Desa VYM27PR installation manual Ventilation AIR, Ventilation Air From Inside, Building

Page 6

VANGUARD FLAME-MAX®

UNVENTED PROPANE/LP GAS LOG HEATER

AIR FOR COMBUSTION AND VENTILATION

Continued

VENTILATION AIR

Ventilation Air From Inside

Ventilation

Grills

Into Adjoining

12"

Ventilation Grills

Into Adjoining Room,

Room,

Or

Option 2

Option 1

Remove

Building

This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining unconfined space, you must pro- vide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 2). You can also remove door into adjoining room (see op- tion 3, Figure 2). Follow the National Fuel Gas Code NFPA 54/ANS Z223.1, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

WARNING: Rework work- sheet, adding the space of the adjoining unconfined space. The combined spaces must have enough fresh air to supply all appliances in both spaces.

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts. You must provide two per- manent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces.

IMPORTANT: Do not provide openings for inlet or outlet air into attic if attic has a thermostat-controlled power vent. Heated air entering the attic will activate the power vent.

Door into Adjoining Room, Option 3

12"

Figure 2 - Ventilation Air from Inside Building

Ventilated

Outlet Attic

Air

Outlet

 

Air

To Attic

 

To

Crawl

Space

Inlet

Air

Inlet Air

 

Ventilated

 

 

Crawl Space

 

 

Figure 3 - Ventilation Air from Outdoors

6

104675

Image 6
Contents What to do if YOU Smell GAS OWNER’S Operation and Installation ManualRemote Control Ready Model Save this manual for future referenceSafety Information Vanguard FLAME-MAX Unvented PROPANE/LP GAS LOG HeaterProduct Identification Product FeaturesRemote Control Accessories Local CodesUnusually Tight Construction AIR for Combustion and VentilationProviding Adequate Ventilation Confined and Unconfined SpaceAIR for Combustion Ventilation Determining FRESH-AIR Flow for Heater LocationDetermining if You Have a Confined or Unconfined Space Building Ventilation AIRVentilation Air From Inside Ventilation Air From OutdoorsCheck GAS Type InstallationInstallation Clearances Minimum Fireplace Clearance to Combustible MaterialsIf Not Using Mantel If Using MantelMinimum Noncombustible Material Clearances Determining Minimum Mantel Clearance Determining Minimum Mantel Clearance When Using a HoodMantel Clearances Floor ClearancesInstallation Items Needed Installing Damper Clamp Accessory for Vented OperationInstalling Heater Base Assembly Chimney Minimum Permanent Height ft Flue Opening sq. insConnecting to GAS Supply Attaching Flexible Gas Hose to HeaterChecking GAS Connections Pressure Testing Heater Gas ConnectionsPressure Testing Gas Supply Piping System Test Pressures In Excess Of 1/2 PsigInstalling Logs Installing Bottom Log #1For Your Safety Read Before Lighting Operating HeaterLighting Instructions Manual Lighting Procedure To Turn OFF GAS To ApplianceOptional Remote Operation Burner Primary AIR Holes Inspecting BurnersPilot Flame Pattern Main BurnerTroubleshooting Observed Problem Possible CauseObserved Problem Possible Cause Remedy Maintenance,Gas leak. See Warning statement at TopService Hints Wiring Diagram Replacement PartsSpecifications Technical ServiceCleaning and Maintenance Cleaning Burner INJEC- TOR Holder and Pilot AIR Inlet HoleLogs Illustrated Parts Breakdown VYM27PRParts List Description QTYAccessories 104675 Warranty Information Limited Warranty VENT-FREE Propane GAS LOG Heaters