DUAL SETPOINT BEHAVIOR - The adjustable setpoint range is: 35 - 99 degrees in Fahrenheit and 7 - 35 degrees in Centigrade. When in the modes Heat or Cool, this adjustable range is unhampered.

When adjusting any Auto mode, including programming Occupied and Unoccupied periods, the 1050 will not allow the Heat setpoint to get closer to the Cool setpoint than the value programmed as the minimum difference in step 7, page 13.

When entering the Auto mode from Cool, the Heat and Cool setpoints will remain spread apart by the amount that they were adjusted, prior to entering Auto.

For example: If the Cool setpoint was set to 80 while in the Cool mode and the Heat setpoint was adjusted to 70 while in the Heat mode, upon entering the Auto mode the Heat and Cool setpoints would be 80 and 70. Both setpoints would then move up and down together, (in this example spread by 10 degrees), by pressing the up or down buttons.

To move the Heat and Cool setpoints closer together, enter the Cool or Heat mode by pressing the Mode button, then adjust the setpoint(s) closer together. Heat is limited to how close it can come to Cool by step 7, page 13.

Page 19

Image 20
Contents O G R a M M a B L E D I G I T a L E R M O S T a T Advanced Setup About Advanced Operation Warranty Table Of ContentsFront Panel I200 Pm DisplayDisplay I200 Select Mode Basic OperationI200 Pm Programming Time periods 530 Pm ProgrammingI30 Pm Night Time period programming Advanced Setup I200 Am81f Select the cycles per Hour limit Advanced Setup Table About Advanced Features & Operation I200 I200 Am Night About Advanced Features & Operation About Advanced Features & Operation Warranty