Honeywell 42011076-003 manual Category 2 System Settings

Page 11

4.5.2 Category 2 - System Settings

Parameter

Parameter Factory Default Setting No.

Optional Setting

Category 2 Parameters – System Settings (press the button to access this category)

 

 

Display

Description

Display

Description

 

 

 

 

 

 

Minimum boiler

1:Ot

1

1 minute minimum

2 to 5

Selection of 2, 3, 4 or 5 minutes

ON time

 

 

ON time

 

minimum ON time

 

 

 

 

 

 

Cycle Rate

2:Cr

6

6 cycles per hour

3,9 or

Selection of 3, 9 or 12 cph

 

 

 

(cph)

12

 

 

 

 

 

 

 

Heat/Cool Change

4:HC

0

Disabled

1

Enabled

 

 

 

 

 

 

Pump Exercise

5:PE

0

Pump exercise

1

Pump exercise enabled

 

 

 

disabled

 

 

 

 

 

 

 

 

System

6:Sn

0

Standard operation of

1

Room unit configured as Synchroniser

Synchronisation

 

 

the Room Unit

 

 

 

 

 

 

 

 

Loss of

7:LC

0

Relay Off

1

Relay 20% on / 80% off

Communications

 

 

 

 

 

Instruction

 

 

 

 

 

 

 

 

 

 

 

The following Parameters are for the control of other Honeywell Wireless products such as Wireless Underfloor Heating controls and Wireless Radiator controls. For more information please contact Honeywell sales.

Room Temperature

8:Su

0

HC60 control

1,2,3

1 - HR80/HM80 control with own/remote

Sensor Use

 

 

 

or 4

sensor (no temperature displayed)

 

 

 

 

 

2 - Hr80/HM80/HCE80 control with CM

 

 

 

 

 

sensor

 

 

 

 

 

3 - HC60 control and HR80/HM80/

 

 

 

 

 

HCE80 control with own/remote sensor

 

 

 

 

 

4 – Hr80/HM80/HCE80 control with own/

 

 

 

 

 

remote sensor (temperature displayed)

 

 

 

 

 

 

HR80 Window-

9:HO

0

Disabled

1

Enabled

Open Function

 

 

 

 

 

 

 

 

 

 

 

HR80 Local

10:HL

1

Enabled

0

Disabled

Override

 

 

 

 

 

 

 

 

 

 

 

Maximum Flow

11:uF

55

55°C Maximum Flow

0 to 99

0°C to 99°C adjustment in 1°C steps

Setpoint

 

 

Temp.

 

 

 

 

 

 

 

 

Minimum Flow

12:LF

15

15°C Minimum Flow

0 to 50

0°C to 50°C adjustment in 1°C steps

Setpoint

 

 

Temp.

 

 

 

 

 

 

 

 

Mixing Value Run

13:Ar

150

150 seconds

0 to

0 to 240 sec. adjustment in 1sec steps

Time

 

 

 

240

 

 

 

 

 

 

 

Pump Overrun Run

14:Pr

15

15 minutes

0 to 99

0 to 99 mins adjustment in 1min steps

Time

 

 

 

 

 

 

 

 

 

 

 

Notes

1)Remember to always press the green button to confirm that you want to store your new Installer Set- Up setting. To exit the Installer Mode move the slider switch to the AUTO or MAN position.

2)These parameters are set centrally for the zoning system at the room thermostat configured as the system synchroniser.

3)Minimum on-time setting applies only to the boiler controller. All receiver box zone controllers will work with the minimum on-time of 30 seconds.

10

CM900 Wireless - Programmable Room Thermostat

Image 11
Contents 42011076-003 Description Table of ContentsInstallation Information Installing the Receiver Box Installing the CM900 Wireless SystemRF Communication Check Test Mode Installing the Room Thermostat 2.2.1 Power UpSystem Check Locating the Room ThermostatTemporary Manual Override Installer ModeBasic Operation of the System Automatic OperationHC60NG Receiver Box Fail-Safe Mode Setup Entering Installer ModeUsing the Special Features of the Room Thermostat Using the Room Thermostat for Specific ApplicationsCategory 1 Parameters Room Thermostat Settings Category 2 System Settings Multi-Zone System Additional Installation InformationBinding / Rebinding Procedure Diagnostic Mode Trouble ShootingTrouble Shooting Guide