Desa Tech CGN20TA installation manual Determining FRESH-AIR Flow for Heater Location

Page 5

OWNER’S MANUAL

FRESH AIR FOR COMBUSTION AND VENTILATION

Continued

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

Use this worksheet to determine if you have a confined or unconfined space.

Space: Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.

1.Determine the volume of the space (length x width x height).

Length x Width x Height =

__________ cu. ft. (volume of space)

Example: Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or open- ings, add the volume of these rooms to the total volume of the space.

2.Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.

_______________ (volume of space)

÷50 cu. ft. = (Maximum Btu/Hr the space can support)

Example: 2560 cu. ft. (volume of space) ÷ 50 cu. ft. = 51.2 or 51,200 (maximum Btu/Hr the space can sup- port)

3.Add the Btu/Hr of all fuel burning ap- pliances in the space.

Vent-free heater __________ Btu/Hr Gas water heater* ________ Btu/Hr Gas furnace _____________ Btu/Hr Vented gas heater _________ Btu/Hr

Gas fireplace logs ________ Btu/Hr

Other gas appliances* +

___ Btu/Hr

Total

=

___ Btu/Hr

Example:

 

 

 

Gas water heater

40,000

Btu/Hr

Vent-free heater

+ 20,000

Btu/Hr

Total

= 60,000 Btu/Hr

*Do not include direct-vent gas appli- ances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

__________ Btu/Hr (maximum the

space can support)

__________ Btu/Hr (actual amount of

Btu/Hr used)

Example: 51,200 Btu/Hr (maximum the space can support)60,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a con- fined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoining room or add ventila- tion grills between rooms. See Ventila- tion Air From Inside Building, page 6.

B.Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 6.

C.Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

Continued

104190

5

Image 5
Contents What to do if YOU Smell GAS Blue Flame VENT-FREE Natural GAS HeaterCGN20TA Safety InformationProduct Identification Product FeaturesLocal Codes UnpackingProviding Adequate Ventilation Fresh AIR for Combustion and VentilationUnusually Tight Construction Confined and Unconfined SpaceDetermining if You Have a Confined or Unconfined Space Determining FRESH-AIR Flow for Heater LocationVentilation Air From Outdoors Ventilation AIRVentilation Air From Inside Building Installation Items InstallationCheck GAS Type Locating HeaterThermostat Sensing Bulb Installing Heater to WallPlacing Heater On Mounting Bracket Installing Bottom Mounting ScrewsAttaching Mounting Bracket To Wall Typical Inlet Pipe Diameters Connecting to GAS SupplyPressure Testing Heater GAS Connections Pressure Testing GAS Supply Piping SystemChecking GAS Connections Test Pressures In Excess Of 1/2Operating Heater For Your Safety Read Before LightingLighting Instructions To Turn OFF GAS To ApplianceInspecting Burner Manual Lighting ProcedureThermostat Control Operation Pilot Flame PatternObserved Problem Possible Cause Remedy TroubleshootingMaintenance, Gas leak. See Warning statement at Service Publications Replacement Parts Cleaning and Maintenance SpecificationsTechnical Service Service HintsFBD Parts CentralsManual Shutoff AccessoriesFAN Kits GA3100A and GA3200TA CGN20TA Illustrated Parts BreakdownKEY Part Number Description QTY Parts ListCGN20TA 104190 Warranty Information