Desa Tech CSBNT, CSPINT, CSBPT Determining FRESH-AIR Flow for Heater Location, Ventilation AIR

Page 6

AIR FOR COMBUSTION

AND VENTILATION

Continued

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

Use this work sheet to determine if you have a confined or unconfined space.

Space: Includes the room in which you will install heater plus any adjoining rooms with door- less passageways or ventilation grills between the rooms.

1.Determine the volume of the space (length x width x height).

Length x Width x Height = ________cu. ft. (volume of space)

Example: Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is sup- plied with grills or openings, add the volume of these rooms to the total volume of the space.

2.Multiply the space volume by 20 to determine the maximum Btu/Hr the space can support.

(volume of space) x 20 = (maximum Btu/Hr the space can support)

Example: 2560 cu. ft. (volume of space) x 20 = 51,200 (maximum Btu/Hr the space can support)

3.Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

________ Btu/Hr

Gas water heater*

________ Btu/Hr

Gas furnace

________ Btu/Hr

Vented gas heater

________ Btu/Hr

Gas fireplace logs

________ Btu/Hr

Other gas appliances*

+ _______ Btu/Hr

Total

= _______ Btu/Hr

*Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

Example:

Gas water heater

 

40,000

Btu/Hr

Vent-free heater

+

30,000

Btu/Hr

Total

=

70,000

Btu/Hr

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

_______ Btu/Hr (maximum the space can support)

______ Btu/Hr (actual amount of Btu/Hr used)

Example: 51,200 Btu/Hr (maximum the space can support)

70,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air From Inside Building.

B.Vent room directly to the outdoors. See Ven- tilation Air From Outdoors, page 7.

C.Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maxi- mum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

WARNING: If the area in which the heater may be oper- ated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section

5.3or applicable local codes.

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining un- confined space. When ventilating to an adjoining unconfined space, you must provide two perma- nent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 2, page 7). You can also remove door into adjoining room (see option 3, Figure 2, page 7). Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

6

www.desatech.com

111487-01E

Image 6 Contents
What to do if YOU Smell GAS Models CSBNT, CSBPT, CSPBNT, CSPBPT, CSPINT, Cspipt Table of Contents Safety Information Product Identification Local CodesProvide adequate clearances around air openings Product Features AIR for Combustion VentilationDetermining if You Have a Confined or Unconfined Space Determining FRESH-AIR Flow for Heater LocationVentilation AIR Ventilation Air From Inside BuildingAIR for Combustion Ventilation Unpacking Ventilation Air From OutdoorsClearances to Combustibles Vent-Free Operation Only InstallationCheck GAS Type Minimum Wall and Ceiling Clearances see ,Front View Connecting to GAS SupplyInstallation Items Needed Top ViewPetroleum LP gas Back ViewTest Pressures Equal To or Less Than 1/2 Psig 3.5 kPa Checking GAS ConnectionsTest Pressures In Excess Of 1/2 Psig 3.5 kPa Correct all leaks at onceStove cavity see Figure Installing LOG SETInstalling ROD and Screen Wall clearances as outlined onFor Your Safety Read Before Lighting Operating HeaterLighting Instructions Cleaning Maintenance Inspecting BurnersBlow air into the primary air holes on the injector holder Burner Injector Holder and Pilot AIR Inlet HoleLogs Replace logs if broken or chipped dime-sized or largerTroubleshooting Observed Problem Possible Cause RemedyWhen burner is lit Delayed ignition burnerBurner orifice clogged Clean burner see Cleaning Dark residue on logs or inside Improper log placementGas leak. See Warning Statement at topTechnical Service SpecificationsService Hints Replacement PartsIllustrated Parts Breakdown Parts List Stove Body Models CSB SERIES, Cspb Series and Cspi Series Parts Centrals Warranty Information Keep this Warranty
Related manuals
Manual 24 pages 61.37 Kb