Honeywell R7426B Throttling Range Xpc / Xph P.10 / P11, Reset Time tr1 / tr2 P.12 / P13, Tr1 Tr2

Page 9

R7426A,B,C TEMPERATURE CONTROLLER WITH AND WITHOUT REAL TIME CLOCK

limit or cascade sensor (T2) to operate the output device from full open (100%) to full closed (0%) or vice versa.

Xp1 is the throttling range for the main control loop, Xp2 is used if limitation or cascade control (submaster control loop) is active (see Table 11).

Table 11. Throttling range and reset time reference

application

sens.

Xp1

Xp2

Xpc

Xph

tr1

tr2

R7426A Controller

 

 

 

 

 

 

 

Main Temp.Control

T1

x

 

 

 

x

 

High or Low Limit

T2

 

x

 

 

 

x

Temperature Control

 

 

 

 

 

 

 

 

 

 

 

Cascade Control

 

 

 

 

 

 

 

Master

T1

x

 

 

 

x

 

Submaster

T2

 

x

 

 

 

x

R7426B,C Controller

 

 

 

 

 

 

 

Main Temp. Seq. Control

 

 

 

 

 

 

 

Mixed Air Damper

T1

x

 

 

 

x

 

Energy Recovery

T1

x

 

 

 

x

 

Heating

T1

 

 

 

x

x

 

Cooling

T1

 

 

x

 

x

 

R7426B,C Controller

 

 

 

 

 

 

 

Temperature Cascade

 

 

 

 

 

 

 

Sequence Control

 

 

 

 

 

 

 

Master

T1

x

 

 

 

x

 

Submaster

 

 

 

 

 

 

 

- Mixed Air Dampers

T2

 

x

 

 

 

x

- Energy Recovery

T2

 

x

 

 

 

x

- Heating

T2

 

 

 

x

 

x

- Cooling

T2

 

 

x

 

 

x

Throttling Range Xpc / Xph (P.10 / P11)

The control parameters Xpc and Xph are only available on R7426B,C controllers and are used to set the cooling and heating throttling ranges for the following applications

Temperature sequence control with heating, mixed air dampers, and cooling (see Fig. 3 and Table 11)

Temperature cascade control with heating, mixed air dampers, and cooling (see Table 11)

In applications without cooling, the throttling range Xpc must be set to OFF 100% fresh air supply at actual temperature above the control point is required (outdoor and return air dampers fully open).

Y[%]

 

 

 

 

 

100

 

1/4 Xp1

 

if Xpc = Off

 

Damper

 

 

 

 

 

 

 

 

Y1

 

 

 

 

 

Y3

 

 

Y2

 

MINPOS

Heating

 

 

Cooling

 

 

 

 

if Xpc = Off

 

0

 

 

 

 

 

 

 

Xwh / Xwc /Xwd

 

CTRPH

CTRP1

CTRPC

 

 

 

 

Xph

Xp1

 

Xpc

T2

 

 

 

Fig. 3. Temperature sequence control with heating, mixed

air dampers, and cooling valve

Setting Guidelines for Proportional Band of P and P+I Control

To estimate the proportional band (throttling range Xp) for stable control under all different load conditions, the control or correcting range Xh of the heating or cooling coil must be known. This is the maximum air temperature increase pro- duced by the heating coil or decrease of a cooling coil if the control valve is fully open.

The proportional band Xp for discharge air control can be calculated by using the following rule-of thumb formula:

Xp = Xh 5

For room temperature control, the following rule-of-thumb formula can be used:

Xp = Xh or tmaxdischarge air

1010

The tmax (Xh) of the discharge air for mixed air damper con- trol is the maximum difference between outdoor air (OA) temperature and return air (RA) temperature.

Xh = ϑRA - ϑOAmin

The often-specified accuracy for room control of ±1 (Xp = 2K) allows a discharge air alteration of 20 °C.

In P+I control the same proportional band can be used as for P control. The following rule-of-thumb formulae are used for P+I control:

Discharge air control

Xp =

Xh

 

 

 

 

 

 

 

4...5

 

 

Room control

Xp =

Xh

or tmaxdischarge air

 

 

 

8...10

 

8 ... 10

 

Reset Time tr1 / tr2 (P.12 / P13)

 

 

 

Xw

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

t

 

Y

 

 

 

 

 

 

 

 

 

 

 

P

P

%/s

 

 

 

 

 

tr

 

 

 

P =100 X w %

 

 

 

 

 

Xp

 

 

 

 

 

 

 

tr

 

 

 

t

 

 

 

 

 

 

 

Fig. 4. Step change response of P+I control

In the case of combined action including proportional and integral components (P+I control), the reset time (tr) is defined as the required time after which the integral part is equal to the change due to the proportional action for a predetermined step change in the input variable. See Fig. 4.

The control parameter tr1 sets the reset time of the P+I main temperature control loop. For limit or submaster cascade control the control parameter tr2 sets the reset time of these control loops, e.g. discharge temperature T2 (see Table 11).

If only proportional control is required, parameter tr must be set to OFF.

9

EN1B-0203GE51 R0507C

Image 9
Contents Before Installation Note GeneralMounting Power Supply and Grounding WiringTerminal Connection Controller to CPA/SPA potentiometer TerminalConfiguration and Control Parameters Y1CTRF Minpos SoffsNoffs Control Point / Setpoint Adjustment Cpatyp C.05 Configuration SettingsOperating Range Selection Ctrltyp C.04 Output Control Range Selection YRange C.06Supply of Temperature Signal T2 T2ext C.12 Output Signal Mode YMode C.11Limit Type LimTyp C.13 Sensor Type Senstyp C.14Parameter Settings Adjustment Throttling range and reset time reference Application Sens Reset Time tr1 / tr2 P.12 / P13Throttling Range Xpc / Xph P.10 / P11 Tr1 Tr2Start Point Ystart P.15 Night Mode Offset Noffs P.26 Controller with RTC onlyCompensation Changeover Point Wcomp P.03 Summer / Winter Compensation Authority Su / Wi P.04 / P.05Return Air Offset RetOffs P.20 Operating OverviewMinimum Position Minpos P.14 Runtimex, x = Y1, Y2, or Y3 P.21...P.23Operating overview Changing Operating ModesTime Out Standard display modeResetting Param. Values to Default Values Adjusting Configuration / Parameter ValuesDisplaying Actual Values Selecting ParametersOutput Selection Mode Using the Schedules with RTC, only Example of annual schedule no defaultDay1 Point Adjusting Date and Time with RTC, only Selecting Clock and Schedules with RTC, onlyProgramming Standard Schedule with RTC, only Programming Holiday Schedule with RTC, only Interpreting Error MessagesAnnual schedule Weekly schedule and holiday types Automation and Control Solutions

R7426C, R7426A, R7426B specifications

Honeywell's R7426 series comprises three advanced models: R7426B, R7426A, and R7426C. These devices are designed to optimize control for HVAC applications, emphasizing energy efficiency, ease of use, and superior control capabilities. Each model incorporates unique features and technologies catering to specific system requirements while maintaining common foundational characteristics.

The R7426B is engineered with a microprocessor-based control system, allowing for precise temperature management across varied environments. It supports a range of heating and cooling applications, making it versatile in both residential and commercial settings. The unit boasts dual-stage heating and cooling capabilities, ensuring optimal comfort by allowing for gradual temperature changes. It also includes an easy-to-read LCD display for user-friendly navigation and parameter adjustments.

R7426A enhances functionality with additional communication technologies. This model incorporates Honeywell's proprietary communication protocols, enabling seamless connection with smart thermostats and home automation systems. This ensures users can monitor and control their HVAC systems remotely, leading to enhanced energy management and convenience. R7426A also includes advanced diagnostic capabilities that simplify troubleshooting and maintenance processes.

R7426C further extends the capabilities of the series by integrating state-of-the-art sensors for real-time environmental monitoring. These sensors continuously track indoor air quality parameters such as humidity and particulate matter levels, allowing for immediate adjustments to maintain optimal indoor conditions. The model is also equipped with smart algorithms that learn user preferences over time, automatically adjusting settings to enhance comfort and efficiency.

Common features across the R7426 series include robust construction for long-lasting performance and compatibility with a wide range of HVAC systems, including heat pumps and conventional heating systems. Each model supports programmable settings, enabling users to create schedules that align with their unique lifestyle or business needs. Safety features, including freeze protection and delay timers, are integrated to safeguard against potential system failures.

Overall, the Honeywell R7426B, R7426A, and R7426C models represent a significant advancement in HVAC control technology. With their focus on efficiency, automation, and user-centric design, these devices help users achieve optimal climate management in their spaces while minimizing energy consumption. Whether for residential comfort or commercial efficiency, these models stand out as reliable solutions in the HVAC market.