5) Additional Installation Information
5.1 Binding / Rebinding Procedure
The binding operation described below is required if:
•Any of the system components (room thermostat or receiver box) are replaced.
•The receiver box has incorrect or no binding data stored (e.g. when
NOTE: During the binding procedure keep approximately 1m distance between the room thermostat and the receiver box.
To bind/rebind:
1.Press and hold the receiver box push button for 15 seconds to reset any previously stored data. After 15 seconds the red LED will change to flashing 0.1sec on/0.9sec off.
NOTE: After 5 seconds the red LED will start to flash 0.5sec on/0.5sec off, but continue to hold the button).
2.Release the push button.
3.Press and hold the receiver box push button for 5 seconds to enter the binding mode. The Red LED will start flashing at 0.5sec on/0.5sec off to confirm the binding mode has been entered.
4.Move the room thermostat slider to the OFF position and press the and buttons together along with the button. The unit will display InSt and ‘CONTROL BINDING’.
5.Press the green button to send the binding signal out to the receiver box. The red LED is switched off to confirm successful binding operation. If the red LED still flashes push the button again until binding is successful.
6.Now go to Section 2) Installing the CM900 Wireless System to setup the system.
5.2 Multi-Zone System
Multiple room thermostats and receiver box sets can also be used to control
NOTE: Some of the labels supplied with the pack are for use in multizone applications.
Installation Guide | 11 |