WATER HEATER STATUS MENU
This menu displays non adjustable operational information. Use the Up & Down Buttons to navigate to the bottom of this menu.
Top of Menu
Bottom of Menu
Element # On
Displays the on/off status of each heating element. Yes = On, No = Off.
Tank Full
Displays the status of the optional LWCO (Low Water Cut Off) device. Yes = water level is acceptable, No = water level is low.
Alarm Condition
Displays the status of the user definable Alarm Output function - see Alarm Output Setup Menu. Yes = alarm condition has been met, No = alarm condition has not been met.
Alarm Relay Output
Displays the state of the normally open contacts of the Alarm Output relay. This relay (J3 contacts on the CCB - see wiring diagrams) is used for building EMS (Energy Management System) notification of operational conditions such as Fault conditions.
Status
Displays the current Operating State of the control system. IE: Heating, Standby, Fault.
Elements On #
Displays the number of heating elements the control system has energized.
ECO Contact
Displays the current state of the ECO high temperature limit switch contacts.
Enable / Disable 1 & 2
Displays the current state, open or closed, of the two Enable/Disable circuits (J7 socket on the CCB - see wiring diagrams on page 6) provided for external supervisory controls such as building EMS (Energy Management System). Both of these Enable/Disable circuits must be closed to “enable” heating operation. If either Enable/Disable circuit is open for any reason heating operation will be “disabled.” There is a plug with two jumper wires installed from the factory in the CCB J7 socket to enable heating operation when external controls are not in use.
Service Note: If a supervisory control(s) is used to enable/disable heating operation, install field wiring between the J7 socket on the CCB and a set of “dry contacts” on the external control per all applicable building codes. This is a switching circuit only: DO NOT apply any external voltage or connect any load (IE: relay coil) to either circuit.
ECONOMY MODE SETUP MENU
This menu contains settings used to establish an “Economy Set Point” and “Economy Mode” operating periods. This control system feature can help reduce operating costs during unoccupied, low load, or peak demand periods.
Desktop Screen During Economy Mode
Economy Mode Setup Menu
Setpoint Adjustment
Adjustable user setting (2°F to 50°F - factory default is 20°F) the control system uses to calculate the “Economy Set Point.” The Economy Set Point = normal Operating Set Point minus the programmed Setpoint Adjustment value.
14