Honeywell R7426A, R7426B, R7426C Start Point Ystart P.15, Compensation Changeover Point Wcomp P.03

Page 10

R7426A,B,C TEMPERATURE CONTROLLER WITH AND WITHOUT REAL TIME CLOCK

Setting Guidelines for Reset Time of P+I Control

The reset time tr should be adjusted to 2...3 times of the response time Tu , which is the time interval between the beginning of a sustained disturbance (e.g. rapid step change of valve position) and the instant when the resulting change in the output signal reaches a specified fraction of its final steady-state value, either before overshoot or in the absence of overshoot.

The response time Tu in discharge air control is normally in the range of 0.1 to 0.6 min, which allows adjustments of the reset time tr in a range of 0.2 to 2 min.

In room control the response time Tu is in the range of 0.5 to 5 min, which results in a setting of 1 to 15 min.

Start Point Ystart (P.15)

This control parameter is available only on the single output controller R7426A and on the R7426B controller if the three 3- position floating outputs are configured for 6-stage ON/OFF sequence control and on the R7426B,C controllers if YMode = 1 is selected.

The start point determines the midrange shift of the output Y1 from the calculated control point.

The start point is calibrated in degrees K and is the offset (plus or minus) from the set values or calculated control points at which the output Y1 is at 50%. Normally and especially in P+l control, the start point should be set at zero. A change is required only in specific applications where a asymmetrical arrangement results in improved control per- formance, e.g. if for heat-up of a large space in the morning a high heat capacity is needed and for normal control the valve must be opened by only a small amount.

Compensation Changeover Point Wcomp (P.03)

The control parameter Wcomp defines the start point of summer or winter compensation. Above the compensation changeover point (Wcomp) summer compensation and below Wcomp winter compensation is performed.

Summer / Winter Compensation Authority Su / Wi (P.04 / P.05)

These authority settings determine the reset effect (OATComp) the compensation sensor (T3) has on the main setpoint W1 in percentages. Outside temperature reset in summer and winter time are commonly used applications.

To calculate winter and summer authority, the throttling range must be considered in proportional-only control according to Table 12.

Table 12. Calculation of summer/winter compensation

 

control

 

room temp.

outdoor air

 

throttling

 

 

 

 

temp.

 

 

 

 

schedule

 

(T1)

 

 

 

range (XP)

 

 

 

 

(T3/Tcomp)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20°C

 

 

20°C

 

 

 

 

2°C

 

 

 

22°C

 

 

-15°C

 

 

 

 

2°C

 

 

 

Aut Wi =

 

T1+ Xp

 

100%

=

 

 

 

 

Winter

 

 

t Outside Air

 

 

 

 

 

 

 

(22 - 20) + 2

 

 

 

 

 

 

 

 

 

 

 

100% =≈ 12%

 

 

 

 

 

 

35

 

 

 

 

 

 

 

 

 

 

 

20°C

 

 

20°C

 

 

 

 

2°C

 

 

 

26°C

 

 

35°C

 

 

 

 

2°C

 

 

 

Aut Su =

 

T1Xp

 

100%

=

 

 

 

 

Summer

 

 

t Outside Air

 

 

 

 

 

(26 - 20) - 2

 

 

 

 

 

 

 

 

 

100% =≈ 27%

 

 

 

 

 

 

15

 

 

 

 

 

 

 

 

Compensation change-over at +20 °C outdoor air temperature

NOTE: With P+I control Xp = 0

Occupied/Unoccupied Function SOFFS (P.16)

A potential-free contact can be used between terminals 1 and 4 to switch the controller between occupied (contact closed) or unoccupied (contact open) mode.

In occupied mode, the temperature set point W1 is used for the control point calculation. In unoccupied mode, the SOFFS parameter value is added (cooling) to or subtracted (heating) from the calculated control point.

In the case of the R7426A controller, the parameter Y1CTRF must be set to 0 or 1 (Cho) to match the required heating or cooling application.

If the configuration parameter Y1CTRF is set to 2 (summer / winter changeover), the parameter SOFFS is not considered.

In sequence applications of heating and cooling, the SOFFS parameter value is added to the control point for cooling (CTRPC) and subtracted from the control point for heating

(CTRPH) (see Fig. 5).

Night Mode Offset NOFFS (P.26: Controller with RTC only)

This control parameter is used to set the night mode offset.

During night mode, freeze protection is active and the occupied / unoccupied function is inactive.

Night Cycle NightLow and NightHigh (P.24 and P.25: with RTC, only)

The control parameters NightLow and NightHigh are used by the night cycle program (controller mode = OFF) to assign unoccupied night low or high limits for the protection of a space and its contents against temperature extremes.

EN1B-0203GE51 R0507C

10

Image 10
Contents General Before Installation NoteMounting Terminal Connection Controller to CPA/SPA potentiometer WiringPower Supply and Grounding TerminalConfiguration and Control Parameters Y1CTRF Soffs MinposNoffs Operating Range Selection Ctrltyp C.04 Configuration SettingsControl Point / Setpoint Adjustment Cpatyp C.05 Output Control Range Selection YRange C.06Limit Type LimTyp C.13 Output Signal Mode YMode C.11Supply of Temperature Signal T2 T2ext C.12 Sensor Type Senstyp C.14Parameter Settings Adjustment Throttling Range Xpc / Xph P.10 / P11 Reset Time tr1 / tr2 P.12 / P13Throttling range and reset time reference Application Sens Tr1 Tr2Compensation Changeover Point Wcomp P.03 Night Mode Offset Noffs P.26 Controller with RTC onlyStart Point Ystart P.15 Summer / Winter Compensation Authority Su / Wi P.04 / P.05Minimum Position Minpos P.14 Operating OverviewReturn Air Offset RetOffs P.20 Runtimex, x = Y1, Y2, or Y3 P.21...P.23Changing Operating Modes Operating overviewStandard display mode Time OutDisplaying Actual Values Adjusting Configuration / Parameter ValuesResetting Param. Values to Default Values Selecting ParametersOutput Selection Mode Example of annual schedule no default Using the Schedules with RTC, onlyDay1 Point Selecting Clock and Schedules with RTC, only Adjusting Date and Time with RTC, onlyProgramming Standard Schedule with RTC, only Interpreting Error Messages Programming Holiday Schedule with RTC, onlyAnnual schedule Automation and Control Solutions Weekly schedule and holiday types

R7426C, R7426A, R7426B specifications

Honeywell's R7426 series comprises three advanced models: R7426B, R7426A, and R7426C. These devices are designed to optimize control for HVAC applications, emphasizing energy efficiency, ease of use, and superior control capabilities. Each model incorporates unique features and technologies catering to specific system requirements while maintaining common foundational characteristics.

The R7426B is engineered with a microprocessor-based control system, allowing for precise temperature management across varied environments. It supports a range of heating and cooling applications, making it versatile in both residential and commercial settings. The unit boasts dual-stage heating and cooling capabilities, ensuring optimal comfort by allowing for gradual temperature changes. It also includes an easy-to-read LCD display for user-friendly navigation and parameter adjustments.

R7426A enhances functionality with additional communication technologies. This model incorporates Honeywell's proprietary communication protocols, enabling seamless connection with smart thermostats and home automation systems. This ensures users can monitor and control their HVAC systems remotely, leading to enhanced energy management and convenience. R7426A also includes advanced diagnostic capabilities that simplify troubleshooting and maintenance processes.

R7426C further extends the capabilities of the series by integrating state-of-the-art sensors for real-time environmental monitoring. These sensors continuously track indoor air quality parameters such as humidity and particulate matter levels, allowing for immediate adjustments to maintain optimal indoor conditions. The model is also equipped with smart algorithms that learn user preferences over time, automatically adjusting settings to enhance comfort and efficiency.

Common features across the R7426 series include robust construction for long-lasting performance and compatibility with a wide range of HVAC systems, including heat pumps and conventional heating systems. Each model supports programmable settings, enabling users to create schedules that align with their unique lifestyle or business needs. Safety features, including freeze protection and delay timers, are integrated to safeguard against potential system failures.

Overall, the Honeywell R7426B, R7426A, and R7426C models represent a significant advancement in HVAC control technology. With their focus on efficiency, automation, and user-centric design, these devices help users achieve optimal climate management in their spaces while minimizing energy consumption. Whether for residential comfort or commercial efficiency, these models stand out as reliable solutions in the HVAC market.