Bryant TSTATBBPB501 manual About Advanced Features & Operation

Page 17

About Advanced Features & Operation

2 STAGE OPERATION - The 2nd Stage of heat or cool is turned on when (1) the 1st Stage has been on for a minimum of two minutes, and (2) the temperature spread from the setpoint is equal to or greater than: the setpoint plus the deadband, plus 2 degrees.

Heating

Cooling

2 degrees

Dead Band

Dead

Band

2 degrees

2nd Stage

1st Stage

Heat

Cool

1st Stage

2nd Stage

turn on

turn on

Setpoint

Setpoint

turn on

turn on

MINIMUM HEAT/COOL SETPOINT DIFFERENCE - The Heat and Cool setpoints will not be allowed to come any closer to each other than the value set in Advanced Setup step

#7, on page 13. This minimum difference is enforced during Auto changeover and Program On operation.

Page 16

Image 17
Contents O G R a M M a B L E D I G I T a L E R M O S T a T Table Of Contents Advanced Setup About Advanced Operation WarrantyFront Panel Display I200 PmDisplay I200 Basic Operation Select ModeI200 Pm Programming Time periods Programming 530 PmI30 Pm Night Time period programming I200 Am Advanced Setup81f Select the cycles per Hour limit Advanced Setup Table About Advanced Features & Operation I200 I200 Am Night About Advanced Features & Operation About Advanced Features & Operation Warranty