LG Electronics LCN240CP service manual Troubleshooting CH01, CH02, CH06, Check Point

Page 39

Troubleshooting Guide

TroubleshootingCH01,CH02,CH06

Display

Title

 

 

 

Cause of error

 

 

 

 

Check point & Normal condition

code

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor air sensor

 

• Open / Short

Normal resistor : 10K/ at 25°C(77°F) (Unplugged)

01

 

• Soldered poorly

 

Normal voltage : 2.5Vdc / at 25°C(77°F)

(plugged)

 

 

 

 

 

 

 

 

• Internal circuit error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Open / Short

Normal resistor :

5K/ at 25°C(77°F) (Unplugged)

02

Indoor inlet pipe sensor

 

• Soldered poorly

 

Normal voltage : 2.5Vdc / at 25°C(77°F)

(plugged)

 

 

 

 

 

 

 

 

• Internal circuit error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Open / Short

Normal resistor :

5K/ at 25°C(77°F) (Unplugged)

06

Indoor outlet pipe sensor

 

• Soldered poorly

 

Normal voltage : 2.5Vdc / at 25°C(77°F) (plugged)

 

 

 

 

 

 

 

 

• Internal circuit error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10k

Check the resistance

2.5Vdc

V

Check the voltage

Check Point

1.Unplug the sensor on Indoor unit PCB.

2.Estimate the resistance of each sensor.

3.If the resistance of the sensor is 10K/ 5Kat 25°C(77°F), then sensor is normal.

4.If the resistance of the sensor is 0 Kor , then sensor is abnormal. Change the sensor.

5.Plug the sensor on Indoor unit PCB and Power ON.

6.Estimate the voltage of each sensor.

7.If the voltage of the sensor is 2.5Vdc at 25°C(77°F), then sensor is normal.

8.If the resistance of the sensor is 0 or 5Vdc, then sensor is abnormal. Repair or Change the PCB.

Service Manual 39

Image 39
Contents Ceiling Cassette Air Conditioner Table of Contents Local model name Models ListIndoor units Outdoor unitsInstallation Safety PrecautionsDo not let electric parts of the product get wet Do not install, remove, or reDefective installation stand OperationalBe cautious that water could not enter the product Do not step on or put anyting on the product. outdoor units Keep level even when installing the productThinner Use two or more people to lift and transport the productFeatures & Benefits Two Thermistor Control Swirl SwingSpace Control Auto Restart OperationWater Drain Pump Time Delay Safety FunctionZero Standby Power High Ceiling OperationCeiling Cassette List of FunctionsFunction of Remote Control Wireless LCD Remote ControlNd F Button Wired LCD Remote Control Indoor unit type Ceilling Cassette 4way Model SpecificationsAT-C243HLFO AT-C343HLFO Model No. LCN240CP/LC240CPI/LCN340CP/LC340CPI Dimensional DrawingsModel No. LCU240CP/LC240CPO Model No. LCU340CP/LC340CPO Indoor Unit Wiring DiagramsLCU340CP/LC340CPO Outdoor UnitCooling Only Models Refrigerant Cycle DiagramsOutdoor Unit InstallationSelect the best location Indoor UnitSettlement of outdoor unit Indoor Unit Installation24k/34k Btu/h 1Ø Cooling & Heating type Wiring ConnectionAir conditioner unit Piping side Installation of Decoration PanelHeat Insulation Heat Insulation and pipingsDrain Pipe Work Drain Piping of Ceiling CassetteDrain test Test running Precautions in Test RUNEvaluation of the performance Connection of power supplyTwo Thermistor System Optional OperationRemote Controller Adjusting air volume to the height of ceilingProcedure Wiring designTroubleshooting Guide Cycle Troubleshooting GuideTrouble analysis Trouble Electronic Parts Troubleshooting GuideProduct doesnt operate with the remote controller When cooling does not operate When indoor Fan does not operate Trouble 5 When Vertical Louver does not operate Self-diagnosis Function Indoor ErrorOutdoor Error Error IndicatorCheck Point Troubleshooting CH01, CH02, CH06Troubleshooting CH03 Troubleshooting CH04 Troubleshooting CH05, CH53 Troubleshooting CH24, CH25 Constant Troubleshooting CH32, CH33Troubleshooting CH41, CH44, CH45, CH46, CH47, CH65 Troubleshooting CH51, CH60 Troubleshooting CH61, CH62 Way Valve Liguid Side Way Valve Gas Side Way ValveSet the liquid side valve to the closed position ProcedurePumping down Air purging of the charge hoseMount the valve caps and the service port caps EvacuationAll amount of refrigerant leaked Connect the gauge to the charging cylinder Mount the valve stem nuts and the service port nutGas Charging After EvacuationMain P.C.B ASM Electronic Control DeviceModel No. LCN240CP/LCN340CP Exploded View and Replacement Parts ListDescription Remarks Parts ListModel No. LCU240CP Description Remarks LCU240CP / LC240CPO Model No Description Remarks LCU340CP / LC340CPO Model No. PT-CDC1 Description Remarks PT-CDC1 No A20911A