Sea-Fire FM200 manual Area, Diameter Model, Auto, Lbs, Part#

Page 2

WARNING

CONCENTRATED AGENT AND BY-PRODUCT OF APPLICATION TO FIRE ARE TOXIC. AVOID BREATHING OF FUMES OR PROLONGED EXPOSURE. ACCIDENTAL DIS- CHARGE MAY OCCUR DURING HANDLING OR INSTALLATION OF THIS DEVICE, READ AND COMPLY WITH INSTRUCTIONS, WARNINGS, AND LIMITATIONS CONTAINED IN THIS MANUAL. DO NOT LIFT, CARRY, OR HANDLE BY VALVE. DO NOT DROP. KEEP AWAY FROM HEAT. KEEP AWAY FROM CHILDREN.

APPLICATION

FM-200®(CF3CHFCF3), the extinguishing agent, used in all Sea-Fire “FT’’ series fire extin- guishers, is a suitable EPA accepted alternate replacement for Halon. FM-200®is electrically nonconductive and residue free extinguishing agent that requires no cleanup.

These features and the versatility of design make the “FT’’ series fire extinguisher ideal for a broad range of applications. The systems are ideal for small volumes, 150 cubic feet or less, that are difficult to access. These applications would include marine, recreational vehicles, commercial and industrial use where flammable liquids are likely source of fire.

Application Examples:

Engine Compartments (maximum 150 cubic feet)

Bow Thrusters

Small Generator Set Enclosures

Consoles

Electrical Enclosures

Flammable Liquid Storage Areas

Pump Enclosures

Alternative Fuel Storage Areas

Sea-Fire “FT” extinguishers are designed to induce a minimum atmospheric concentration of 10.0% within the protected compartment.* The specification table in this manual lists the minimum and maximum approved compartment volume (size) allowable for each model. Volume can be determined by multiplying the compartment’s length x width x height which equals the volume in cubic feet or meters (LxWxH=V).

Exception: If the boat manufacturer has placed a permanently affixed label in the compart- ment specifying the gross volume less the volume of permanently installed tankage, then this volume may be used to determine the proper size extinguisher. Check specification table for proper application before making installation.

*Reference: NFPA-2001 National Fire Protection Assoc. Boston, MA and UL 2166 Underwriters laboratories

SEA-FIRE “FT” SERIES AUTOMATIC FIRE SUPPRESSION SYSTEMS FT — STINGER SPECIFICATION TABLE

 

AREA OF

FM-200 @

 

DIAMETER X

 

 

 

 

MODEL

PROTECTION

240 PSI

 

HEIGHT

TUBE PART # / LENGTH

 

CU.FT.

CU.M.

 

 

 

 

 

 

 

 

 

AUTO

AREA

AREA

LBS.

KG

 

INCH

MM

PART#

 

FT.

MM

FT-25

25

0.7

1.25

0.56

 

3.0 X 11.2

76 X 285

130-121

 

10

3000

FT-50

50

1.4

2.50

1.13

 

3.1 X 13.5

78 X 342

130-121

 

10

3000

FT-75

75

2.1

3.75

1.70

 

3.1 X 16.5

78 X 419

130-121

 

10

3000

FT-100

100

2.8

5.00

2.26

 

3.5 X 17.5

89 X 444

130-122

 

15

4500

FT-125

125

3.5

6.25

2.83

 

4.1 X 17.0

104 X 432

130-122

 

15

4500

FT-150

150

4.2

7.50

3.40

 

5.2 X 19.0

132 X 482

130-122

 

15

4500

 

 

 

 

 

 

 

 

 

 

 

 

CU. FT. = Cubic Feet

 

 

FT. = Feet

 

 

KG = Kilograms

CU.M. = Cubic Meters

 

 

LBS. = Pounds

 

MM = Millimeters

CAUTION: NEVER INSTALL A UNIT WITH A VOLUME RATING LESS THAN THE GROSS VOLUME OF THE COMPARTMENT TO BE PROTECTED. DO NOT DEDUCT FOR ENGINES, REMOVABLE TANKS OR OTHER EQUIPMENT.

2

Image 2
Contents Model FT Fire Extinguishers Auto AreaDiameter Model LBSDiesel Engines Pressure SwitchSystem Operations Gasoline EnginesInstallation Other ApplicationsPage Indicator Light Installation System Maintenance Sdda Three 3 Year FT Series Limited WarrantyOptional Equipment ESRS-2Model FT Parts List OUT of Warranty REPLACEMENTS/RECHARGESEquipment List for Installation ConditionsPage Material Safety Data Sheet FG/FD/FT/MD/R/C-MODELPhysical & Chemical Properties Handling and StorageExposure Controls/Personal Protection Stability and ReactivityDisclaimer of Expressed and Implied Warranties Regulatory InformationOther Information SEA-FIRE Marine