INSTALLATION
Continued
3.For carpeted floors, make a small cut with a sharp knife at marked locations prior to drill- ing. If mounting base to a wood floor, drill 1/8 inch diameter hole, 3/4 inch deep. (Do not use anchors in wood floors).
If mounting base to a concrete floor, drill with 1/4 inch diameter concrete drill bit, 13/8 inches into floor. Insert anchors completely into holes.
4.Reposition heater with base feet over holes. Secure base to floor with wood screws. See Figure 13, page 11.
CONNECTING TO GAS SUPPLY
WARNING: This appliance requires a 3/8" NPT (National Pipe Thread) inlet connection to the pressure regulator.
WARNING: A qualified ser- vice person must connect heater to gas supply. Follow all local codes.
WARNING: For natural gas, never connect heater to private
IMPORTANT: For natural gas, check gas line pressure before connecting heater to gas line. Gas line pressure must be no greater than 10.5 inches of water. If gas line pressure is higher, heater regu-
For propane/LP gas, the installer must supply an external regulator. The external regulator will re- duce incoming gas pressure. You must reduce in- coming gas pressure to between 11 and 14 inches of water. If you do not reduce incoming gas pres- sure, heater regulator damage could occur. Install the external regulator with the vent pointing down as shown in Figure 14. Pointing the vent down protects it from freezing rain or sleet.
CAUTION: Use only new, black iron or steel pipe. Inter-
Typical Inlet Pipe Diameters
10,000/20,000 Btu/Hr Models - 3/8" or greater
30,000 Btu/Hr Models - 1/2" or greater
Installation must include equipment shutoff valve, union, and plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge hook up. NPT tap must be upstream from heater (see Figure 15, page 13). IMPORTANT: Install an equipment shutoff valve in an accessible location. The equipment shutoff valve is for turning on or shutting off the gas to the appliance.
Apply pipe joint sealant lightly to male NPT threads. This will prevent excess sealant from go- ing into pipe. Excess sealant in pipe could result in clogged heater valves.
lator damage could occur.
CAUTION: For propane/LP gas,neverconnectheaterdirectly to the propane/LP supply. This heater requires an external regu- lator (not supplied). Install the ex- ternal regulator between the heater and propane/LP supply.
Propane/LP Supply Tank
External Regulator
Vent
Pointing
Down
Figure 14 - External Regulator With Vent
Pointing Down
12 | www.desatech.com |