LG Electronics LCN240CP Drain Pipe Work, Drain Piping of Ceiling Cassette, Drain test

Page 27

Installation

In case of the Outdoor Unit being installed above position of the Indoor Unit.

2.Tape the Pipings and Connecting cable from bot- tom to top.

3.Form the pipings gathered by taping along the exterior wall, and make the trap prevent water from entering into the room.

4.Fix the pipings onto the wall by saddle or equiva- lent.

Seal a small opening around the pipings with gum type sealer.

Trap

7. Drain Pipe Work

Drain Piping of Ceiling Cassette

Drain piping must have down-slope (1/50 to 1/100): be sure not to provide up-and-down slope to prevent reversal flow.

During drain piping connection, be careful not to exert extra force on the drain port on the indoor unit.

The outside diameter of the drain connection on the indoor unit is 32mm(1.26inch).

Piping material: Polyvinyl chloride pipe VP-25 and pipe fittings

Be sure to install heat insulation on the drain piping.

Heat insulation material: Polyethylene foam with thickness more than 8 mm(0.31inch).

Install the drain raising pipes at a right angle to the indoor unit and no more than 300mm(11.81inch) from the unit.

Pipe clamp

Upward

routing

 

 

not allowed

Indoor unit

 

Maintenance

 

drain port

 

300mm

 

1 -1.5m(3.32-4.92ft)

(11.81inch) or less

 

 

700mm

(27.6inch)or less

 

 

Drain raising pipe

 

Clamp metal(attached)

Drain hose(attached)

 

Drain test

The air conditioner uses a drain pump to drain water. Use the following procedure to test the drain pump operation:

Feed water

Flexible drain hose

 

(accessory)

 

Main

 

drain pipe

 

Drain

 

Drain Pump

port

Glue the joint

 

 

 

Drain hose connection

 

Use the clip (accessory)

Drain pan

CAUTION

The supplied flexible drain hose should not be curved, neither screwed. The curved or screwed hose may cause a leakage of water.

Connect the main drain pipe to the exterior and leave it provisionally until the test comes to an end.

Feed water to the flexible drain hose and check the piping for leakage.

Be sure to check the drain pump for normal operat- ing and noise when electrical wiring is complete.

When the test is complete, connect the flexible drain hose to the drain port on the indoor unit.

Flexible drain hose

1/50~1/100

MAX 700mm

(27.6inch)

Service Manual 27

Image 27
Contents Ceiling Cassette Air Conditioner Table of Contents Local model name Models ListIndoor units Outdoor unitsInstallation Safety PrecautionsDo not let electric parts of the product get wet Do not install, remove, or reDefective installation stand OperationalBe cautious that water could not enter the product Do not step on or put anyting on the product. outdoor units Keep level even when installing the productThinner Use two or more people to lift and transport the productFeatures & Benefits Two Thermistor Control Swirl SwingSpace Control Auto Restart OperationWater Drain Pump Time Delay Safety FunctionZero Standby Power High Ceiling OperationCeiling Cassette List of FunctionsFunction of Remote Control Wireless LCD Remote ControlNd F Button Wired LCD Remote Control Indoor unit type Ceilling Cassette 4way Model SpecificationsAT-C243HLFO AT-C343HLFO Model No. LCN240CP/LC240CPI/LCN340CP/LC340CPI Dimensional DrawingsModel No. LCU240CP/LC240CPO Model No. LCU340CP/LC340CPO Indoor Unit Wiring DiagramsLCU340CP/LC340CPO Outdoor UnitCooling Only Models Refrigerant Cycle DiagramsOutdoor Unit InstallationSelect the best location Indoor UnitSettlement of outdoor unit Indoor Unit Installation 24k/34k Btu/h 1Ø Cooling & Heating type Wiring ConnectionAir conditioner unit Piping side Installation of Decoration PanelHeat Insulation Heat Insulation and pipingsDrain Pipe Work Drain Piping of Ceiling CassetteDrain test Test running Precautions in Test RUNEvaluation of the performance Connection of power supplyTwo Thermistor System Optional OperationRemote Controller Adjusting air volume to the height of ceilingProcedure Wiring designTroubleshooting Guide Cycle Troubleshooting GuideTrouble analysis Trouble Electronic Parts Troubleshooting GuideProduct doesnt operate with the remote controller When cooling does not operate When indoor Fan does not operate Trouble 5 When Vertical Louver does not operate Self-diagnosis Function Indoor ErrorOutdoor Error Error IndicatorCheck Point Troubleshooting CH01, CH02, CH06Troubleshooting CH03 Troubleshooting CH04 Troubleshooting CH05, CH53 Troubleshooting CH24, CH25 Constant Troubleshooting CH32, CH33Troubleshooting CH41, CH44, CH45, CH46, CH47, CH65 Troubleshooting CH51, CH60 Troubleshooting CH61, CH62 Way Valve Liguid Side Way Valve Gas Side Way ValveSet the liquid side valve to the closed position ProcedurePumping down Air purging of the charge hoseMount the valve caps and the service port caps EvacuationAll amount of refrigerant leaked Connect the gauge to the charging cylinder Mount the valve stem nuts and the service port nutGas Charging After EvacuationMain P.C.B ASM Electronic Control DeviceModel No. LCN240CP/LCN340CP Exploded View and Replacement Parts ListDescription Remarks Parts ListModel No. LCU240CP Description Remarks LCU240CP / LC240CPO Model No Description Remarks LCU340CP / LC340CPO Model No. PT-CDC1 Description Remarks PT-CDC1 No A20911A