5) Additional Installation Information

5.1 Binding / Rebinding Procedure

The binding operation described below is required if:

Any of the system components (room thermostat or receiver box) are replaced.

The receiver box has incorrect or no binding data stored (e.g. when pre-bound system pack components have been mismatched).

NOTE: During the binding procedure keep approximately 1m distance between the room thermostat and the receiver box.

To bind/rebind:

1.Press and hold the receiver box push button for 15 seconds to reset any previously stored data. After 15 seconds the red LED will change to flashing 0.1sec on/0.9sec off.

NOTE: After 5 seconds the red LED will start to flash 0.5sec on/0.5sec off, but continue to hold the button).

2.Release the push button.

3.Press and hold the receiver box push button for 5 seconds to enter the binding mode. The Red LED will start flashing at 0.5sec on/0.5sec off to confirm the binding mode has been entered.

4.Move the room thermostat slider to the OFF position and press the and buttons together along with the button. The unit will display InSt and ‘CONTROL BINDING’.

5.Press the green button to send the binding signal out to the receiver box. The red LED is switched off to confirm successful binding operation. If the red LED still flashes push the button again until binding is successful.

6.Now go to Section 2) Installing the CM900 Wireless System to setup the system.

5.2 Multi-Zone System

Multiple room thermostats and receiver box sets can also be used to control multi-zone systems and the CM927/921 room thermostat is compatible with a variety of other Honeywell products including HR80 radiator controllers and HCE80 underfloor heating controllers. If you intend to use it in this way additional installation and user instructions can be obtain by contacting the address at the end of this guide.

NOTE: Some of the labels supplied with the pack are for use in multizone applications.

Installation Guide

11

Image 12
Contents 42011076-003 Table of Contents DescriptionInstallation Information Installing the CM900 Wireless System Installing the Receiver BoxInstalling the Room Thermostat 2.2.1 Power Up RF Communication Check Test ModeLocating the Room Thermostat System CheckInstaller Mode Basic Operation of the SystemAutomatic Operation Temporary Manual OverrideEntering Installer Mode HC60NG Receiver Box Fail-Safe Mode SetupUsing the Room Thermostat for Specific Applications Using the Special Features of the Room ThermostatCategory 1 Parameters Room Thermostat Settings Category 2 System Settings Additional Installation Information Binding / Rebinding ProcedureMulti-Zone System Trouble Shooting Trouble Shooting GuideDiagnostic Mode