Carrier 33CS450-01 owner manual Explanation of Jumper Settings, W3 Jumper Setting

Page 97

Carrier

Explanation of Jumper Settings

W3 JUMPER SETTING

If the jumper for MISC1, MISC2, or MISC3 is set to W3, the corresponding MISC screw terminal on the backplate will control a third stage of heat.

W3 MULTI-STAGE OPERATION EXPLAINED - PAGE 13.4

The 3rd Stage of Heat is turned on when:

(A)The 1st and 2nd stages have been on for the time required (steps 27

and 28, page 13.6). It is adjustable from 0-60 minutes and the default And is two minutes.

(B)The temperature from the setpoint is equal to or greater than: the set- point plus the 1st stage deadband (step #24, 13.5), plus the 2nd stage deadband (step #25, 13.5) plus the 3rd stage deadband (step #26, 13.5). This 3rd stage deadband is adjustable from 0-10 degrees and the default is two degrees.

 

 

Heating

 

 

Cooling

 

 

Deadband

Deadband

Deadband

Deadband

Deadband

 

 

db 3

db 2

db 1

db 1

db 2

 

 

(adj. 0-10 )

(adj. 0-10 )

(adj. 1-6 )

(adj. 1-6 )

(adj. 0-10 )

 

3rd Stage

2nd Stage

1st Stage

Heat

Cool

1st Stage

2nd Stage

turn on

turn on

turn on

Setpoint

Setpoint

turn on

turn on

DECREASE TEMPERATURE INCREASE

PROG JUMPER SETTING

If the jumper for MISC1, MISC2, or MISC3 is set to PROG, the corresponding MISC screw terminal on the backplate will control a pilot relay or other accessory.

PROGRAMMABLE OUTPUT - SECTION 14

This jumper setting allows the MISC outputs to control a pilot relay by time, temperature, or a signal from the Internet/Phone. The following are three possible scenarios:

By Time: A device that requires a start and stop time. For example, 21 an exterior lighting system that needed to be energized every day

between the hours of 8pm and 1am.

By Temperature: An exhaust fan that needs to energize whenever the temperature from RS1 rises above 90 degrees F.

By Remote: Remotely arming a security system through the web or phone.

Page 21.3

Image 97
Contents DAY Carrier How to Use This Manual Glossary of Terms Page Table of Contents Contents Setting the Day Setting the ClockSelecting the Heat or Cool Mode Adjusting the setpoints Selecting Your Desired TemperatureFront Panel Buttons Display Features Glows red Front PanelI888 Pm Display FeaturesOccupied & Unoccupied icons Section AUX Heat Contents At the same time Contents Programmable or Non-Programmable Thermostat Button to enter Setup screensMODE, press the Program Manual or Auto-Changeover Thermostat Cool I200 Su Pm70 68HEAT Program On Selecting Your Desired Temperature adjusting setpoints Viewing the Outside Temperature Viewing the Indoor Humidity Temperature Viewing the Outside TemperaturePress the Program For the dayTo view the indoor humidity Viewing the Indoor HumiditySchedule Overriding the DailyPress Programming a Daily Schedule600 Pm Or each time, this routine will repeat Programming Tips Overriding the Daily Schedule Fan Purge Operation Using the Fan Button Smart Fan OperationSmart Fan Operation Using the Fan ButtonPress the Mode button repeatedly Setting the Fan-Off Time DelayUntil this setup screen appears 000 Fan Purge OperationLevel Programming a SecurityTurning On/Off the Backlight I20085 Locking/Unlocking the KeypadProgramming a Security Level Setpoint Installing the HumidityBack of 33CS450-01 Installing the Humidity ModuleImportant Caution Setting a Thermostat Jumper for Humidity OperationHumidity Setup screen Adjusting the Humidification SetpointPress the Humidity Button to enter 10.3 Using the Dehum10.5 10.6Setting a Thermostat Jumper for Dehumidification Operation Press the Mode button once Adjusting the Dehumidification SetpointAppears only if is set to on Using Your Air Conditioner to DehumidifyUsing the Reheat Function Using the Dehum Terminal Run-Time 11.3 Run-Time 11.2Run-Time 11.4 Run-Time 11.5Viewing the Heat Run-Time Energy Watch Viewing the Cool Run-Time Energy Watch Viewing the Override Operation Run-Time Viewing the Humidification Run-Time Viewing the UV Light Run-Time Electric Heat and Heat Pump Operation Viewing the Heat Pump Reversing Valve Jumper Settings Viewing the Electric Heat Jumper Setting Using Emergency Heat 13.3 Selecting 2nd Stage Turn Off Temperature 13.713.6 Adjusting the Heat/Cool Differential Adjusting the Cycles Per Hour Temperature from the setpoint is equal to or greater Adjusting the Deadband2Setup Adjusting the Minutes of Run-Time Before the Next Stage Select On or Off On 2nd stage will Selecting 2nd Stage Turn Off TemperatureConfiguring a Thermostat Output Prog Possible Time scenarios Time-Based Control Programmable OutputAm Start Pm Stop Setup35 Temperature-Based Control Internet/Phone Control Programmable Output Until this setup screen appears15.2 Installing the Remote15.4 Installing the Remote Sensors Controlling or Reading Remote Temperature RS1 Averaging the Remote Sensor RS1 with the Thermostat Sensor Contents Appears only if is YES Dry Contact OperationOccupied Dry Contact ProgrammingClosure of the Dry Contact to force Occupied 1 time period Random Start OperationAdjusting the Light Sensor 17.3 Setting up the Thermostat For Light Activated17.2 Setting up the Thermostat for Light Activated Operation Light Sensor Adjustment Screw Adjusting the Light SensorEnergy Save Operation How to Use the Energy Save Feature19.2 Setting and Resetting Service Filter Fan Run-TimeHow to Set and Reset the Service Filter Fan Run-Time Alert How to Set and Reset the UV Light Run-Time Alert How to Set and Reset the Humidifier Run-Time Alert Press the Holiday button to enter Holiday programming setupSteps Overriding the Holiday Mode Programming Holiday Mode21.3 Configuring the Jumpers 21.2Configuring the Jumpers W3 Jumper Setting Explanation of Jumper SettingsHUM Jumper Setting Econ Jumper Setting Factory Defaults, Calibration, and Sensors Factory Default Settings for default values see Resetting the Thermostat toI200 Pm Calibrating the Temperature and Humidity SensorsUntil setup step #48 appears Viewing the Remote Temperature SensorsAccessories Advanced Setup Table Section Index Holiday TOTALINECarrierIndex Index Energy Save IndexWarranty Programming Worksheet

33CS450-01 specifications

The Carrier 33CS450-01 is a highly efficient and reliable air conditioning unit that has been designed to meet the cooling needs of residential and light commercial spaces. As a part of Carrier's comprehensive range of HVAC solutions, this model stands out due to its advanced features, energy efficiency, and user-friendly technology.

One of the standout features of the Carrier 33CS450-01 is its remarkable SEER (Seasonal Energy Efficiency Ratio) rating, which indicates high energy efficiency and low operational costs. This makes it an excellent choice for environmentally conscious consumers looking to reduce their carbon footprint while enjoying comfortable indoor conditions.

Equipped with a quiet operation mode, this model ensures that noise levels are kept to a minimum, making for a more peaceful living environment. This is particularly beneficial for homes located in densely populated areas or for individuals sensitive to noise. The compressor design also contributes to the overall silent operation, allowing for a seamless cooling experience without intrusive background noise.

The Carrier 33CS450-01 employs a single-stage compressor, which facilitates straightforward installation and maintenance. The unit is designed for easy access, making service and repairs uncomplicated and hassle-free. Additionally, the model is equipped with a robust cabinet construction that ensures durability and longevity, making it a long-term investment for homeowners.

In terms of technology, the Carrier 33CS450-01 comes with advanced refrigerant management, utilizing environmentally friendly R-410A refrigerant. This not only enhances energy efficiency but also aligns with contemporary environmental standards. The unit is also designed with a precision cooling system that enables it to maintain consistent temperatures across different climates, ensuring optimal performance year-round.

The installation flexibility of the Carrier 33CS450-01 is another attractive feature. It can be easily integrated into existing systems or installed as a standalone unit, making it suitable for various applications. Furthermore, Carrier's commitment to innovation is evident in this model’s design, incorporating features like a protective coil guard and enhanced airflow design that maximizes performance while minimizing energy consumption.

Overall, the Carrier 33CS450-01 offers a winning combination of efficiency, quiet operation, and easy maintenance, making it a top choice for homeowners and businesses looking for dependable cooling solutions.