Carrier 33CS450-01 owner manual Adjusting the Light Sensor, Light Sensor Adjustment Screw

Page 87

Carrier

Adjusting the Light Sensor

The light sensor can be adjusted for variable degrees of sensitivity. The sensitivity adjustment screw is located on the side of the thermostat, as illustrated below. Turning the screw clockwise increases the sensitivity of the sensor to light.

To check for correct sensitivity, place the thermostat in the Program On mode. When the lights are on the thermostat should enter Occupied 1 and blink the Occupied 1 icon. If the thermostat does not enter Occupied 1 while the lights are on, use the supplied screw driver to turn the light sensor screw clockwise until the Occupied 1 icon appears on the display. The thermostat should enter an unoccupied period when the lights are off. If the sensor does not enter an unoccupied period when the lights are turned off, use the supplied screw driver to turn the light sensor screw counterclockwise until the Unoccupied icon appears on the display, with the lights off.

The Light Sensor Adjustment Screw

is located on the side of the thermostat.

17

Light Sensor

Adjustment Screw

Turn the screw clockwise to INCREASE light sensor sensitivity

Turn the screw counter- clockwise to DECREASE light sensor sensitivity

Due to varying lighting conditions, light activation may not be suitable for all installations.

Page 17.3

Image 87
Contents DAY Carrier How to Use This Manual Glossary of Terms Page Table of Contents Contents Setting the Day Setting the ClockSelecting the Heat or Cool Mode Adjusting the setpoints Selecting Your Desired TemperatureFront Panel Buttons Display Features Glows red Front PanelI888 Pm Display FeaturesOccupied & Unoccupied icons Section AUX Heat Contents At the same time Contents Button to enter Setup screens Programmable or Non-Programmable ThermostatMODE, press the Program Manual or Auto-Changeover Thermostat Cool I200 Su Pm70 68HEAT Program On Selecting Your Desired Temperature adjusting setpoints Viewing the Outside Temperature Viewing the Indoor Humidity For the day Viewing the Outside TemperatureTemperature Press the ProgramTo view the indoor humidity Viewing the Indoor HumiditySchedule Overriding the DailyPress Programming a Daily Schedule600 Pm Or each time, this routine will repeat Programming Tips Overriding the Daily Schedule Fan Purge Operation Using the Fan Button Smart Fan OperationSmart Fan Operation Using the Fan ButtonSetting the Fan-Off Time Delay Press the Mode button repeatedlyUntil this setup screen appears 000 Fan Purge OperationLevel Programming a SecurityTurning On/Off the Backlight I20085 Locking/Unlocking the KeypadProgramming a Security Level Setpoint Installing the HumidityBack of 33CS450-01 Installing the Humidity ModuleImportant Caution Setting a Thermostat Jumper for Humidity OperationAdjusting the Humidification Setpoint Humidity Setup screenPress the Humidity Button to enter 10.6 Using the Dehum10.3 10.5Setting a Thermostat Jumper for Dehumidification Operation Press the Mode button once Adjusting the Dehumidification SetpointAppears only if is set to on Using Your Air Conditioner to DehumidifyUsing the Reheat Function Using the Dehum Terminal Run-Time 11.5 Run-Time 11.2Run-Time 11.3 Run-Time 11.4Viewing the Heat Run-Time Energy Watch Viewing the Cool Run-Time Energy Watch Viewing the Override Operation Run-Time Viewing the Humidification Run-Time Viewing the UV Light Run-Time Electric Heat and Heat Pump Operation Viewing the Heat Pump Reversing Valve Jumper Settings Viewing the Electric Heat Jumper Setting Using Emergency Heat Selecting 2nd Stage Turn Off Temperature 13.7 13.313.6 Adjusting the Heat/Cool Differential Adjusting the Cycles Per Hour Temperature from the setpoint is equal to or greater Adjusting the Deadband2Setup Adjusting the Minutes of Run-Time Before the Next Stage Select On or Off On 2nd stage will Selecting 2nd Stage Turn Off TemperatureConfiguring a Thermostat Output Prog Possible Time scenarios Time-Based Control Programmable OutputAm Start Pm Stop Setup35 Temperature-Based Control Internet/Phone Control Programmable Output Until this setup screen appearsInstalling the Remote 15.215.4 Installing the Remote Sensors Controlling or Reading Remote Temperature RS1 Averaging the Remote Sensor RS1 with the Thermostat Sensor Contents Appears only if is YES Dry Contact OperationOccupied Dry Contact ProgrammingClosure of the Dry Contact to force Occupied 1 time period Random Start OperationSetting up the Thermostat For Light Activated Adjusting the Light Sensor 17.317.2 Setting up the Thermostat for Light Activated Operation Light Sensor Adjustment Screw Adjusting the Light SensorEnergy Save Operation How to Use the Energy Save Feature19.2 Setting and Resetting Service Filter Fan Run-TimeHow to Set and Reset the Service Filter Fan Run-Time Alert How to Set and Reset the UV Light Run-Time Alert How to Set and Reset the Humidifier Run-Time Alert Holiday programming setup Press the Holiday button to enterSteps Overriding the Holiday Mode Programming Holiday Mode21.3 Configuring the Jumpers 21.2Configuring the Jumpers W3 Jumper Setting Explanation of Jumper SettingsHUM Jumper Setting Econ Jumper Setting Factory Defaults, Calibration, and Sensors Factory Default Settings for default values see Resetting the Thermostat toI200 Pm Calibrating the Temperature and Humidity SensorsUntil setup step #48 appears Viewing the Remote Temperature SensorsAccessories Advanced Setup Table Section Index Holiday TOTALINECarrierIndex Index Energy Save IndexWarranty Programming Worksheet

33CS450-01 specifications

The Carrier 33CS450-01 is a highly efficient and reliable air conditioning unit that has been designed to meet the cooling needs of residential and light commercial spaces. As a part of Carrier's comprehensive range of HVAC solutions, this model stands out due to its advanced features, energy efficiency, and user-friendly technology.

One of the standout features of the Carrier 33CS450-01 is its remarkable SEER (Seasonal Energy Efficiency Ratio) rating, which indicates high energy efficiency and low operational costs. This makes it an excellent choice for environmentally conscious consumers looking to reduce their carbon footprint while enjoying comfortable indoor conditions.

Equipped with a quiet operation mode, this model ensures that noise levels are kept to a minimum, making for a more peaceful living environment. This is particularly beneficial for homes located in densely populated areas or for individuals sensitive to noise. The compressor design also contributes to the overall silent operation, allowing for a seamless cooling experience without intrusive background noise.

The Carrier 33CS450-01 employs a single-stage compressor, which facilitates straightforward installation and maintenance. The unit is designed for easy access, making service and repairs uncomplicated and hassle-free. Additionally, the model is equipped with a robust cabinet construction that ensures durability and longevity, making it a long-term investment for homeowners.

In terms of technology, the Carrier 33CS450-01 comes with advanced refrigerant management, utilizing environmentally friendly R-410A refrigerant. This not only enhances energy efficiency but also aligns with contemporary environmental standards. The unit is also designed with a precision cooling system that enables it to maintain consistent temperatures across different climates, ensuring optimal performance year-round.

The installation flexibility of the Carrier 33CS450-01 is another attractive feature. It can be easily integrated into existing systems or installed as a standalone unit, making it suitable for various applications. Furthermore, Carrier's commitment to innovation is evident in this model’s design, incorporating features like a protective coil guard and enhanced airflow design that maximizes performance while minimizing energy consumption.

Overall, the Carrier 33CS450-01 offers a winning combination of efficiency, quiet operation, and easy maintenance, making it a top choice for homeowners and businesses looking for dependable cooling solutions.