Hearth and Home Technologies SL-750TR-D, SL-950TR-D, SL-550TR-D Fire Risk. Explosion Risk

Page 34

Installing Wall Shield Firestops and Horizontal Termination Cap (SL Series Pipe ONLY)

WARNING

Fire Risk

Exhaust Fumes Risk

Impaired Performance of Appliance

Ensure vent components are locked together correctly.

Pipe may separate if not properly joined.

ForHorizontalRuns-WallshieldfirestopsareREQUIREDon bothsidesofacombustiblewallthroughwhichtheventpasses.

NOTE: Model SLK-01TRD does not need an exterior wall shield firestop on an exterior combustible wall.

To install wall shield firestops for horizontal runs that pass through either interior or exterior walls:

Cut a 10 in. x 10 in. (254mm x 254mm) hole for SL-D- series pipe. The center of the framing hole is one (1) inch (25.4mm) above the center of the horizontal vent pipe.

Position the wall shield firestops on both sides of the hole previously cut and secure the wall shield firestops with nails or screws.

The heat shields of the wall shield firestops MUST BE placed towards the top of the hole.

Continue the vent run through the wall shield firestops.

WARNING

Fire Risk. Explosion Risk.

Do NOT pack insulation or other combustibles between firestops.

ALWAYS maintain specified clearances around venting and firestop systems.

Install firestops as specified.

Failure to keep insulation or other material away from vent pipe may cause fire.

Installing the Horizontal Termination Cap

Vent termination must not be recessed in the wall. Siding may be brought to the edge of the cap base.

Flash and seal as appropriate for siding material at out side edges of cap.

When installing a horizontal termination cap, follow the cap location guidelines as prescribed by current ANSI Z223.1 and CAN/CGA-B149installation codes.

10 in. (254mm)

1 in. (25.4 mm)

10 in. (254mm)

VENT PIPE

Figure 8.14 Hole and Vent Pipe

HEAT SHIELD

TRIM HEAT SHIELD IF TOO LONG, ADD TO SHIELD IF TOO SHORT

WALL SHIELD

FIRESTOP

(EXTERIOR)

WALLSHIELD

FIRESTOP (INTERIOR)

WARNING

Burn Risk

• Local codes may require installation of a cap shield to prevent anything or anyone from touching the hot cap.

WARNING

Do NOT connect a pipe section to a termination cap without using the telescoping flue section found on the termination cap.

NOTE: Where required, an exterior wall flashing is available. When penetrating a brick wall, a brick extension kit is avail- able for framing the brick.

Figure 8.15 Heat Shield, Interior & Exterior Firestops

34

Heat & Glo • SL-550 / 750 / 950TR-D • InD • 2044-985 Rev. M • 10/06

Image 34
Contents Models SL-550TR-D SL-750TR-D SL-950TR-D What to do if you smell gasCongratulations Homeowner Reference InformationTable of Contents Listing and Code Approvals Requirements for the Commonwealth of Massachusetts Inspect Appliance and Components Design and Installation ConsiderationsGetting Started Tools and Supplies NeededSelecting Appliance Location Framing and ClearancesModels Constructing the Appliance Chase ClearancesMantel Projections Clearances to Mantels or other Combustibles above ApplianceVent Termination Minimum Clearances Termination LocationsSee .4 for specific clearances Alcove Applications Minimum Clearances for TerminationUse of Elbows Vent Information and DiagramsVent Table Key Measuring StandardsUse of Flex Vent Vent Diagrams Top Vent Horizontal Termination Venting with 1 elbow NGTop Vent Horizontal Termination Venting with 2 elbows NG MinimumTop Vent Horizontal Termination Venting with 3 elbows NG Baffle Instruction Components onlyTop Vent Vertical Termination Venting with 2 elbows NG Top Vent Vertical Termination Venting with 2 elbows PropaneTop Vent Vertical Termination Venting with 3 elbows NG Top Vent Vertical Termination Venting with 3 elbows PropaneH1 = 9 in mm Maximum Rear Vent Horizontal Termination Venting with 2 elbows Rear Vent Horizontal Termination Venting with 3 elbowsRear Vent Vertical Termination Venting with 1 elbow Rear Vent Vertical Termination Venting with 2 elbowsRear Vent Vertical Termination Venting with 3 elbows V1 MIN H1 MAX H2 MAXCombustible Wall Penetration Vent Clearances and FramingPipe Clearances to Combustibles Wall Penetration Framing Non-Combustible Wall PenetrationInstalling Attic Shield Installing the Ceiling FirestopVertical Penetration Framing Appliance Preparation Choosing the Top or Rear VentRear Vent Cut the metal retaining band and fold the sides outSecuring and Leveling the Appliance Fire Risk Prevent contact with sagging, loose insulationAttaching Vent to the Firebox Assembly Installing Vent PipeAssembly of Vent Sections DVP Pipe only Assembling Pipe SectionsAssembling Minimum Installations MI Sections Assembling DVP-12A Slip SectionsSecuring the Vent Sections Vertical Sections Disassembly of Vent SectionsDVP Pipe only Horizontal SectionsAttach the First Vent Component to Starting Collars Assembly of Vent Sections SL Series Pipe onlyInstall Support Brackets Continue Adding Vent ComponentsInstalling the Horizontal Termination Cap Heat Shield Requirements for Horizontal TerminationFire Risk. Explosion Risk Installing Roof Flashing and Vertical Termination Cap 16 Minimum Height from Roof to Lowest Discharge OpeningAssembling and Installing Storm Collar 19 Assembling the Storm Collar Around the PipeGas Pressures Gas InformationFuel Conversions Gas Connection Pressure Natural Gas PropaneHigh Altitude Installations Connecting to the Appliance Recommendation for WireElectrical Information Standing Pilot Ignition System Wiring Intellifire Ignition System WiringJunction Box Installation Wall Switch Installation for Fan OptionalFacing Material FinishingSee for combustible/non-combustible definitions Accessories Appliance SetupClean the Appliance Remove Shipping MaterialsLog Set Assembly LOGS-SL550-D Models SL-550TR-D Positioning the LogsTAB Locator Log Set Assembly LOGS-SL750-D Models SL-750TR-D, SL-950TR-D Notches Raised Flat Spots Replacing Glass Assembly Glass AssemblyRemoving Glass Assembly Shutter SettingsOperating Instructions Before Lighting ApplianceLighting Appliance Turn off all electric power to the applianceTurn on all electric power to the appliance This appliance is equipped with an ignitionFor Your Safety Read Before Lighting Instructions Standing Pilot IgnitionInitial Break-in Procedure Frequently Asked QuestionsAfter Appliance is Lit Symptom Possible Causes Corrective Action TroubleshootingStanding Pilot Ignition System Troubleshooting Symptom Possible Cause Corrective ActionIntellifire Ignition System Sympton Possible Cause Corrective ActionSure must not exceed 14 in. W.C Maintaining and Servicing Appliance Inspect Maintenance Tasks Recommend addition of screen if one is not presentAppliance Dimension Diagram Reference MaterialsVent Components Diagrams DVP45 45 ElbowDVP-TRAP 13-7/8 352 mm 241 mm 13-1/4367 mm 356 mmVertical Termination Cap 184 mm 12-1/2 318 mm 133 mm 98 mm10-1/2 Vertical Termination Cap High windSL Series Vent Components Pipe Length/InchesService Parts Log Set AssemblyService Parts List Additional service part numbers may appear on the followingSL-750TR-D 215Additional service part numbers may appear on the following SL-750TR-DSL-950TR-D 216Service Parts List SL-550 / 750 / 950TR-D-IPI Intermittent Pilot IgnitionSL-550 / 750 / 950TR-D Limited Lifetime Warranty Limited Lifetime Warranty Heat & GLO GAS Appliance ProductsContact Information

SL-950TR-D, SL-750TR-D, SL-550TR-D specifications

Hearth and Home Technologies has consistently pushed the boundaries of modern heating solutions, and their SL-550TR-D, SL-750TR-D, and SL-950TR-D gas fireplace inserts are prime examples of this innovation. Designed to enhance both the aesthetic appeal and functionality of any living space, these units are ideal for homeowners seeking efficient, reliable heating without sacrificing style.

Starting with the SL-550TR-D, this model features a compact design that is perfect for smaller rooms while still delivering impressive heat output. With a BTU range of 25,000, it efficiently warms spaces without overwhelming them. The SL-550TR-D uses advanced combustion technology, ensuring a clean and efficient burn that minimizes emissions. The large viewing area, complemented by a contemporary linear design, allows for an unobstructed flame view, making it an attractive centerpiece in any room.

Moving on to the SL-750TR-D, this insert expands on the features of the SL-550TR-D, with a higher BTU output of 35,000, making it suitable for larger spaces or homes in colder climates. It also includes an adjustable flame height feature, allowing users to customize the ambiance and heat level to their liking. Additionally, the SL-750TR-D comes equipped with a remote control, providing convenience and ease of use. Its sleek design and modern aesthetics make it an appealing choice for contemporary home settings.

Finally, the SL-950TR-D takes efficiency and style to the next level with a robust BTU output of 45,000. This model is designed for maximum warmth and efficiency, catering to expansive living areas. Its enhanced airflow management system ensures even heat distribution throughout the space. Moreover, the SL-950TR-D offers customizable options such as LED lighting, creating a stunning visual effect that complements the flickering flames.

All three models are equipped with Hearth and Home Technologies' patented Power Vent technology, allowing for flexible installation options, even in challenging spaces. This system provides the ability to vent vertically or horizontally, granting homeowners the freedom to optimize their fireplace's location.

In conclusion, the SL-550TR-D, SL-750TR-D, and SL-950TR-D gas fireplace inserts offer unparalleled heating solutions tailored to various needs and preferences. Their combination of high efficiency, elegant design, and user-friendly features make them standout choices for anyone looking to enhance their home’s comfort and style.