Honeywell R7426A Output Signal Mode YMode C.11, Supply of Temperature Signal T2 T2ext C.12

Page 7

R7426A,B,C TEMPERATURE CONTROLLER WITH AND WITHOUT REAL TIME CLOCK

Output Signal Mode YMode (C.11)

Sequence Operation

The controllers R7426B,C are supplied from the factory configured for sequence operation of heating, mixed air, and cooling control.

The sequence operation can be configured for the following control applications by the control parameters YMode and Y1CTRF (see Table 8). Sequence control will be activated if at least one control parameter YxMode is not equal 4 (R7426B, only).

Table 8. Sequence Operation Selection

sequence control

YMode

Y1CTRF

YxMode

for cooling with three outputs

1

0

0

(Y1, Y2, Y3)

 

 

 

for heating with three outputs

1

1

0

(Y1, Y2, Y3)

 

 

 

with two outputs (Y1, Y3) for

 

 

 

heating and one output for

2

n.a.

0

cooling (Y2)

 

 

 

with one output (Y2) for

 

 

 

heating and two outputs for

3

n.a.

0

cooling (Y1, Y3)

 

 

 

 

 

 

 

damper, cooling and heating

0

0

0

(Y1, Y2 and Y3)

 

 

 

 

 

 

 

energy recovery, cooling and

0

1

0

heating

 

 

 

Multistage ON/OFF Function

In the case of the three floating output controller R7426B, several ON/OFF sequence control functions can be selected by the configuration parameter YMode (see Table 9).

Table 9. Multistage Selection

 

 

 

 

 

 

 

provided

 

function

 

 

output function

 

YMode

 

YxMode

by

 

 

 

 

 

 

of Y2

 

 

 

 

 

 

 

output

 

 

 

 

 

 

 

 

 

 

 

6-stage ON/OFF

1

 

4 (x=1, 2,

Y1,Y2,Y3

 

n.a.

 

sequence control

 

 

 

and 3)

 

 

 

 

4-stage ON/OFF

 

 

 

4 (x=1

 

 

 

 

sequence control

2

 

Y1,Y3

 

 

 

 

and 3)

 

 

 

heating

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4-stage ON/OFF

 

 

 

4 (x=1

 

 

according

 

sequence control

3

 

Y1,Y3

 

 

 

and 3)

 

to

 

cooling

 

 

 

 

 

 

 

 

 

 

 

 

Y2Mode

 

15-stage binary

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

coded ON/OFF

5

 

n.a.

Y1,Y3

 

 

 

sequence control

 

 

 

 

 

 

 

 

 

 

 

 

H.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

two-position

4

 

n.a.

Y1

 

Y2 and

 

damper control

 

 

Y3 1)

 

 

 

 

 

 

 

 

 

1)

individual (cooling and heating)

 

 

 

 

 

 

 

 

In the case of the R7426B,C controller, the output Y1 can be configured for two-position damper control by setting the configuration parameter YMode to 4.

Supply of Temperature Signal T2

T2ext (C.12)

If sensor T1 is used also for high or low limit control, the con- figuration parameter T2ext must be set to 1. This inter- connects the T1 and T2 input internally and the sensor has to be connected only to the T1 input.

By using a limit temperate sensor T2, the parameter T2ext has to be set to 0 (default).

Limit Type LimTyp (C.13)

The configuration parameter LimTyp allows the selection of high or low limit control. High limit control is performed if configuration parameter LimTyp = 1; low limit control is performed if configuration parameter LimTyp = 0.

Sensor Type Senstyp (C.14)

Three different sensor types can be used with the controller (see Table 10).

Table 10. Sensor Types

automatic ID

temperature

 

characteristics

 

of sensor type

range

 

 

 

 

 

Pt 1000

-30....+130°C

 

1000at 0°C

BALCO 500

-30....+130°C

 

500at 23.3°C

NTC 20k

-30....+85°C /

 

20kat 25°C

-30....+130°C1)

 

1) NTC sensor is detected automatically if, during power- up, the sensor temperature is within -30....+85°C and the

configuration parameter Senstyp = 0. NTC sensor is selected manually if the configuration parameter Senstyp is set to 1.

Automatic identification of sensor type is selected if the configuration parameter Senstyp = 0 (default). After power up reset, the controller detects automatically the type of sensor connected to the main temperature input T1. For correct auto detection, it is necessary that the measured temperature be in the specified range (see Table 10). The same type of sensor must be used for all temperature inputs (T1, T2 and T3).

Output Control Function Y1CTRF (C.15)

The R7426A controller performs cooling control if the configuration parameter Y1CTRF is set to 0. A rise in the measured variable will increase the output value (direct acting). The control action must be reversed for heating control by setting the control parameter Y1CTRF to 1. A rise in the measured variable will decrease the output value.

If the configuration parameter is set to 2, the R7426A controller provides summer/winter changeover control by a potential-free contact connected to the occupancy input (terminals 1 and 4).

In the case of the R7426B,C controller, the configuration parameter Y1CTRF has to be set to 0 (default) to perform mixed air damper control and to 1 for energy recovery systems.

7

EN1B-0203GE51 R0507C

Image 7
Contents General Before Installation NoteMounting Terminal WiringPower Supply and Grounding Terminal Connection Controller to CPA/SPA potentiometerConfiguration and Control Parameters Y1CTRF Soffs MinposNoffs Output Control Range Selection YRange C.06 Configuration SettingsControl Point / Setpoint Adjustment Cpatyp C.05 Operating Range Selection Ctrltyp C.04Sensor Type Senstyp C.14 Output Signal Mode YMode C.11Supply of Temperature Signal T2 T2ext C.12 Limit Type LimTyp C.13Parameter Settings Adjustment Tr1 Tr2 Reset Time tr1 / tr2 P.12 / P13Throttling range and reset time reference Application Sens Throttling Range Xpc / Xph P.10 / P11Summer / Winter Compensation Authority Su / Wi P.04 / P.05 Night Mode Offset Noffs P.26 Controller with RTC onlyStart Point Ystart P.15 Compensation Changeover Point Wcomp P.03Runtimex, x = Y1, Y2, or Y3 P.21...P.23 Operating OverviewReturn Air Offset RetOffs P.20 Minimum Position Minpos P.14Operating overview Changing Operating ModesTime Out Standard display modeSelecting Parameters Adjusting Configuration / Parameter ValuesResetting Param. Values to Default Values Displaying Actual ValuesOutput Selection Mode Example of annual schedule no default Using the Schedules with RTC, onlyDay1 Point Selecting Clock and Schedules with RTC, only Adjusting Date and Time with RTC, onlyProgramming Standard Schedule with RTC, only Programming Holiday Schedule with RTC, only Interpreting Error MessagesAnnual schedule Weekly schedule and holiday types Automation and Control Solutions

R7426C, R7426A, R7426B specifications

Honeywell's R7426 series comprises three advanced models: R7426B, R7426A, and R7426C. These devices are designed to optimize control for HVAC applications, emphasizing energy efficiency, ease of use, and superior control capabilities. Each model incorporates unique features and technologies catering to specific system requirements while maintaining common foundational characteristics.

The R7426B is engineered with a microprocessor-based control system, allowing for precise temperature management across varied environments. It supports a range of heating and cooling applications, making it versatile in both residential and commercial settings. The unit boasts dual-stage heating and cooling capabilities, ensuring optimal comfort by allowing for gradual temperature changes. It also includes an easy-to-read LCD display for user-friendly navigation and parameter adjustments.

R7426A enhances functionality with additional communication technologies. This model incorporates Honeywell's proprietary communication protocols, enabling seamless connection with smart thermostats and home automation systems. This ensures users can monitor and control their HVAC systems remotely, leading to enhanced energy management and convenience. R7426A also includes advanced diagnostic capabilities that simplify troubleshooting and maintenance processes.

R7426C further extends the capabilities of the series by integrating state-of-the-art sensors for real-time environmental monitoring. These sensors continuously track indoor air quality parameters such as humidity and particulate matter levels, allowing for immediate adjustments to maintain optimal indoor conditions. The model is also equipped with smart algorithms that learn user preferences over time, automatically adjusting settings to enhance comfort and efficiency.

Common features across the R7426 series include robust construction for long-lasting performance and compatibility with a wide range of HVAC systems, including heat pumps and conventional heating systems. Each model supports programmable settings, enabling users to create schedules that align with their unique lifestyle or business needs. Safety features, including freeze protection and delay timers, are integrated to safeguard against potential system failures.

Overall, the Honeywell R7426B, R7426A, and R7426C models represent a significant advancement in HVAC control technology. With their focus on efficiency, automation, and user-centric design, these devices help users achieve optimal climate management in their spaces while minimizing energy consumption. Whether for residential comfort or commercial efficiency, these models stand out as reliable solutions in the HVAC market.