Desa VYM27PR installation manual Troubleshooting, Observed Problem Possible Cause

Page 17

OWNER’S MANUAL

TROUBLESHOOTING

Note: For additional help, visit DESA International’s technical service web site at www.desatech.com.

Note: All troubleshooting items are listed in order of operation.

WARNING: Turn off heater and let cool before servicing. Only a qualified service person should service and repair heater.

CAUTION: Never use a wire, needle, or similar object to clean ODS/pilot. This can damage ODS/ pilot unit.

OBSERVED PROBLEM

POSSIBLE CAUSE

REMEDY

When ignitor button is pressed, there is no spark at ODS/pilot

1.Ignitor electrode not connected to igni- tor cable

2.Ignitor cable pinched or wet

3.Piezo ignitor nut is loose

4.Broken ignitor cable

5.Bad piezo ignitor

6.Ignitor electrode broken

7.Ignitor electrode positioned wrong

1.Reconnect ignitor cable

2.Free ignitor cable if pinched by any metal or tubing. Keep ignitor cable dry

3.Tighten nut holding piezo ignitor to base panel of log set. Nut is located behind base panel.

4.Replace ignitor cable

5.Replace piezo ignitor

6.Replace piezo ignitor

7.Replace piezo ignitor

When ignitor button is pressed, there is spark at ODS/pilot but no ignition

1.Gas supply turned off or manual shutoff valve closed

2.Control knob not in PILOT position

3.Control knob not pressed in while in PILOT position

4.Air in gas lines when installed

5.Depleted gas supply

6.ODS/pilot is clogged

7.Gas regulator setting is not correct

1.Turn on gas supply or open manual shutoff valve

2.Turn control knob to PILOT position

3.Press in control knob while in PILOT position

4.Continue holding down control knob. Repeat igniting operation until air is re- moved

5.Contact local propane gas company

6.Clean ODS/pilot (see Cleaning and Maintenance, page 21) or replace ODS/ pilot assembly

7.Replace gas control

ODS/pilot lights but flame goes out when control knob is released

1.Control knob not fully pressed in

2.Control knob not pressed in long enough

3.Manual shutoff valve not fully open

4.Pilot flame not touching thermocouple, which allows thermocouple to cool, causing pilot flame to go out. This prob- lem could be caused by one or both of the following:

A)Low gas pressure

B)Dirty or partially clogged ODS/pilot

5.Thermocouple connection loose at con- trol valve

6.Thermocouple damaged

7.Control valve damaged

1.Press in control knob fully

2.After ODS/pilot lights, keep control knob pressed in 30 seconds

3.Fully open manual shut-off valve

4.A) Contact local propane gas company

B) Clean ODS/pilot (see Cleaning and Maintenance, page 21) or replace ODS/ pilot assembly

5.Hand tighten until snug, then tighten 1/4 turn more

6.Replace thermocouple

7.Replace control valve

www.desatech.com

Continued

104675

17

Image 17
Contents Remote Control Ready Model OWNER’S Operation and Installation ManualWhat to do if YOU Smell GAS Save this manual for future referenceVanguard FLAME-MAX Unvented PROPANE/LP GAS LOG Heater Safety InformationRemote Control Accessories Product FeaturesProduct Identification Local CodesProviding Adequate Ventilation AIR for Combustion and VentilationUnusually Tight Construction Confined and Unconfined SpaceDetermining if You Have a Confined or Unconfined Space AIR for Combustion VentilationDetermining FRESH-AIR Flow for Heater Location Ventilation Air From Inside Ventilation AIRBuilding Ventilation Air From OutdoorsInstallation Clearances InstallationCheck GAS Type Minimum Fireplace Clearance to Combustible MaterialsMinimum Noncombustible Material Clearances If Not Using MantelIf Using Mantel Mantel Clearances Determining Minimum Mantel Clearance When Using a HoodDetermining Minimum Mantel Clearance Floor ClearancesInstalling Heater Base Assembly Installing Damper Clamp Accessory for Vented OperationInstallation Items Needed Chimney Minimum Permanent Height ft Flue Opening sq. insAttaching Flexible Gas Hose to Heater Connecting to GAS SupplyPressure Testing Gas Supply Piping System Pressure Testing Heater Gas ConnectionsChecking GAS Connections Test Pressures In Excess Of 1/2 PsigInstalling Bottom Log #1 Installing LogsLighting Instructions For Your Safety Read Before LightingOperating Heater Optional Remote Operation Manual Lighting ProcedureTo Turn OFF GAS To Appliance Pilot Flame Pattern Inspecting BurnersBurner Primary AIR Holes Main BurnerObserved Problem Possible Cause TroubleshootingMaintenance, Observed Problem Possible Cause RemedyTop Gas leak. See Warning statement atSpecifications Wiring Diagram Replacement PartsService Hints Technical ServiceLogs Cleaning and MaintenanceCleaning Burner INJEC- TOR Holder and Pilot AIR Inlet Hole VYM27PR Illustrated Parts BreakdownDescription QTY Parts ListAccessories 104675 Limited Warranty VENT-FREE Propane GAS LOG Heaters Warranty Information