State Industries 185244-004, 315466-000, GS6 50 YRVIT, GS6 50 YBVIT 2 Insulation Blankets

Page 9

and 12" (30.5 cm) from the top. (Standard clearance.) If clearances stated on the heater differ from standard clearances, install water heater according to clearances stated on the heater.

Adequate clearance for servicing this appliance should be considered before installation, such as changing the anodes, etc.

A minimum clearance of 5" (12.7 cm) must be allowed for access to replaceable parts such as the thermostats, drain valve and relief valve.

When installing the heater, consideration must be given to proper location. Location selected should be as close to the wall as practicable and as centralized with the water piping system as possible.

FIGURE 4.

A gas water heater cannot operate properly without the correct amount of air for combustion. Do not install in a confined area such as a closet, unless you provide air as shown in the “Locating The New Water Heater” section. Never obstruct the flow of ventilation air. If you have any doubts or questions at all, call your gas supplier. Failure to provide the proper amount of combustion air can result in a fire or explosion and cause death, serious bodily injury, or property damage.

FIGURE 5.

If this water heater will be used in beauty shops, barber shops, cleaning establishments, or self-service laundries with dry cleaning equipment, it is imperative that the water heater or water heaters be installed so that combustion and ventilation air be taken from outside these areas.

Propellants of aerosol sprays and volatile compounds, (cleaners,

9

chlorine based chemicals, refrigerants, etc.) in addition to being highly flammable in many cases, will also react to form corrosive hydrochloric acid when exposed to the combustion products of the water heater. The results can be hazardous, and also cause product failure.

INSULATION BLANKETS

Insulation blankets are available to the general public for external use on gas water heaters but are not necessary with these products. The purpose of an insulation blanket is to reduce the standby heat loss encountered with storage tank heaters. Your water heater meets or exceeds the National Appliance Energy Conversation Act standards with respect to insulation and standby loss requirements, making an insulation blanket unnecessary.

Should you choose to apply an insulation blanket to this heater, you should follow these instructions (For identification of components mentioned below, see Figure 1). Failure to follow these instructions can restrict the air flow required for proper combustion, potentially resulting in fire, asphyxiation, serious personal injury or death.

Do not apply insulation to the top of the water heater, as this will interfere with safe operation of the draft hood.

Do not cover the outer door, thermostat or temperature & pressure relief valve.

Do not allow insulation to come within 2" (5.1 cm) of the floor to prevent blockage of combustion air flow to the burner.

Do not cover the instruction manual. Keep it on the side of the water heater or nearby for future reference.

Do obtain new warning and instruction labels from the manufacturer for placement on the blanket directly over the existing labels.

Do inspect the insulation blanket frequently to make certain it does not sag, thereby obstructing combustion air flow.

COMBUSTION AIR AND VENTILATION FOR APPLIANCES LOCATED IN UNCONFINED SPACES

UNCONFINED SPACE is space whose volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8 cubic meters per kW) of the aggregate input rating of all appliances installed in that space. Rooms communicating directly with the space in which the appliances are installed, through openings not furnished with doors, are considered a part of the unconfined space.

In unconfined spaces in buildings, infiltration may be adequate to provide air for combustion, ventilation and dilution of flue gases. However, in buildings of tight construction (for example, weather stripping, heavily insulated, caulked, vapor barrier, etc.), additional air may need to be provided using the methods described in “Combustion Air and Ventilation for Appliances Located in Confined Spaces.”

COMBUSTION AIR AND VENTILATION FOR APPLIANCES LOCATED IN CONFINED SPACES

CONFINED SPACE is a space whose volume is less than 50 cubic feet per 1,000 Btu per hour (4.8 cm per kW) of the aggregate input rating of all appliances installed in that space.

Image 9
Contents Printed AN Odorant is Added to the GAS Used By this Water HeaterImportant Definitions Safe INSTALLATION, USE and ServiceGeneral Safety Introduction Table of ContentsKeep Clear of ALL Obstructions Drain Pan Typical InstallationNatural HOT Surface Igniter & Main Burner Propane HOT Surface Igniter & Main BurnerHotter Water can Scald Mixing Valve UsageFacts to Consider about the Location Locating the NEW Water HeaterInsulation Blankets ALL AIR from Outdoors See Figures 7, 8 ALL AIR from Inside Buildings SeeWater Piping Installing the NEW Water HeaterClosed Water Systems Thermal ExpansionValve and Pipe Insulation if supplied TEMPERATURE-PRESSURE Relief ValveGAS Piping GAS Piping with Flexible ConnectorSequence of Installation Blower Assembly InstallationSediment Traps Filling the Water HeaterVenting and Installation Vent Connections to Blower AssemblyMaximum and Minimum Vent Lengths CondensateVenting Vent Terminal InstallationMasonry Side Walls Wooden Side WallsVertical Vent Through Roof Vertical Vent Termination RestrictionsRecommended BRUSH* Size for Primer Cement Applications Vent Pipe PreparationStep E Step BStep F Step GPage GAS Control Valve Front View Temperature RegulationStart UP Conditions For Your InformationBurner Cleaning Periodic MaintenanceVenting System Inspection Burner Operation and InspectionDrain Valve Washer Replacement TEMPERATURE-PRESSURE Relief Valve OperationAnode ROD Inspection DrainingLeakage Checkpoints ServiceRepair Parts List Burner Assembly Drain PAN Outer Door AlternateNot Shown Optional Trouble Shooting Troubleshooting GuidelinesPage Troubleshooting Guidelines Important Information Tennessee Waltz Parkway Ashland City, TN

GS6 50 YBVIT, GS6 40 YRVIT, GS6 50 YBVIT 2, GS6 40 YBVIT 2, 315466-000 specifications

State Industries manufactures a variety of high-efficiency water heaters, including the GS6 models, which are designed to meet diverse residential and commercial needs. Among these, the GS6 50 YRVIT, GS6 40 YBDS, and GS6 40 YBVIT 2 stand out for their performance, advanced technologies, and distinctive features.

The GS6 50 YRVIT is a powerful 50-gallon gas water heater that boasts a 40,000 BTU input. This model is designed with a high-efficiency rating, enabling it to deliver a strong hot water supply while minimizing energy costs. Its glass-lined tank provides superior protection against rust and corrosion, ensuring durability and extending the lifespan of the unit. This model also features an innovative flue design that maximizes combustion efficiency, making it an environmentally friendly choice that adheres to stringent energy regulations.

The GS6 40 YBDS, on the other hand, is a more compact 40-gallon gas water heater, also with a 40,000 BTU input. This unit is particularly popular for smaller households or commercial spaces where space is limited. It also incorporates advanced technology to optimize performance while remaining user-friendly. The GS6 40 YBDS is equipped with a direct vent system, allowing for flexible installation options, ensuring that high-efficiency heating is available even in confined areas.

Lastly, the GS6 40 YBVIT 2 model takes energy efficiency a step further with its cutting-edge insulation system and advanced temperature control features. This 40-gallon water heater is specifically engineered to minimize heat loss, which translates into reduced energy expenses for the user. The stainless steel burner and exceptional venting design contribute to efficient hot water production, making the GS6 40 YBVIT 2 a reliable choice for families seeking consistent performance.

Across all GS6 models, State Industries emphasizes safety and reliability. Each unit includes several built-in safety features, such as a temperature and pressure relief valve and a flame arrestor to prevent flammable vapors from entering the burner. Moreover, the easy-to-use digital display allows users to monitor settings effortlessly.

In summary, the State Industries GS6 series, including the GS6 50 YRVIT, GS6 40 YBDS, and GS6 40 YBVIT 2, combines efficiency, cost-effectiveness, and advanced technologies, catering to the hot water needs of any home or business. With their robust construction and innovative features, these water heaters provide dependable service and peace of mind to users.