Desa Tech CBP20T, CBN20T, CBP30T, CBN30T Connecting to GAS Supply, Typical Inlet Pipe Diameters

Page 11

INSTALLATION

Connecting To Gas Supply

11

INSTALLATION

Continued

CONNECTING TO GAS SUPPLY

WARNING: This appliance requires a 3/8" NPT (National Pipe Thread) inlet connection to the pres- sure regulator.

WARNING: A qualified service person must con- nect heater to gas supply. Follow all local codes.

WARNING: For natural gas, never connect heater to private (non-utility) gas wells. This gas is com- monly known as wellhead gas.

Typical Inlet Pipe Diameters

20,000 Btu/Hr Models - 3/8" or greater

30,000 Btu/Hr Models - 1/2" or greater

Installation must include equipment shutoff valve, union, and plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge hook up. NPT tap must be upstream from heater (see Figure 15).

IMPORTANT: Install an equipment shutoff valve in an accessible location. The equipment shutoff valve is for turning on or shutting off the gas to the appliance.

Apply pipe joint sealant lightly to male NPT threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged heater valves.

IMPORTANT: For natural gas, check gas line pressure before connecting heater to gas line. Gas line pressure must be no greater than 14 inches of water. If gas line pressure is higher, heater regulator damage could occur.

CAUTION: For propane/LP gas, never connect heater directly to the propane/LP supply. This heater requires an external regulator (not supplied). Install the external regulator between the heater and pro- pane/LP supply.

For propane/LP gas, the installer must supply an external regulator. The external regulator will reduce incoming gas pressure. You must reduce incoming gas pressure to between 11 and 14 inches of water. If you do not reduce incoming gas pressure, heater regulator damage could occur. Install the external regulator with the vent pointing down as shown in Figure 14. Pointing the vent down protects it from freezing rain or sleet.

WARNING: Use pipe joint sealant that is resistant to liquid petroleum (LP) gas.

Install sediment trap in supply line as shown in Figure 15. Locate sediment trap where it is within reach for cleaning. Locate sediment trap where trapped matter is not likely to freeze. A sediment trap traps moisture and contaminants. This keeps them from going into heater controls. If sediment trap is not installed or is installed wrong, heater may not run properly.

IMPORTANT: Hold the pressure regulator with wrench when connecting it to gas piping and/or fittings. Do not over tighten pipe connection to regulator. The regulator body could be damaged.

Pressure

Note: Burner

bracket not

Regulator

shown for

 

clarity

Propane/LP

Supply

Tank

External

Regulator

Vent

Pointing

Down

 

3/8" NPT

 

 

Pipe Nipple

Heater

 

 

 

Tee Joint

Cabinet

 

Ground Joint Union

Test

Reducer

 

Bushing to

Equipment

Gauge

Connection*

1/8" NPT

Shutoff Valve *

 

1/8" NPT

Natural Gas

 

Plug Tap

 

From Gas Meter

 

 

 

Tee

(5" W.C. to 10.5"

 

Joint

W.C. Pressure)

Figure 14 - External Regulator With Vent Pointing Down

CAUTION: Use only new, black iron or steel pipe. Internally-tinned copper tubing may be used in certain areas. Check your local codes. Use pipe of large enough diameter to allow proper gas volume to heater. If pipe is too small, undue loss of volume will occur.

Sediment

 

 

Pipe

 

 

3"

Propane/LP

 

 

 

 

 

 

 

 

Trap

 

 

Nipple

 

 

 

Minimum

From External

 

 

 

 

 

 

Cap

 

 

 

Regulator

 

 

 

 

 

 

 

 

 

(11" W.C. to 14"

Figure 15 - Gas Connection

 

 

 

W.C. Pressure)

 

 

 

 

*A CSA design-certified equipment shutoff valve with 1/8" NPT tap is an acceptable alternative to test gauge connection. Purchase the optional CSA design-certified equipment shutoff valve from your dealer. See Accessories, page 24.

For morevisit www..com

107882-01E

Image 11
Contents What to do if YOU Smell GAS Safety Information Installation ManualSafety Information Table of ContentsLocal Codes Product FeaturesProduct Identification UnpackingConfined and Unconfined Space AIR for Combustion and VentilationProviding Adequate Ventilation Unusually Tight ConstructionDetermining if You Have a Confined or Unconfined Space Determining FRESH-AIR Flow for Heater LocationVentilation Air From Outdoors Ventilation AIRVentilation Air From Inside Building Locating Heater InstallationInstallation Items Check GAS TypeThermostat Sensing Bulb Installing Heater to WallPlacing Heater On Mounting Bracket Attaching Mounting Bracket To WallMounting Base Feet to Heater Installing Bottom Mounting ScrewsMounting Base Feet to Floor Where required by local code Mounting Heater to FloorTypical Inlet Pipe Diameters Connecting to GAS SupplyChecking GAS Connections Pressure Testing Heater Gas ConnectionsPressure Testing Gas Supply Piping System Lighting Instructions For Your Safety Read Before LightingOperating Heater Thermostat Control Operation Manual Lighting ProcedureInspecting Heater To Turn OFF GAS To ApplianceODS/PILOT and Burner Cleaning MaintenanceCleaning Burner Pilot AIR Inlet Burner Flame PatternService Publications SpecificationsService Hints Technical ServiceObserved Problem Possible Cause TroubleshootingObserved Problem Possible Cause Remedy Gas leak. See Warning statement at CBN20 CBP20 Illustrated Parts BreakdownKEY Part Number for CBN20 CBP20 Description QTY Parts ListCBN20T, CBP20T CBN30T, CBP30T NJF 8C Accessories Replacement PartsOwners Registration Form For Com Parts Centrals Washer Equipment Co Laporte’s Parts & ServiceWarranty Information