust the fire’s intensity with ease, creating the perfect ambiance for any occasion.

In terms of technology, the Jotul GF 600 DV is built with advanced burner systems that provide a realistic flame pattern and efficient combustion. The model operates with direct vent technology, which ensures that the fireplace draws air from the outside for combustion, thereby eliminating any risk of indoor air contamination. This feature also enhances energy efficiency, as the fireplace can efficiently maintain indoor temperatures without drawing heated air out of the home.

Another significant characteristic of the Jotul GF 600 DV is its ease of installation and operation. The unit can be installed in various types of framing and can be vented vertically or horizontally to accommodate different house designs. Additionally, it can be complemented with optional remote controls or wall thermostats, providing convenience and greater control over heating and comfort levels without manual adjustments.

Safety is also a key consideration in the design of the Jotul GF 600 DV. It includes features such as an automatic shut-off mechanism that activates in case of malfunction or irregular operation. This commitment to safety ensures peace of mind for users and their families.

In summary, the Jotul GF 600 DV is not only a functional heating solution but also a stylish addition to any home. With its blend of advanced technology, efficiency, and aesthetic qualities, it exemplifies modern fireplace design, meeting the needs of contemporary living while ensuring warmth and comfort throughout the colder months.