Hearth and Home Technologies 6000GL-IPI-S, 6000GL-IPILP-R, 6000GL-IPILP-S Ues to spark, and main

Page 58

Intellifire Ignition System - (continued)

Symptom

Possible Cause

Corrective Action

 

 

 

 

A. A shorted or loose connection in flame

Verify all connections to wiring diagram in manual. Verify

4. Pilot lights but contin-

sensing rod.

connections underneath pilot assembly are tight. Verify con-

ues to spark, and main

 

nections are not grounding out to metal chassis, pilot burn-

burner will not ignite.

 

er, pilot enclosure or screen if present, or any other metal

(If the pilot continues

 

object.

to spark after the

 

 

B. Poor flame rectification or contaminated

With fixed glass assembly in place, verify that flame is en-

pilot flame has been lit,

flame sensing rod.

gulfing flame sensing rod on left side of pilot hood. Flame

flame rectification has

 

sensing rod should glow shortly after ignition. Verify cor-

not occurred.)

 

 

rect pilot orifice is installed and gas inlet is set to pressure

 

 

 

 

specifications. Clean flame sensing rod with emery cloth to

 

 

remove any contaminants that may have accumulated on

 

 

flame sensing rod.

 

 

 

 

C. Module is not grounded.

Verify module is securely grounded to metal chassis of ap-

 

 

pliance. Verify that wire harness is firmly connected to the

 

 

module.

 

 

 

 

D. Damaged pilot assembly or contami-

Verify that ceramic insulator around the flame sensing rod

 

nated flame sensing rod.

is not cracked, damaged, or loose. Verify connection from

 

 

flame sensing rod to white sensor wire. Clean flame sensing

 

 

rod with emery cloth to remove any contaminants that may

 

 

have accumulated on flame sensing rod. Verify continuity

 

 

with a multimeter with ohms set at lowest range. Replace

 

 

pilot if any damage is detected.

 

 

 

 

E. Module.

Turn ON/OFF rocker switch or wall switch to OFF position.

 

 

Remove ignitor wire “I” from module. Place ON/OFF rocker

 

 

switch or wall switch in ON position. If there is no spark at “I”

 

 

terminal module must be replaced. If there is a spark at “I”

 

 

terminal, module is fine.

 

 

 

58

Heat & Glo • 6000GL-IPI-R, 6000GL-IPI-S2102-900 Rev. O • 12/08

Image 58
Contents What to do if you smell gas Hot glass will cause burnsCongratulations Homeowner Reference InformationTable of Contents User GuideFinishing Appliance SetupTroubleshooting Reference MaterialsCONDITIONS, Exclusions & Limitation of Liability Limited Lifetime Warranty Listing and Code Approvals Installation of Carbon Monoxide Detectors Requirements for the Commonwealth of MassachusettsOperating Instructions User Guide Gas Fireplace SafetyYour Fireplace Fan Kit optional Fixed Glass AssemblyRemote Controls, Wall Controls and Wall Switches Clear SpaceLighting Instructions IPI Turn off all electric power to the applianceOn position. The ON/OFF switch may Final inspection byFrequently Asked Questions After Fireplace is LitGlass Cleaning Maintenance and ServiceMaintenance Tasks-Homeowner Remote ControlVenting Maintenance Tasks-Qualified Service TechnicianGasket Seal and Glass Assembly Inspection LogsIPI Pilot Flame Patterns Getting Started Typical Appliance SystemInspect Appliance and Components Design and Installation ConsiderationsTools and Supplies Needed Any such action may cause a fire hazardFraming and Clearances Selecting Appliance LocationConstructing the Appliance Chase ClearancesCombustible Mantels Mantel and Wall ProjectionsCombustible Mantel Legs or Wall Projections Termination Locations Vent Termination Minimum ClearancesCovered Alcove Applications Vent Table Key Vent Information and DiagramsApproved Pipe Use of ElbowsTwo Elbows Vent Diagrams Top Vent Horizontal TerminationOne Elbow V1 Minimum H1 MaximumTop Vent Horizontal Termination Three Elbows Min MaxBreak Here Top Vent Vertical Termination Maximum + V 2 MinTop Vent Vertical Termination Three Elbows H1 + H2 V1 + V2 Minimum H1 + H2 MaximumHeat & Glo 6000GL-IPI-R, 6000GL-IPI-S 2102-900 Rev. O 12/08 H1 Maximum V1 Minimum H1 + H2 Maximum Rear Vent Horizontal Termination Two ElbowsH1 Maximum V1 Minimum H2+ H3 H1+ H2+ H3 Max Rear Vent Vertical Termination One Elbow H1 + H2 Maximum V1 MinimumRear Vent Vertical Termination Three Elbows V1 Minimum H1 + H2 + H3Wall Penetration Framing Vent Clearances and FramingPipe Clearances to Combustibles Combustible Wall PenetrationInstall the Ceiling Firestop Pipe DVP SLPFlat Ceiling Installation Install Attic Insulation ShieldInstalling the Optional Heat-Zone-Gas Kit Vaulted Ceiling InstallationChoosing the Top or Rear Vent Appliance PreparationProceed to Section Installing the Non-combustible Board Rear Vent Securing and Leveling the ApplianceAssemble Vent Sections DVP Pipe Only Installing Vent Pipe DVP and SLP PipeAttach Vent to the Firebox Assembly Assemble Pipe SectionsAssemble Vent Sections SLP Pipe Only Assemble Slip SectionsSecure the Vent Sections Disassemble Vent SectionsInstall Decorative Ceiling Components SLP only Install Metal Roof Flashing Assemble and Install Storm CollarInstall RF4-8 SLP-FSInstall Decorative Wall Components SLP only Install Vertical Termination CapHeat Shield Requirements for Horizontal Termination Ansi Z223.1 and CAN/CGA-B149 installation codes Install Horizontal Termination Cap DVP and SLP PipeRefer to of this manual Gas Pressure Gas InformationFuel Conversion Gas ConnectionOptional Accessories Requirements Wiring RequirementsIntellifire Ignition System Wiring Electrical InformationElectrical Service and Repair Intellifire Pilot Ignition IPI Wiring DiagramJunction Box Installation Wall Switch Installation for Fan OptionalFinishing Facing MaterialDoors Finish Door FIT Material See Maximum ThicknessAppliance Setup Ember Placement Placement of EmbersLog Assembly LOGS-6000GL Install the Log Assembly10 Front View Air Shutter Setting Install the MeshInstall Trim and/or Surround Air Shutter SettingsSymptom Possible Cause Corrective Action TroubleshootingIntellifire Ignition System Ues to spark, and main Reference Materials Appliance Dimension DiagramLocation Inches Millimeters Vent Components Diagrams DVP vent componentsHorizontal Termination Cap DVP vent components13-3/4 13-7/8 352 mm 349 mm 787 mm 13-1/4 367 mm 24-5/8 625 mm 27-1/2 127 mmRoof Flashing Multi-pak 13-3/4 11-7/8 349 mm 127 mm 302 mm 146 mmDVP-TVHW DVP-HRC-SS DVP-HRC-ZC-SS Horizontal Termination CAP Elbow 165 mm165 mm 222 mm 235 mm 152 mm 168 mm 251 mmCathedral Ceiling Vertical Snorkel Support Box-BlackBlack Termination CapLog Set Assembly Service PartsStocked Service Parts List 6000GL-IPI-R, -SAt Depot 6000GL-IPI-R,-S Intermittent Pilot IgnitionContact Information

6000GL-IPILP-S, 6000GL-IPI-R, 6000GL-IPILP-R, 6000GL-IPI-S specifications

Hearth and Home Technologies has consistently set the benchmark for innovation and efficiency in the realm of gas fireplaces. Among their notable offerings, the models 6000GL-IPI-S, 6000GL-IPILP-R, 6000GL-IPI-R, and 6000GL-IPILP-S stand out for their superior design and advanced technologies. These models cater to diverse homeowner needs, combining aesthetic appeal with functionality.

A defining feature of the 6000GL series is the advanced IntelliFireā„¢ Ignition System. This patented technology ensures a safe and efficient startup and operation, minimizing energy consumption while maximizing user convenience. With this system, users can enjoy a worry-free experience, as the ignition system is designed to only operate when needed.

Another significant characteristic of these models is their customizable options. Homeowners can choose linear and modern designs, along with various media options, including glass and stone, to create a personalized look that complements their space. The ability to customize not only enhances the beauty of the fireplaces but also allows for harmonious integration into various interior designs.

The 6000GL-IPI-S and 6000GL-IPILP-S models focus on direct vent technology, allowing for safe venting of exhaust gases without compromising indoor air quality. This is particularly beneficial in modern homes with tight construction. The models require minimal clearance, making them ideal for both new constructions and remodels.

For those who wish to enjoy a more traditional style, the 6000GL-IPI-R and 6000GL-IPILP-R models present a refined aesthetic, boasting classic fireplace elements that enhance any living space. These options engage viewers with a captivating flame pattern, producing realistic flickering flames that create an inviting atmosphere.

Moreover, Hearth and Home Technologies have incorporated energy-efficient features in these models. The fans operate quietly and efficiently, distributing heat more evenly throughout the room, thus ensuring a comfortable environment without the usual noise disturbances associated with traditional heating methods.

In summary, the Hearth and Home Technologies 6000GL-IPI-S, 6000GL-IPILP-R, 6000GL-IPI-R, and 6000GL-IPILP-S models exemplify the perfect blend of cutting-edge technology and timeless beauty. With customizable aesthetics, advanced ignition systems, direct vent capabilities, and energy-efficient performance, these fireplaces not only enhance home ambiance but also provide reliable heating solutions. Whether it's a modern or traditional setting, these models are sure to impress homeowners while delivering quality and comfort.