E36/39/42 INSTALLATION INSTRUCTIONS
D. PRE-INSTALLATION PREPARATION
1. Fireplace Locations and Space Requirements
Several options are available to you when choosing a location for your fireplace. This fireplace may be used as a room divider, installed along a wall, across a corner or used in an exterior chase. See Figure 2.
Locating the fireplace in a basement, near frequently opened doors, central heat outlets or returns, or other locations of considerable air movement can affect the performance and cause intermittent smoke spillage from the front of the fireplace. Consideration should be given to these factors before deciding on a location.
CLEARANCES!
A minimum 1/2 in. air clearance must be maintained at the back and sides of the fireplace assembly.
Chimney sections at any level require a 2 in. minimum air space clearance between the framing and chimney section.
Figure 2 - Fireplace Locations
Figures 3 and 4 show two typical installations assuming an outside air kit is being used. Therefore, an allowance must be made for 90-deg bends. Less space is required when ducting goes directly outside without forming elbows.
These are
rough
framing
dimensions
only.
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Cat # |
| A | B |
|
|
| Cat # | A | B | C |
| D | E | |
|
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| E/EC36 |
| 42 in | 45 in. |
|
|
| E/EC36 | 42 in. |
| |||||
|
| 1067 mm | 1143 mm |
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
| 1067 mm | 1848 mm | 924 mm |
| 397 mm | 1305 mm | ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| E/EC39 |
| 45 in. | 48 in. |
|
|
| E/EC39 | 45 in. |
| |||||
|
| 1143 mm | 1219 mm |
|
|
| 1143mm | 1924 mm | 962 mm |
| 422 mm | 1359 mm | |||
|
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| E/EC42 |
| 48 in. | 51 in. |
|
|
| E/EC42 | 48 in. |
| |||||
|
| 1219 mm | 1295 mm |
|
|
| 1219 mm | 2000 mm | 1000 mm |
| 448 mm | 1407 mm | |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Figure 3 |
|
|
|
|
|
|
| Figure 4 |
|
| |||
Installation Along a Wall or an Exterior Chase |
|
|
| Corner Installation |
|
|
WARNING!
Do not draw outside air from garage spaces. Exhaust products of gasoline engines are hazardous.
Do not install outside air ducts such that the air may be drawn from attic spaces, basements or above the roofing where other heating appliances or fans and chimneys exhaust or utilize air. These precautions will reduce the possibility of fireplace smoking or air flow reversal.
WARNING!
To prevent contact with sagging or loose insulation, the fireplace must not be installed against vapor barriers or exposed insulation. Localized overheating could occur and a fire could result.
10 | 17335 Rev L | 07/04 |