State Industries 185244-004, 315466-000 Venting, Vent Terminal Installation, Masonry Side Walls

Page 17

For 4" Venting, the maximum equivalent feet of pipe allowed is 160 feet (48.8 m). This does not include the Vent Termination (supplied locally) for the water heater. For the 4" venting, one 90° elbow is approximately equal to 8 feet (2.4 m). One 45° elbow is approximately equal to 4 feet (1.2 m). It is recommended that at least 2 feet (0.6 m) of spacing be used in between all 45° elbows and all 90°elbows.

55,000 and 62,500 BTU Units:

NOTE: The 55,000 and 62,500 BTU Units are not approved for 2" venting.

For 3" Venting, the maximum equivalent feet of pipe allowed is 80 feet (24.4 m). This does not include the supplied Vent Termination for the water heater. For the 3" venting, one 90° elbow is approximately equal to 5 feet (1.5 m). One 45° elbow is approximately equal to 2.5 feet (0.8 m). It is recommended that at least 2 feet (0.6 m) of spacing be used in between all 45° elbows and all 90°elbows.

For 4" Venting, the maximum equivalent feet of pipe allowed is 120 feet (36.6 m). This does not include the Vent Termination (supplied locally) for the water heater. For the 4" venting, one 90° elbow is approximately equal to 8 feet (2.4 m). One 45° elbow is approximately equal to 4 feet (1.2 m). It is recommended that at least 2 feet (0.6 m) of spacing be used in between all 45° elbows and all 90°elbows.

VENTING

The vent system must terminate so that proper clearances are maintained as cited in local codes or the current edition of the National Fuel Gas Code, ANSI Z223.1/NFPA 54, 7.3.4e and 7.8a,b, as follows:

1.The exit terminals of a mechanical vent system shall be not less than 7 feet (2.13 m) above grade when located adjacent to public walkways, see Figure 16.

2.A venting system shall terminate at least 3 feet (0.91 m) above any forced air inlet located within 10 feet (3.1 m), see Figure 16.

3.The venting system shall terminate at least 4 feet (1.2 m) below, 4 feet (1.2 m) horizontally from or, 1 foot (0.31 m) above any door, window or gravity air inlet into any building.

The manufacturer also recommends that the vent termination should not be installed closer than 18" (45.7 cm) from an inside corner of an L shaped structure and not be less than 1 foot (0.31 m) above grade.

The vent shall terminate a minimum of 12'' (30.5 cm) above expected snowfall level to prevent blockage of vent termination, see Figure 16.

4.In cold climates, it is recommended that vent termination not be mounted directly above or within 3 feet (0.91 m) horizontally from an oil tank vent or gas meter to avoid potential freeze-up from condensation, see Figure 16..

Plan the vent system layout so that proper clearances are maintained from plumbing and wiring.

Vent pipes serving power vented appliances are classified by building codes as “vent connectors”. Required clearances from combustible materials must be provided in accordance with information in this manual under LOCATION OF HEATER and VENT TERMINAL INSTALLATIONS, and with the National Fuel Gas Code and local codes.

VENT TERMINAL INSTALLATION

1.After the point of termination has been determined, use the cover plate as a template to mark the hole for the vent pipe to insert through the wall. BEWARE OF CONCEALED WIRING AND PIPING INSIDE OF WALL.

2.If the Vent Terminal is being installed on the outside of a finished wall, it may be easier to mark both the inside and outside wall. Align the holes by drilling a hole through the center of the template from the inside through to the outside. The template can now be positioned on the outside wall using the drilled hole as a centering point for the template.

3.A) MASONRY SIDE WALLS

Chisel an opening approximately one half inch larger than the marked circle.

B) WOODEN SIDE WALLS

Drill a pilot hole approximately one quarter inch outside of the marked circle. This pilot hole is used as a starting point for a saws-all or sabre saw blade. Cut around the marked circle staying approximately one quarter inch outside of the line. (This will allow the vent pipe to easily slide through the opening. The resulting gap will be covered up by the vent terminal cover plates.) Repeat this step on inside wall if necessary.

17

Image 17
Contents Printed AN Odorant is Added to the GAS Used By this Water HeaterImportant Definitions Safe INSTALLATION, USE and ServiceGeneral Safety Introduction Table of ContentsKeep Clear of ALL Obstructions Drain Pan Typical InstallationNatural HOT Surface Igniter & Main Burner Propane HOT Surface Igniter & Main BurnerHotter Water can Scald Mixing Valve UsageFacts to Consider about the Location Locating the NEW Water HeaterInsulation Blankets ALL AIR from Outdoors See Figures 7, 8 ALL AIR from Inside Buildings SeeWater Piping Installing the NEW Water HeaterClosed Water Systems Thermal ExpansionValve and Pipe Insulation if supplied TEMPERATURE-PRESSURE Relief ValveGAS Piping GAS Piping with Flexible ConnectorSequence of Installation Blower Assembly InstallationSediment Traps Filling the Water HeaterVenting and Installation Vent Connections to Blower AssemblyMaximum and Minimum Vent Lengths CondensateVenting Vent Terminal InstallationMasonry Side Walls Wooden Side WallsVertical Vent Through Roof Vertical Vent Termination RestrictionsRecommended BRUSH* Size for Primer Cement Applications Vent Pipe PreparationStep E Step BStep F Step GPage GAS Control Valve Front View Temperature RegulationStart UP Conditions For Your InformationBurner Cleaning Periodic MaintenanceVenting System Inspection Burner Operation and InspectionDrain Valve Washer Replacement TEMPERATURE-PRESSURE Relief Valve OperationAnode ROD Inspection DrainingLeakage Checkpoints ServiceNot Shown Optional Repair Parts ListBurner Assembly Drain PAN Outer Door Alternate Trouble Shooting Troubleshooting GuidelinesPage Troubleshooting Guidelines Important Information Tennessee Waltz Parkway Ashland City, TN

GS6 50 YBVIT, GS6 40 YRVIT, GS6 50 YBVIT 2, GS6 40 YBVIT 2, 315466-000 specifications

State Industries manufactures a variety of high-efficiency water heaters, including the GS6 models, which are designed to meet diverse residential and commercial needs. Among these, the GS6 50 YRVIT, GS6 40 YBDS, and GS6 40 YBVIT 2 stand out for their performance, advanced technologies, and distinctive features.

The GS6 50 YRVIT is a powerful 50-gallon gas water heater that boasts a 40,000 BTU input. This model is designed with a high-efficiency rating, enabling it to deliver a strong hot water supply while minimizing energy costs. Its glass-lined tank provides superior protection against rust and corrosion, ensuring durability and extending the lifespan of the unit. This model also features an innovative flue design that maximizes combustion efficiency, making it an environmentally friendly choice that adheres to stringent energy regulations.

The GS6 40 YBDS, on the other hand, is a more compact 40-gallon gas water heater, also with a 40,000 BTU input. This unit is particularly popular for smaller households or commercial spaces where space is limited. It also incorporates advanced technology to optimize performance while remaining user-friendly. The GS6 40 YBDS is equipped with a direct vent system, allowing for flexible installation options, ensuring that high-efficiency heating is available even in confined areas.

Lastly, the GS6 40 YBVIT 2 model takes energy efficiency a step further with its cutting-edge insulation system and advanced temperature control features. This 40-gallon water heater is specifically engineered to minimize heat loss, which translates into reduced energy expenses for the user. The stainless steel burner and exceptional venting design contribute to efficient hot water production, making the GS6 40 YBVIT 2 a reliable choice for families seeking consistent performance.

Across all GS6 models, State Industries emphasizes safety and reliability. Each unit includes several built-in safety features, such as a temperature and pressure relief valve and a flame arrestor to prevent flammable vapors from entering the burner. Moreover, the easy-to-use digital display allows users to monitor settings effortlessly.

In summary, the State Industries GS6 series, including the GS6 50 YRVIT, GS6 40 YBDS, and GS6 40 YBVIT 2, combines efficiency, cost-effectiveness, and advanced technologies, catering to the hot water needs of any home or business. With their robust construction and innovative features, these water heaters provide dependable service and peace of mind to users.