Test Running

Test Running

1.Check that all tubing and wiring have been properly connected.

2.Check that the gas and liquid side service valves are fully open.

Prepare remote control

1. Remove the battery cover by pulling it according to the arrow direction.

2. Insert new batteries making sure that the (+) and (–) of battery are installed correctly.

3.Reattach the cover by pushing it back into position.

NOTE:

Use 2 AAA(1.5volt) batteries. Do not use rechargeable batteries.

Remove the batteries from the remote control if the system is not going to be used for a long time.

Settlement of outdoor unit

Anchor the outdoor unit with a bolt and

nut(ø 10mm(0.39in) tightly and horizontally on a concrete or rigid mount.

When installing on the wall, roof or rooftop, anchor the mounting base securely with a nail or wire assuming the influence of wind and earthquake.

In the case when the vibration of the unit is con- veyed to the hose, secure the unit with an anti- vibration rubber.

Bolt

Tubing connection

Evaluation of the performance

Operate unit for 15~20 minutes, then check the system refrigerant charge:

1. Measure the pressure of the gas side service valve.

2.Measure the temperature of the intake and discharge of air.

3.Ensure the difference between the intake tem- perature and the discharge is more than 46.4°F(8°C) (Cooling) or (Heating).

Intake temperature

Discharge air

Discharge

temperature

4.For reference; the gas side pressure of optimum condition is as below.(Cooling)

Outside ambient TEMP.

The pressure of the gas side service valve

 

 

95°F(35°C)

8.5~9.5kg/cm2 G(120~135 P.S.I.G.)

NOTE: If the actual pressure are higher than shown, the system is most likely over- charged, and charge should be removed. If the actual pressure are lower than shown, the system is most likely undercharged, and charge should be added.

The air conditioner is now ready for use.

PUMP DOWN

This is performed when the unit is to be relocated or the refrigerant circuit is serviced.

Pump Down means collecting all refrigerant in the out- door unit without loss of refrigerant.

CAUTION:

Be sure to perform Pump Down procedure with the unit cooling mode.

Pump Down Procedure

1.Connect a low-pressure gauge manifold hose to the charge port on the gas side service valve.

2.Open the gas side service valve halfway and purge the air from the manifold hose using the refrigerant gas.

3.Close the liquid side service valve(all the way in).

4.Turn on the unit's operating switch and start the cooling operation.

5.When the low-pressure gauge reading becomes 1 to 0.5kg/cm2 G(14.2 to 7.1 P.S.I.G.), fully close the gas side valve stem and then quickly turn off the unit. At that time, Pump Down has been completed and all refriger- ant will have been collected in the outdoor unit.

32Room Air Conditioner

Image 32
Contents Room Air Conditioner Table of Contents Safety Precautions InstallationDo not modify or extend the power cord Be sure not to do Be sure to follow the instructionOperation Moisture may condense and wet or damage furnishings Keep level even when installing the product Do not direct airflow at room occupants Do not block the inlet or outlet of air flowReplace all the batteries in the remote DisuseDo not drink the water drained from the unit Indoor Unit DimensionsSymbols Used in this Manual Outdoor Unit 12kFeatures IntroductionInstallation Tools InstallationInstallation Parts Installation Map Bushing-SleeveConfirm The Refrigerant This Product Contains R-410A RefrigerantOutdoor unit Rooftop InstallationsIndoor unit Piping Length and Elevation How to Mount Installation Plate Drill a Hole In The WallFlaring Work Cut the pipes and the cableBurrs removal Putting nut onIndoor Connecting The PipingIndoor unit installation Wrap the insulation material around the connecting portion Tighten the flare nut with a wrenchInsert the connecting cable into the indoor unit Indoor unit installationPiping for passage through piping hole Correct case Incorrect caseConnection of The Drain Hose Connection of Piping -OutdoorWiring Diagram Connection of The CableFront panel removing How to use the front panel Front panel openingFront panel closing Checking The Drainage Drain pipingForming The Piping Air Purging Air purging With Vacuum PumpPreparation Leak testEvacuation Finishing the jobCharging Prepare remote control Test RunningSettlement of outdoor unit Evaluation of the performanceCooling Mode Operation Healthy Dehumidification ModeOperation Function of ControlsHeating Mode Operation Defrost ControlSleep Timer Operation Chaos Natural Wind ModeJet Cool Mode Operation C/O Model Jet Cool Mode Operation H/P ModelForced operation Test operationAuto restart Protection of the evaporator pipe from frostingHeating Model Display FunctionSelf-diagnosis Function Remote Control Operations Operation ModeDisassembly To remove the Grille from the ChassisTo remove the Control Box To remove the Motor Cover Troubleshooting Guide Refrigeration Cycle DiagramCooling Only Models Cooling & Heating ModelsWay, 3-way Valve Way Valve Liquid SideProcedure Pumping DownBalance Refrigerant of the 3-way Valve Vacuum pump Gas Charging After EvacuationMethod of using graph Method of using equationAccording to Indoor & Outdoor Temperature Additional gas chargingCycle Parts Trouble analysisElectronic Parts Product does not operate at allProduct is not operate with the remote controller Compressor/Outdoor Fan are unable to drive When indoor Fan does not operate NectorWhen Vertical Louver does not operate When a comunication error occurs Phenomena in case of connecting error Indoor UnitOutdoor Unit Schematic Diagram Electric Control DeviceOutdoor 12k Wiring Diagram Models 12kModels 12kC/O Models 12kH/P Components Location Outdoor12k 6871A00087B 6871A00088A6871A20259D 6306A90009AProduct Specifications Cooling OnlyCooling & Heating E.R P.EExploded View Outdoor Unit 12k Btu/h Seriess W0CZZReplacement Parts List Parts List IndoorParts List Outdoor No. MFL31443001

LA121HPMI, LAU121CNM, LAN121CNM, LAN121CNM, LAU121CNM, LA121HPMI, LA121HPMO, LAN121HNM, LAU121HNM, LA121CPMI, LA121CPMO specifications

LG Electronics has established itself as a leader in innovative home appliance technologies, particularly in the air conditioning segment. The LG LAN121CNM, LAU121CNM, LA121HPMI, LA121HPMO, LAN121HNM, LAU121HNM, LA121CPMI, and LA121CPMO models exemplify the blend of efficiency, comfort, and advanced features that LG is known for.

These air conditioning units are designed with energy efficiency in mind, boasting high SEER (Seasonal Energy Efficiency Ratio) ratings that help reduce electricity consumption. This not only saves money on energy bills but also aligns with eco-friendly initiatives by minimizing environmental impact.

The air conditioners are equipped with LG's Dual Inverter technology, which enhances cooling performance while reducing noise levels. This innovative technology allows the compressor to operate at variable speeds, resulting in faster cooling and dehumidification, as well as quieter operation than traditional units.

Moreover, the models feature a modern aesthetic with sleek designs that seamlessly blend into both residential and commercial environments. The intuitive user interface, combined with remote control capabilities, makes adjusting temperature settings easier for users, giving them full control over their indoor climate.

Another significant characteristic of these models is the use of advanced filtration systems. Many units incorporate a multi-stage filtration process that captures dust, allergens, and pollutants, ensuring the air quality in the home remains high. These filters are easy to clean and replace, making maintenance straightforward and user-friendly.

The LG LAN121CNM, LAU121CNM, and others in the lineup also include Wi-Fi connectivity. This smart technology allows users to monitor and control their air conditioning units through mobile applications, providing convenience and flexibility. Users can adjust settings, schedule operations, and receive alerts about filter maintenance directly from their smartphones.

For those looking for flexibility, these models offer various installation options. They can be installed as wall-mounted, floor-mounted, or ceiling-mounted systems, catering to different space constraints and design preferences.

In conclusion, the LG LAN121CNM, LAU121CNM, LA121HPMI, LA121HPMO, LAN121HNM, LAU121HNM, LA121CPMI, and LA121CPMO air conditioning models are exemplary products that demonstrate LG’s commitment to quality, efficiency, and user-centric design. With cutting-edge technology and a focus on sustainability, these units cater to the needs of modern consumers while ensuring comfort all year round.