Carrier 33CS450-01 owner manual Advanced Setup Table

Page 105

SECTION 24

 

 

 

 

 

 

 

 

 

Advanced Setup Table

 

 

 

 

Carrier

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Step#

Description

Pg#

Range

Df*

 

Step#

Description

Pg#

Range

 

Df*

1

Programmable

4.2

Yes/No

Yes

27

Minutes Between

13.6

0-60min

 

2

 

Thermostat

 

 

 

 

 

Stage 1 & 2

 

 

 

 

2

Auto-Changeover

4.3

Yes/No

Yes

28

Minutes Between

13.6

0-60min

 

2

 

Thermostat

 

 

 

 

 

Stage 2 & 3

 

 

 

 

3

Fan Off Delay

7.3

0, 30, 60,

0

29

2nd Stage turn off at

13.7

On/Off

 

Off

 

 

 

 

90

 

 

 

setpoint

 

 

 

 

4

Fan Purge

7.4

0 - 3 hrs.

0

 

30

Programmable

14.3

Off/Time/

 

Off

5

Thermoglow

8.2

Auto/On/

Au-

 

 

Output

 

Temp/Aux

 

 

 

Backlight

 

Off

to

 

31

Programmable

14.4

NO/NC

 

NO

6

F or C

8.2

F/C

F

 

 

Output Polarity

 

 

 

 

7

Security Level

8.4

0 - 3

0

 

32

7 Day/1 Day

14.4

7Day/

 

7

8

Max Heat Setpoint

8.4

35 - 99

80

 

 

Programmable Output

 

1Day

 

 

33

Programmable Output

14.4

Mo - Su

 

Mo

9

Min Cool Setpoint

8.4

35 - 99

65

 

10

Cool to Dehumidify

10.4

On/Off

Off

 

 

Output Day of the Week

 

 

 

 

 

 

 

24 Hour

 

 

11

Maximum Dehum

10.4

0 - 5

3

34

Programmable Output

14.4

 

7am

 

Overshoot

 

 

 

 

 

Start Time

 

 

 

 

 

 

 

 

35

Programmable Output

14.5

24 Hour

 

9pm

12

Reheat Operation

10.5

On/Off

Off

 

13

DEHUM Terminal

10.6

NO/NC

NC

 

 

Stop Time

 

 

 

 

 

Polarity

 

 

 

36

Programmable Output

14.6

35 -125

 

80

14

Energy Watch -

11.2

read only

- -

 

 

Temp. Setpoint

 

 

 

 

 

Heat Timer

 

 

 

37

Thermostat control

15.3

Yes/No

 

No

15

Energy Watch -

11.3

read only

- -

 

 

to RS1?

 

 

 

 

 

Cool Timer

 

 

 

38

Thermostat Sensor

15.4

On/Off

 

Off

16

Override Run-Time

11.4

read only

- -

 

 

Averaging

 

 

 

 

39

Dry Contact

16.2

Yes/No

 

Yes

17

Reset Service

11.5

read only

- -

 

 

Humidify Icon

 

 

 

 

 

Operation

 

 

 

 

 

 

 

 

 

40

Dry Contact Polarity

16.2

NO/NC

 

NO

18

Reset UV Light Icon

11.6

read only

- -

 

 

41

Dry Contact

16.3

Occ. 1/

 

Occ.

19

Heatpump Jumper

12.2

read only

- -

 

 

Setting

 

 

 

 

 

Programming

 

Service

 

1

20

Reversing Valve

12.2

read only

- -

 

 

 

 

 

Pan

 

 

 

42

Light Activated

17.2

Yes/No

 

No

 

Jumper Setting

 

 

 

 

 

 

 

 

 

43

Energy Save

18.1

Off/On

 

Off

21

Electric Heat

12.3

read only

- -

 

 

44

Reset Service Filter

19.2

read only

 

- -

22

Minimum Heat/Cool

13.2

0 - 6

2

 

 

Differential

 

 

 

 

 

Icon

 

 

 

 

 

 

 

 

45

Service Filter Run

19.2

0 - 1950

 

0

23

Cycles Per Hour

13.3

d1, d, 2-6

6

 

24

Deadband/Temp.

13.5

1 - 6

2

 

 

Time Set

 

 

 

 

 

Swing 1st Stage

 

 

 

46

UV Light Run-Time

19.3

0 - 1990

 

0

25

Deadband/Temp.

13.5

0 - 10

2

 

 

Set

 

 

 

 

47

Service Humidify

19.4

0 - 1990

 

0

 

Swing 2nd Stage

 

 

 

 

26

Deadband/Temp.

13.5

0 - 10

2

 

 

Run-Time Set

 

 

 

 

 

Swing 3rd Stage

 

 

 

48

Viewing the Remote

22.4

- -

 

- -

 

 

 

 

 

 

Sensor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temperature(s)

 

 

 

 

*Df = Factory Default Setting

24

Page 24.1

Image 105
Contents DAY Carrier How to Use This Manual Glossary of Terms Page Table of Contents Contents Setting the Day Setting the ClockSelecting the Heat or Cool Mode Adjusting the setpoints Selecting Your Desired TemperatureFront Panel Buttons Display Features Glows red Front PanelI888 Pm Display FeaturesOccupied & Unoccupied icons Section AUX Heat Contents At the same time Contents Button to enter Setup screens Programmable or Non-Programmable ThermostatMODE, press the Program Manual or Auto-Changeover Thermostat Cool I200 Su Pm70 68HEAT Program On Selecting Your Desired Temperature adjusting setpoints Viewing the Outside Temperature Viewing the Indoor Humidity Temperature Viewing the Outside TemperaturePress the Program For the dayTo view the indoor humidity Viewing the Indoor HumiditySchedule Overriding the DailyPress Programming a Daily Schedule600 Pm Or each time, this routine will repeat Programming Tips Overriding the Daily Schedule Fan Purge Operation Using the Fan Button Smart Fan OperationSmart Fan Operation Using the Fan ButtonSetting the Fan-Off Time Delay Press the Mode button repeatedlyUntil this setup screen appears 000 Fan Purge OperationLevel Programming a SecurityTurning On/Off the Backlight I20085 Locking/Unlocking the KeypadProgramming a Security Level Setpoint Installing the HumidityBack of 33CS450-01 Installing the Humidity ModuleImportant Caution Setting a Thermostat Jumper for Humidity OperationAdjusting the Humidification Setpoint Humidity Setup screenPress the Humidity Button to enter 10.3 Using the Dehum10.5 10.6Setting a Thermostat Jumper for Dehumidification Operation Press the Mode button once Adjusting the Dehumidification SetpointAppears only if is set to on Using Your Air Conditioner to DehumidifyUsing the Reheat Function Using the Dehum Terminal Run-Time 11.3 Run-Time 11.2Run-Time 11.4 Run-Time 11.5Viewing the Heat Run-Time Energy Watch Viewing the Cool Run-Time Energy Watch Viewing the Override Operation Run-Time Viewing the Humidification Run-Time Viewing the UV Light Run-Time Electric Heat and Heat Pump Operation Viewing the Heat Pump Reversing Valve Jumper Settings Viewing the Electric Heat Jumper Setting Using Emergency Heat Selecting 2nd Stage Turn Off Temperature 13.7 13.313.6 Adjusting the Heat/Cool Differential Adjusting the Cycles Per Hour Temperature from the setpoint is equal to or greater Adjusting the Deadband2Setup Adjusting the Minutes of Run-Time Before the Next Stage Select On or Off On 2nd stage will Selecting 2nd Stage Turn Off TemperatureConfiguring a Thermostat Output Prog Possible Time scenarios Time-Based Control Programmable OutputAm Start Pm Stop Setup35 Temperature-Based Control Internet/Phone Control Programmable Output Until this setup screen appearsInstalling the Remote 15.215.4 Installing the Remote Sensors Controlling or Reading Remote Temperature RS1 Averaging the Remote Sensor RS1 with the Thermostat Sensor Contents Appears only if is YES Dry Contact OperationOccupied Dry Contact ProgrammingClosure of the Dry Contact to force Occupied 1 time period Random Start OperationSetting up the Thermostat For Light Activated Adjusting the Light Sensor 17.317.2 Setting up the Thermostat for Light Activated Operation Light Sensor Adjustment Screw Adjusting the Light SensorEnergy Save Operation How to Use the Energy Save Feature19.2 Setting and Resetting Service Filter Fan Run-TimeHow to Set and Reset the Service Filter Fan Run-Time Alert How to Set and Reset the UV Light Run-Time Alert How to Set and Reset the Humidifier Run-Time Alert Holiday programming setup Press the Holiday button to enterSteps Overriding the Holiday Mode Programming Holiday Mode21.3 Configuring the Jumpers 21.2Configuring the Jumpers W3 Jumper Setting Explanation of Jumper SettingsHUM Jumper Setting Econ Jumper Setting Factory Defaults, Calibration, and Sensors Factory Default Settings for default values see Resetting the Thermostat toI200 Pm Calibrating the Temperature and Humidity SensorsUntil setup step #48 appears Viewing the Remote Temperature SensorsAccessories Advanced Setup Table Section Index Holiday TOTALINECarrierIndex Index Energy Save IndexWarranty Programming Worksheet

33CS450-01 specifications

The Carrier 33CS450-01 is a highly efficient and reliable air conditioning unit that has been designed to meet the cooling needs of residential and light commercial spaces. As a part of Carrier's comprehensive range of HVAC solutions, this model stands out due to its advanced features, energy efficiency, and user-friendly technology.

One of the standout features of the Carrier 33CS450-01 is its remarkable SEER (Seasonal Energy Efficiency Ratio) rating, which indicates high energy efficiency and low operational costs. This makes it an excellent choice for environmentally conscious consumers looking to reduce their carbon footprint while enjoying comfortable indoor conditions.

Equipped with a quiet operation mode, this model ensures that noise levels are kept to a minimum, making for a more peaceful living environment. This is particularly beneficial for homes located in densely populated areas or for individuals sensitive to noise. The compressor design also contributes to the overall silent operation, allowing for a seamless cooling experience without intrusive background noise.

The Carrier 33CS450-01 employs a single-stage compressor, which facilitates straightforward installation and maintenance. The unit is designed for easy access, making service and repairs uncomplicated and hassle-free. Additionally, the model is equipped with a robust cabinet construction that ensures durability and longevity, making it a long-term investment for homeowners.

In terms of technology, the Carrier 33CS450-01 comes with advanced refrigerant management, utilizing environmentally friendly R-410A refrigerant. This not only enhances energy efficiency but also aligns with contemporary environmental standards. The unit is also designed with a precision cooling system that enables it to maintain consistent temperatures across different climates, ensuring optimal performance year-round.

The installation flexibility of the Carrier 33CS450-01 is another attractive feature. It can be easily integrated into existing systems or installed as a standalone unit, making it suitable for various applications. Furthermore, Carrier's commitment to innovation is evident in this model’s design, incorporating features like a protective coil guard and enhanced airflow design that maximizes performance while minimizing energy consumption.

Overall, the Carrier 33CS450-01 offers a winning combination of efficiency, quiet operation, and easy maintenance, making it a top choice for homeowners and businesses looking for dependable cooling solutions.