Desa VN600BA Operating Heater, Checking GAS Connections, For Your Safety Read Before Lighting

Page 10

®

BLUE FLAME NATURAL GAS HEATER

INSTALLATION

Continued

CHECKING GAS

CONNECTIONS

WARNING: Test all gas pip- ing and connections for leaks after installing or servicing. Cor- rect all leaks at once.

WARNING: Never use an open flame to check for a leak. Apply a mixture of liquid soap and water to all joints. Bubbles forming show a leak. Correct all leaks at once.

Pressure Testing Gas Supply Piping System

Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)

1.

Disconnect appliance with its appliance

 

main gas valve (control valve) and equip-

 

ment shutoff valve from gas supply pip-

 

ing system. Pressures in excess of 1/2 psig

 

will damage heater regulator.

2.

Cap off open end of gas pipe where

 

equipment shutoff valve was connected.

3.

Pressurize supply piping system by either

 

using compressed air or opening main gas

 

valve located on or near gas meter.

4.

Check all joints of gas supply piping

 

system. Apply mixture of liquid soap

 

and water to gas joints. Bubbles form-

 

ing show a leak.

5.

Correct all leaks at once.

3.Check all joints from gas meter to equipment shutoff valve (see Figure 14). Apply mixture of liquid soap and water to gas joints. Bubbles forming show a leak.

4.Correct all leaks at once.

Pressure Testing Heater Gas Connections

1.Open equipment shutoff valve (see Fig- ure 13).

2.Open main gas valve located on or near gas meter.

3.Make sure control knob of heater is in the OFF position.

4.Check all joints from equipment shutoff valve to control valve (see Figure 14). Apply mixture of liquid soap and wa- ter to gas joints. Bubbles forming show a leak.

5.Correct all leaks at once.

6.Light heater (see Operating Heater, pages 10 and 11). Check the rest of the internal joints for leaks.

7.Turn off heater (see To Turn Off Gas To Appliance, page 11).

8.Replace front panel.

Open

Equipment

Shutoff

Valve

O

Closed

Figure 13 - Equipment Shutoff Valve

OPERATING

HEATER

FOR YOUR SAFETY

READ BEFORE

LIGHTING

WARNING: If you do not fol- low these instructions exactly, a fire or explosion may result caus- ing property damage, personal injury or loss of life.

A.This appliance has a pilot which must be lighted by hand. When lighting the pilot, follow these instructions exactly.

B.BEFORE LIGHTING smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.

WHAT TO DO IF YOU SMELL GAS

Do not try to light any appliance.

Do not touch any electric switch; do not use any phone in your building.

Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.

If you cannot reach your gas sup- plier, call the fire department.

C.Use only your hand to push in or turn the gas control knob. Never use tools. If the knob will not push in or turn by hand, don’t try to repair it, call a qualified service technician or gas supplier. Force or attempted repair may result in a fire or explosion.

6. Reconnect heater and equipment

shutoff valve to gas supply. Check re-

connected fittings for leaks.

Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)

1.Close equipment shutoff valve (see Fig- ure 13).

2.Pressurize supply piping system by ei- ther using compressed air or opening main gas valve located on or near gas meter.

 

Control Valve Location

D. Do not use this appliance if any part

 

 

 

 

has been under water. Immediately

 

 

call a qualified service technician to

 

 

inspect the appliance and to replace

 

 

any part of the control system and

Gas Meter

 

any gas control which has been un-

 

 

der water.

 

Equipment

 

Shutoff

 

 

Valve

 

Figure 14 - Checking Gas Joints

10

104271

Image 10
Contents OWNER’S Operation and Installation Manual VN600BA What to do if YOU Smell GASSafety Information Blue Flame Natural GAS HeaterLocal Codes Product FeaturesProduct UnpackingUnusually Tight Construction AIR for Combustion and VentilationProviding Adequate Ventilation Confined and Unconfined SpaceDetermining FRESH-AIR Flow for Heater Location AIR for Combustion VentilationDetermining if You Have a Confined or Unconfined Space Ventilation Air From Inside Building Ventilation AIRVentilation Air From Outdoors Installing Heater to Wall InstallationInstallation Items Locating HeaterPlacing Heater On Mounting Screws Installing Two Mounting ScrewsInstalling Bottom Mounting Screw Removing Front Panel Of HeaterConnecting to GAS Supply Gas ConnectionPressure Testing Heater Gas Connections For Your Safety Read Before LightingPressure Testing Gas Supply Piping System Operating HeaterTo Turn OFF GAS To Appliance Manual Lighting ProcedureLighting Instructions Shutting Off HeaterCleaning and Maintenance Inspecting BurnerTroubleshooting Observed Problem Possible Cause RemedyMaintenance, Observed Problem Possible Cause Illustrated Parts Breakdown VN600BAParts List KEY Part Number Description QTYTechnical Service SpecificationsReplacement Parts Service Hints104271 Warranty Information

VN600BA specifications

The Desa VN600BA is a versatile and efficient vent-free heater that has garnered attention for its performance and user-friendly design. This model stands out in the market due to its blend of advanced technologies and practical features, making it an attractive choice for homeowners seeking reliable heating solutions.

One of the key features of the Desa VN600BA is its innovative vent-free design, which allows for easy installation in various settings without the need for ductwork. This not only reduces installation costs but also enhances flexibility in terms of placement, enabling homeowners to heat different areas of their homes effectively. The heater operates using natural gas or propane, providing options for users based on their fuel availability and preferences.

The VN600BA is equipped with a powerful heating capacity, capable of delivering up to 30,000 BTUs per hour. This makes it suitable for heating spaces up to 1,000 square feet, ensuring comfortable temperatures during colder months. The adjustable thermostat feature allows for precise temperature control, enhancing user comfort while optimizing energy consumption. Additionally, it includes a safety pilot system that monitors the flame and automatically shuts off the gas flow in case of any irregularities, ensuring safety at all times.

The aesthetic appeal of the Desa VN600BA cannot be overlooked. With its sleek design and attractive finish, it complements different interior styles while serving as a functional heating solution. The heater also features a convenient control panel that allows users to operate the device with ease.

In terms of energy efficiency, the Desa VN600BA is designed to minimize waste while providing effective heating. Being vent-free, it utilizes the fuel it consumes more efficiently compared to traditional heating systems, translating to lower utility bills. Moreover, its design promotes complete combustion, which contributes to cleaner operation and reduced environmental impact.

In summary, the Desa VN600BA vent-free heater is characterized by its efficient heating capacity, flexible installation options, and user-friendly features. Its advanced safety systems, combined with an attractive design, make it a desirable choice for homeowners looking for a reliable and efficient heating solution. Whether for supplemental or primary heating, the VN600BA offers a compelling combination of performance and style, ensuring that it remains a preferred option in the market.