State Industries SEH-200 THRU SEH-10000 Water Heater Status Menu, Economy Mode Setup Menu

Page 14

WATER HEATER STATUS MENU

This menu displays non adjustable operational information. Use the Up & Down Buttons to navigate to the bottom of this menu.

Top of Menu

Bottom of Menu

Element # On

Displays the on/off status of each heating element. Yes = On, No = Off.

Tank Full

Displays the status of the optional LWCO (Low Water Cut Off) device. Yes = water level is acceptable, No = water level is low.

Alarm Condition

Displays the status of the user definable Alarm Output function - see Alarm Output Setup Menu. Yes = alarm condition has been met, No = alarm condition has not been met.

Alarm Relay Output

Displays the state of the normally open contacts of the Alarm Output relay. This relay (J3 contacts on the CCB - see wiring diagrams) is used for building EMS (Energy Management System) notification of operational conditions such as Fault conditions.

Status

Displays the current Operating State of the control system. IE: Heating, Standby, Fault.

Elements On #

Displays the number of heating elements the control system has energized.

ECO Contact

Displays the current state of the ECO high temperature limit switch contacts.

Enable / Disable 1 & 2

Displays the current state, open or closed, of the two Enable/Disable circuits (J7 socket on the CCB - see wiring diagrams on page 6) provided for external supervisory controls such as building EMS (Energy Management System). Both of these Enable/Disable circuits must be closed to “enable” heating operation. If either Enable/Disable circuit is open for any reason heating operation will be “disabled.” There is a plug with two jumper wires installed from the factory in the CCB J7 socket to enable heating operation when external controls are not in use.

Service Note: If a supervisory control(s) is used to enable/disable heating operation, install field wiring between the J7 socket on the CCB and a set of “dry contacts” on the external control per all applicable building codes. This is a switching circuit only: DO NOT apply any external voltage or connect any load (IE: relay coil) to either circuit.

ECONOMY MODE SETUP MENU

This menu contains settings used to establish an “Economy Set Point” and “Economy Mode” operating periods. This control system feature can help reduce operating costs during unoccupied, low load, or peak demand periods.

Desktop Screen During Economy Mode

Economy Mode Setup Menu

Setpoint Adjustment

Adjustable user setting (2°F to 50°F - factory default is 20°F) the control system uses to calculate the “Economy Set Point.” The Economy Set Point = normal Operating Set Point minus the programmed Setpoint Adjustment value.

14

Image 14
Contents Commercial Electric Water Heater Safe INSTALLATION, USE and Service Grounding Instructions General Safety InformationPrecautions Hydrogen GAS Flammable Table of Contents IntroductionElectrical Data Wiring Diagrams ECO TempThermostat Controls Temperature RegulationHigh Temperature Limit Controls ECO Mixing Valves Temperature Adjustment Heating Element Operation Control System FeaturesControl System Operation Control System NavigationStatus Icons Description Operating StatesControl System Menus Menus DescriptionTemperatures Menu Temperature Settings ActionEconomy Mode Setup Menu Water Heater Status MenuCurrent Time Heater In Economy ModeDaily Operating Mode Sun Mon Tue Wed Thu Fri Sat Economy Mode Settings Setpoint Adjustment ValueTime Clock Settings Normal Operation Between Daily Operating Mode SettingsEconomy Mode All Day Heater Information Menu Alarm Output Setup MenuDisplay Settings Menu Fault Occurrence Menu Current Fault / Alert MenuFault History Menu Restore Factory Defaults Menu Factory Defaults Restore Factory DefaultsWater Is Too Hot Troubleshooting ChecklistNot Enough or No Hot Water Water Heater Makes Strange Sounds