LG Electronics LCN240CP service manual Pumping down, Procedure, Air purging of the charge hose

Page 49

(3-way) Valve

(1) Pumping down

Indoor unit

Liquid side

 

Open

Outdoor unit

3-Way valve

Gas side

Closed

3-Way valve

Lo

CLOSECLOSE

Purge the air

Procedure

For pumping down,firstly short the Low Pressure s/w at the outside and then operate below proce- dure.

1.Confirm that both the gas side and liquid side valves are set to the open position.

-Remove the valve stem caps and confirm that the valve stems are in the raised position.

-Be sure to use a hexagonal wrench to operate the valve stems.

2.Operate the unit for 10 to 15 minutes.

3.Stop operation and wait for 3 minutes, then con- nect the manifold gauge to the service port of the gas side valve.

-Connect the hose of the gauge with the push pin to the service port.

4.Air purging of the charge hose.

-Open the Low-handle valve on the gauge slightly to air purge from the hose.

5.Set the liquid side valve to the closed position.

6.Operate the air conditioner at the cooling cycle and stop it when the gauge indicates 1kg/cm2g.

7.Immediately set the gas side valve to the closed position.

-Do this quickly so that the gauge ends up indi- cating 1kg/g.

8.Disconnect the charge set, and mount the liquid side and gas side valve caps and the service port nut.

-Use torque wrench to tighten the service port nut to a torque of 1.8kg.m.(4.2kg.m/5.5kg.m)

-Be sure to check for gas leakage.

Be sure to short pressure S/W. otherwise Low pressure S/W detect low pressure skete and stops the compressor.

Service Manual 49

Image 49
Contents Ceiling Cassette Air Conditioner Table of Contents Indoor units Models ListOutdoor units Local model nameInstallation Safety PrecautionsDefective installation stand Do not install, remove, or reOperational Do not let electric parts of the product get wetBe cautious that water could not enter the product Thinner Keep level even when installing the productUse two or more people to lift and transport the product Do not step on or put anyting on the product. outdoor unitsFeatures & Benefits Space Control Swirl SwingAuto Restart Operation Two Thermistor ControlZero Standby Power Time Delay Safety FunctionHigh Ceiling Operation Water Drain PumpCeiling Cassette List of FunctionsWireless LCD Remote Control Function of Remote ControlNd F Button Wired LCD Remote Control Indoor unit type Ceilling Cassette 4way Model SpecificationsAT-C243HLFO AT-C343HLFO Model No. LCN240CP/LC240CPI/LCN340CP/LC340CPI Dimensional DrawingsModel No. LCU240CP/LC240CPO Model No. LCU340CP/LC340CPO Indoor Unit Wiring DiagramsLCU340CP/LC340CPO Outdoor UnitCooling Only Models Refrigerant Cycle DiagramsSelect the best location InstallationIndoor Unit Outdoor UnitSettlement of outdoor unit Indoor Unit Installation24k/34k Btu/h 1Ø Cooling & Heating type Wiring ConnectionAir conditioner unit Piping side Installation of Decoration PanelHeat Insulation Heat Insulation and pipingsDrain Piping of Ceiling Cassette Drain Pipe WorkDrain test Test running Precautions in Test RUNEvaluation of the performance Connection of power supplyTwo Thermistor System Optional OperationProcedure Adjusting air volume to the height of ceilingWiring design Remote ControllerCycle Troubleshooting Guide Troubleshooting GuideTrouble analysis Trouble Electronic Parts Troubleshooting GuideProduct doesnt operate with the remote controller When cooling does not operate When indoor Fan does not operate Trouble 5 When Vertical Louver does not operate Outdoor Error Indoor ErrorError Indicator Self-diagnosis FunctionCheck Point Troubleshooting CH01, CH02, CH06Troubleshooting CH03 Troubleshooting CH04 Troubleshooting CH05, CH53 Troubleshooting CH24, CH25 Constant Troubleshooting CH32, CH33Troubleshooting CH41, CH44, CH45, CH46, CH47, CH65 Troubleshooting CH51, CH60 Troubleshooting CH61, CH62 Way Valve Liguid Side Way Valve Gas Side Way ValvePumping down ProcedureAir purging of the charge hose Set the liquid side valve to the closed positionEvacuation Mount the valve caps and the service port capsAll amount of refrigerant leaked Gas Charging Mount the valve stem nuts and the service port nutAfter Evacuation Connect the gauge to the charging cylinderMain P.C.B ASM Electronic Control DeviceModel No. LCN240CP/LCN340CP Exploded View and Replacement Parts ListDescription Remarks Parts ListModel No. LCU240CP Description Remarks LCU240CP / LC240CPO Model No Description Remarks LCU340CP / LC340CPO Model No. PT-CDC1 Description Remarks PT-CDC1 No A20911A