Troubleshooting Guide

ElectronicParts (18k model)

Product does not operate at all.

(* Refer to Electronic Control Device drawing and Schematic diagram.)

Turn off Main Power

(After 20 seconds)

Turn on Main Power

Does "beeping" sound is made from the Indoor Unit?

NO

Check the voltage of power(About AC 208V/AC 230V, 60Hz)

Main power's voltage

Voltage applied to the unit

Connecting method of Indoor/Outdoor connecting cable

Check PWB Ass'y(Outdoor unit)

-Fuse

-Pattern damage

-Varistor(ZNR01J)

Check the connection housing for contacting

Connector related to CN-POWER

Connector related to CN-FAN

Connector contacting of Outdoor Fan/Compressor

Display PWB Ass'y Check

Connector related to CN-DC/DC

YES

Primarily, the operating condition of Micom is OK.

Check each load(Indoor/Outdoor Fan Motor, Compressor, Stepping Motor) and contacting condition of related connector(including connecting cable of Indoor/Outdoor Unit)

PCB Board Operation Check

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Items

 

 

 

 

Content

 

 

 

Remedy

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Power Transformer

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Outdoor unit)

 

 

 

 

 

 

 

 

 

 

 

 

- Input Voltage

 

 

- About AC 208V/AC 230V±10%

 

 

 

• Replace SMPS

 

 

 

- Output Voltage

 

 

- Check the power voltage

 

 

 

Module

 

 

 

• IC01D(7812) Output

 

 

- About DC15V±3

 

 

 

 

 

 

 

 

 

• DC +12V

 

 

 

• Replace IC01D

 

 

 

(Indoor/Outdoor unit)

 

 

 

 

 

 

 

 

 

• IC02D(7805) Output (Indoor unit)

 

 

• DC +5V

 

 

 

• Replace

 

 

 

IC04D(7805) Output (Outdoor unit)

 

 

 

 

 

IC02D(Indoor unit)

 

 

 

• IC01A(KIA7036, Reset IC)

 

 

• Voltage of Outdoor unit Micom No. 18,

 

 

 

IC04D(Outdoor unit)

 

 

 

 

 

 

 

 

 

 

 

 

OSC01B(4MHz)

 

 

Voltage of Indoor unit Micom No. 43 and

 

 

 

 

 

 

 

(Indoor/Outdoor unit)

 

 

soldering condition

 

 

 

• Replace faulty parts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Service Manual 53

Image 53
Contents Room Air Conditioner Table of Contents Installation Safety PrecautionsDo not modify or extend the power cord Be sure not to do Be sure to follow the instructionOperation Moisture may condense and wet or damage furnishings Low refrigerant levels may cause product failure Keep level even when installing the productOr more often if necessary Solvents, etcOn the product. outdoor unit Replace all the batteries in the remote DisuseDo not drink the water drained from the unit Indoor Unit DimensionsSymbols Used in this Manual Model Btu Series Dimension Mminch 109042.9 30011.8 1787.0 9k, 12k Outdoor UnitDIM 18k, 24kIntroduction FeaturesInstallation Tools InstallationInstallation Parts Bushing-Sleeve Installation MapThis Product Contains R-410A Refrigerant Confirm The RefrigerantSelect The Best Location Rooftop InstallationsIndoor unit Outdoor unitEvap Moz/ft Piping Length And ElevationDrill a Hole In The Wall How To Mount Installation PlateCut the pipes and the cable Flaring WorkBurrs removal Putting nut onIndoor Connecting The PipingIndoor unit installation Tighten the flare nut with a wrench Wrap the insulation material around the connecting portionIndoor unit installation Insert the connecting cable into the indoor unitConnection Indoor Incorrect case Correct caseConnection Of Piping -Outdoor Connection Of The Drain HoseConnection Of The Cable Wiring DiagramRoom Air Conditioner Drain piping Checking The DrainageSeal small openings around pipings with a gum type sealer Forming The PipingAir purging With Vacuum Pump Air PurgingPreparation Leak testFinishing the job EvacuationCharging Test Running Prepare remote controlSettlement of outdoor unit Evaluation of the performanceHealthy Dehumidification Mode Cooling Mode OperationOperation Function of ControlsDefrost Control Heating Mode OperationChaos Natural Wind Mode Sleep Timer OperationJet Cool Mode Operation C/O Model Jet Cool Mode Operation H/P ModelTest operation Forced operationAuto restart Protection of the evaporator pipe from frostingHeating Model Display FunctionSelf-diagnosis Function Operation Mode Remote Control OperationsTo remove the Grille from the Chassis DisassemblyTo remove the Control Box To remove the Motor Cover Refrigeration Cycle Diagram Troubleshooting GuideCooling Only Models Cooling & Heating ModelsWay Valve Liquid Side Way, 3-way ValvePumping Down ProcedureBalance Refrigerant of the 3-way Valve Vacuum pump After Evacuation Gas ChargingMethod of using equation Method of using graphAccording to Indoor & Outdoor Temperature Additional gas chargingTrouble analysis Cycle PartsProduct does not operate at all Electronic Parts 9k modelElectronic Parts 18k model Product is not operate with the remote controller Compressor/Outdoor Fan are unable to drive.9k Model Compressor/Outdoor Fan are unable to drive.18k Model Nector When indoor Fan does not operateWhen Vertical Louver does not operate When a comunication error occurs Indoor Unit Phenomena in case of connecting errorOutdoor Unit Electric Control Device Schematic DiagramOutdoor 9k, 12k Outdoor 18k, 24k Wiring Diagram Models 9kC/O Models 12kH/P, 12kC/O, H/P Models 18kC/O Models 18kH/P, 24kC/O, H/P Components Location Outdoor9k, 12k Outdoor18k, 24k 6871A20680 6871A20681Cooling Only Product SpecificationsLS090HE LS120HE LS180HE LS240HE Cooling & HeatingExploded View Outdoor Unit 9k, 12k Btu/h Seriess 435512 W0CZZ-2 Outdoor Unit 18kH/P, 24k SeriessParts List Indoor Replacement Parts ListLSN180CE LSU120HE Parts List OutdoorReplacement Parts List LSU240HE No A20462V