Hearth and Home Technologies 6000GL-IPI-S, 6000GL-IPILP-R, 6000GL-IPI-R Finishing, Facing Material

Page 50

13 Finishing

A. Mantel and Wall Projections

WARNING! Risk of Fire! Comply with all minimum clear- ances as specified. Framing closer than the minimums list- ed must be constructed entirely of noncombustible materi- als (i.e., steel studs, concrete board, etc.) Failure to comply could cause fire.

Combustible Mantels

TO CEILING

Note: All

 

18

 

measurements

 

12

 

in inches.

 

 

 

11

 

 

 

 

 

 

10

32

 

 

9

 

 

 

 

8

25

 

 

7

19

 

 

6

 

 

18

 

 

5

 

 

17

 

 

4

16

 

 

3

 

 

15

 

 

 

 

 

 

14

 

 

 

13

 

2-1/2

12

 

 

11

 

 

 

 

 

 

10

 

 

 

5

 

 

 

MEASUREMENTS FROM

 

 

TOP EDGE OF THE OPENING

 

Note: Measurement is taken from top of the opening, NOT the top of the fireplace.

Figure 13.1 Minimum Vertical and Maximum Horizontal

Dimensions of Combustibles

Combustible Mantel Legs or Wall Projections

INTERIOR WALL

TOP VIEW

A

B

 

FIREPLACE OPENING

MANTEL LEG OR WALL PROJECTIONS

If A minimum is ____, then B maximum is_____.

A

Inches

2-7/16

3-7/16

4-7/16

5-7/16

6-7/16

7-7/16

Millimeters

62

87

113

138

164

189

 

B

Inches

1

2

3

4

5

Millimeters

25

51

76

102

127

Figure 13.2 Combustible Mantel Leg or Wall Projections (Acceptable on both sides of opening)

B. Facing Material

Metal front faces may be covered with non-combustible materials only.

Facing and/or finishing materials must not interfere with air flow through louvers, operation of louvers or doors, or access for service.

Facing and/or finishing materials must never overhang into the glass opening.

Observe all clearances when applying combustible materials.

Seal joints between the finished wall and appliance top and sides using a 300 ºF minimum sealant. Refer to Figure 13.3.

WARNING! Risk of Fire! DO NOT apply combustible materials beyond the minimum clearances. Comply with all minimum clearances to combustibles as specified in this manual. Overlapping materials could ignite and will interfere with proper operation of doors and louvers.

NON-COMBUSTIBLE ZONE (Shaded areas)

41 in.

39-3/8 in.

Figure 13.3 Noncombustible Facing Diagram

50

Heat & Glo • 6000GL-IPI-R, 6000GL-IPI-S2102-900 Rev. O • 12/08

Image 50
Contents What to do if you smell gas Hot glass will cause burnsCongratulations Homeowner Reference InformationTable of Contents User GuideFinishing Appliance SetupTroubleshooting Reference MaterialsCONDITIONS, Exclusions & Limitation of Liability Limited Lifetime Warranty Listing and Code Approvals Installation of Carbon Monoxide Detectors Requirements for the Commonwealth of MassachusettsYour Fireplace Gas Fireplace SafetyOperating Instructions User Guide Fan Kit optional Fixed Glass AssemblyRemote Controls, Wall Controls and Wall Switches Clear SpaceLighting Instructions IPI Turn off all electric power to the applianceOn position. The ON/OFF switch may Final inspection byFrequently Asked Questions After Fireplace is LitGlass Cleaning Maintenance and ServiceMaintenance Tasks-Homeowner Remote ControlVenting Maintenance Tasks-Qualified Service TechnicianGasket Seal and Glass Assembly Inspection LogsIPI Pilot Flame Patterns Getting Started Typical Appliance SystemInspect Appliance and Components Design and Installation ConsiderationsTools and Supplies Needed Any such action may cause a fire hazardFraming and Clearances Selecting Appliance LocationConstructing the Appliance Chase ClearancesCombustible Mantel Legs or Wall Projections Mantel and Wall ProjectionsCombustible Mantels Termination Locations Vent Termination Minimum ClearancesCovered Alcove Applications Vent Table Key Vent Information and DiagramsApproved Pipe Use of ElbowsTwo Elbows Vent Diagrams Top Vent Horizontal TerminationOne Elbow V1 Minimum H1 MaximumTop Vent Horizontal Termination Three Elbows Min MaxBreak Here Top Vent Vertical Termination Maximum + V 2 MinTop Vent Vertical Termination Three Elbows H1 + H2 V1 + V2 Minimum H1 + H2 MaximumHeat & Glo 6000GL-IPI-R, 6000GL-IPI-S 2102-900 Rev. O 12/08 H1 Maximum V1 Minimum H2+ H3 H1+ H2+ H3 Max Rear Vent Horizontal Termination Two ElbowsH1 Maximum V1 Minimum H1 + H2 Maximum Rear Vent Vertical Termination One Elbow H1 + H2 Maximum V1 MinimumRear Vent Vertical Termination Three Elbows V1 Minimum H1 + H2 + H3Wall Penetration Framing Vent Clearances and FramingPipe Clearances to Combustibles Combustible Wall PenetrationInstall the Ceiling Firestop Pipe DVP SLPFlat Ceiling Installation Install Attic Insulation ShieldInstalling the Optional Heat-Zone-Gas Kit Vaulted Ceiling InstallationProceed to Section Appliance PreparationChoosing the Top or Rear Vent Installing the Non-combustible Board Rear Vent Securing and Leveling the ApplianceAssemble Vent Sections DVP Pipe Only Installing Vent Pipe DVP and SLP PipeAttach Vent to the Firebox Assembly Assemble Pipe SectionsAssemble Vent Sections SLP Pipe Only Assemble Slip SectionsSecure the Vent Sections Disassemble Vent SectionsInstall Decorative Ceiling Components SLP only Install Metal Roof Flashing Assemble and Install Storm CollarInstall RF4-8 SLP-FSHeat Shield Requirements for Horizontal Termination Install Vertical Termination CapInstall Decorative Wall Components SLP only Refer to of this manual Install Horizontal Termination Cap DVP and SLP PipeAnsi Z223.1 and CAN/CGA-B149 installation codes Gas Pressure Gas InformationFuel Conversion Gas Connection Optional Accessories Requirements Wiring Requirements Intellifire Ignition System Wiring Electrical InformationElectrical Service and Repair Intellifire Pilot Ignition IPI Wiring DiagramJunction Box Installation Wall Switch Installation for Fan OptionalFinishing Facing MaterialDoors Finish Door FIT Material See Maximum ThicknessAppliance Setup Ember Placement Placement of EmbersLog Assembly LOGS-6000GL Install the Log Assembly10 Front View Air Shutter Setting Install the MeshInstall Trim and/or Surround Air Shutter SettingsIntellifire Ignition System TroubleshootingSymptom Possible Cause Corrective Action Ues to spark, and main Location Inches Millimeters Appliance Dimension DiagramReference Materials Vent Components Diagrams DVP vent componentsHorizontal Termination Cap DVP vent components13-3/4 13-7/8 352 mm 349 mm 787 mm 13-1/4 367 mm 24-5/8 625 mm 27-1/2 127 mmRoof Flashing Multi-pak 13-3/4 11-7/8 349 mm 127 mm 302 mm 146 mmDVP-TVHW DVP-HRC-SS DVP-HRC-ZC-SS Horizontal Termination CAP Elbow 165 mm165 mm 222 mm 235 mm 152 mm 168 mm 251 mmCathedral Ceiling Vertical Snorkel Support Box-BlackBlack Termination CapLog Set Assembly Service PartsAt Depot Service Parts List 6000GL-IPI-R, -SStocked 6000GL-IPI-R,-S Intermittent Pilot IgnitionContact Information

6000GL-IPILP-S, 6000GL-IPI-R, 6000GL-IPILP-R, 6000GL-IPI-S specifications

Hearth and Home Technologies has consistently set the benchmark for innovation and efficiency in the realm of gas fireplaces. Among their notable offerings, the models 6000GL-IPI-S, 6000GL-IPILP-R, 6000GL-IPI-R, and 6000GL-IPILP-S stand out for their superior design and advanced technologies. These models cater to diverse homeowner needs, combining aesthetic appeal with functionality.

A defining feature of the 6000GL series is the advanced IntelliFireā„¢ Ignition System. This patented technology ensures a safe and efficient startup and operation, minimizing energy consumption while maximizing user convenience. With this system, users can enjoy a worry-free experience, as the ignition system is designed to only operate when needed.

Another significant characteristic of these models is their customizable options. Homeowners can choose linear and modern designs, along with various media options, including glass and stone, to create a personalized look that complements their space. The ability to customize not only enhances the beauty of the fireplaces but also allows for harmonious integration into various interior designs.

The 6000GL-IPI-S and 6000GL-IPILP-S models focus on direct vent technology, allowing for safe venting of exhaust gases without compromising indoor air quality. This is particularly beneficial in modern homes with tight construction. The models require minimal clearance, making them ideal for both new constructions and remodels.

For those who wish to enjoy a more traditional style, the 6000GL-IPI-R and 6000GL-IPILP-R models present a refined aesthetic, boasting classic fireplace elements that enhance any living space. These options engage viewers with a captivating flame pattern, producing realistic flickering flames that create an inviting atmosphere.

Moreover, Hearth and Home Technologies have incorporated energy-efficient features in these models. The fans operate quietly and efficiently, distributing heat more evenly throughout the room, thus ensuring a comfortable environment without the usual noise disturbances associated with traditional heating methods.

In summary, the Hearth and Home Technologies 6000GL-IPI-S, 6000GL-IPILP-R, 6000GL-IPI-R, and 6000GL-IPILP-S models exemplify the perfect blend of cutting-edge technology and timeless beauty. With customizable aesthetics, advanced ignition systems, direct vent capabilities, and energy-efficient performance, these fireplaces not only enhance home ambiance but also provide reliable heating solutions. Whether it's a modern or traditional setting, these models are sure to impress homeowners while delivering quality and comfort.