Bryant 551B, 551C installation instructions CO2 Sensor Configuration, EconoMi$er IV Control

Page 30

A proportional anticipatory strategy should be taken with the following conditions: a zone with a large area, varied occupancy, and equipment that cannot exceed the required ventilation rate at design conditions. Exceeding the required ventilation rate means the equipment can condition air at a maximum ventilation rate that is greater than the required ventilation rate for maximum occupancy. A proportional-anticipatory strategy will cause the fresh air supplied to increase as the room CO2 level increases even though the CO2 set point has not been reached. By the time the CO2 level reaches the set point, the damper will be at maximum ventilation and should maintain the set point.

In order to have the CO2 sensor control the economizer damper in this manner, first determine the damper voltage output for minimum or base ventilation. Base ventilation is the ventilation required to remove contaminants during unoccupied periods. The following equation may be used to determine the percent of outside-air entering the building for a given damper position. For

N1

N

P1

P

T1

T

AQ1

AQ

SO+

SO

SR+

SR

 

EXH

TR

TR1

 

Set

 

 

2V

10V

 

 

EXH

 

24

24 Vac

 

 

Vac

COM

 

Min

HOT

_

 

Pos

+

 

 

Open

 

 

 

DCV

1

2

 

Max

 

 

 

2V

10V

 

 

DCV

 

 

5

 

 

 

 

DCV

 

4

 

Set

3

2V

10V

 

 

Free

 

EF

EF1

Cool

 

 

 

B

C

 

 

A

D

 

 

551B,C

best results there should be at least a 10 degree difference in outside and return-air temperatures.

(TO x 100OA ) + (TR x 100RA ) =TM

TO = Outdoor-Air Temperature OA = Percent of Outdoor Air TR = Return-Air Temperature RA = Percent of Return Air TM = Mixed-Air Temperature

Once base ventilation has been determined, set the minimum damper position potentiometer to the correct position.

The same equation can be used to determine the occupied or maximum ventilation rate to the building. For example, an output of 3.6 volts to the actuator provides a base ventilation rate of 5% and an output of 6.7 volts provides the maximum ventilation rate of 20% (or base plus 15 cfm per person). Use Fig. 38 to determine the maximum setting of the CO2 sensor. For example, a 1100 ppm set point relates to a 15 cfm per person design. Use the 1100 ppm curve on Fig. 38 to find the point when the CO2 sensor output will be 6.7 volts. Line up the point on the graph with the left side of the chart to determine that the range configuration for the CO2 sensor should be 1800 ppm. The EconoMi$er IV controller will output the 6.7 volts from the CO2 sensor to the actuator when the CO2 concentration in the space is at 1100 ppm. The DCV set point may be left at 2 volts since the CO2 sensor voltage will be ignored by the EconoMi$er IV controller until it rises above the 3.6 volt setting of the minimum position potentiometer.

Once the fully occupied damper position has been determined, set the maximum damper demand control ventilation potentiometer to this position. Do not set to the maximum position as this can result in over-ventilation to the space and potential high-humidity levels.

CO2 Sensor Configuration

The CO2 sensor has preset standard voltage settings that can be selected anytime after the sensor is powered up. (See Table 7.)

C06038

Fig. 37 ---EconoMi$er IV Control

CO2 SENSOR MAX RANGE SETTING

 

6000

 

 

 

 

 

 

(ppm)

5000

 

 

 

 

 

 

 

 

 

 

 

 

 

CONFIGURATION

4000

 

 

 

 

 

800 ppm

 

 

 

 

 

 

3000

 

 

 

 

 

900 ppm

 

 

 

 

 

1000 ppm

 

 

 

 

 

 

2000

 

 

 

 

 

1100 ppm

 

 

 

 

 

 

 

 

 

 

 

 

 

RANGE

1000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

2

3

4

5

6

7

8

 

DAMPER VOLTAGE FOR MAX VENTILATION RATE

C06039

Fig. 38 ---CO2 Sensor Maximum Range Setting

Use setting 1 or 2 for Bryant equipment. (See Table 7.)

1.Press Clear and Mode buttons. Hold at least 5 seconds until the sensor enters the Edit mode.

2.Press Mode twice. The STDSET Menu will appear.

3.Use the Up/Down button to select the preset number. (See Table 7.)

4.Press Enter to lock in the selection.

5.Press Mode to exit and resume normal operation.

The custom settings of the CO2 sensor can be changed anytime after the sensor is energized. Follow the steps below to change the non-standard settings:

1.Press Clear and Mode buttons. Hold at least 5 seconds until the sensor enters the Edit mode.

2.Press Mode twice. The STDSET Menu will appear.

3.Use the Up/Down button to toggle to the NONSTD menu and press Enter.

4.Use the Up/Down button to toggle through each of the nine variables, starting with Altitude, until the desired setting is reached.

5.Press Mode to move through the variables.

6.Press Enter to lock in the selection, then press Mode to continue to the next variable.

30

Image 30
Contents Installation Instructions Field Fabricate Ductwork Install External Trap for Condensate DrainProvide Unit Support Rig and Place UnitRoof Curb Details Unit Leveling Tolerances Unit Operating Dimensions Weight 551C551B 551B 036-072 Base Unit Dimensions 551C 024-060 Base Unit Dimensions Heat Anticipator Settings Field Power SupplyField Control Wiring Make Electrical ConnectionsPhysical Data 551B Base Unit 551BPhysical Data 551C Base Unit 551CPower Wiring Connections Electrical Data-551C FLA MCA LRA Type OutletPerf ect Voltage FLA Crheater 008,009 23.4 30.1 40.8 Electrical Data-551B FLA MCA LRA414 508 Ton 004+005 19.9 24.3 55.2 76.3 86.9 168 34.9 173 002 13.6 A00 or Adjust Factory-Installed Options Typical Perfect Humidity t Adaptive Dehumidification System Outdoor-Air Damper Position Setting Outdoor-Air Damper With Hood AttachedEconoMi$er IV Component Locations Optional EconoMi$er Temperature F Supply Air Temperature SAT SensorSupply Air Sensor Temperature Resistance Values Outdoor Air Lockout SensorEconoMi$er IV Control Modes Outdoor Dry Bulb Changeover EconoMi$er IV Sensor UsageDifferential Dry Bulb Control Outdoor Enthalpy Changeover Differential Enthalphy ControlMinimum Position Control Exhaust Set Point AdjustmentIndoor Air Quality IAQ Sensor Input Damper MovementOutside Air Temperature Changeover Set Points Return Air Temperature or Enthalpy Sensor Mounting LocationCO2 Sensor Configuration EconoMi$er IV ControlDehumidification of Fresh Air with DCV Control Adjust Evaporator-Fan SpeedCO2Sensor Standard Settings Belt Drive MotorsUnit Motor Pulley Turns Open Evaporator-Fan Motor Data Standard Motor Evaporator-Fan Motor Data High-Static Motors024, 036 060 74/84 072 Evaporator-Fan Motor EfficiencyMotor 551B Efficiency Airflow957 522 1000 598 173 718 267 Rpm Bhp Watts 900 566 142 690 228879 9031400 737 355 842 481 932 610 Rpm Bhp Watts 1200 666 252 778 361 873 476 956 5941300 701 809 418 902 540 983 665 875 551 962 6891700 866 478 966 608 Rpm Bhp Watts 1500 790 353 897 471 991 6001600 828 412 931 536 1022 670 1800 905 551 1001 6871495 1858 1700 1462 20671472 1761 1600 1463 1766 1520 1964 18002400 1145 1174 1223 1346 1296 1526 2200 1063 929 1147 1089 1224 1256 1295 14312300 1104 1046 1185 1212 1260 1386 2500 1185 1311 1262 14902000 984 727 1078 892 Rpm Bhp Watts 1800 907 558 1006 708 1092 8601900 945 638 1042 796 2100 1024 823 1115 9972300 1103 1044 1189 1234 1266 1425 2100 1024 823 1115 997 1195 1173 1268 13502200 1063 929 1152 1111 1230 1294 2400 1143 1168 1227 13671100 612 195 735 Rpm Bhp Watts 900 554 134 6811000 583 163 707 9191400 706 324 Rpm Bhp Watts 1200 643 233 762 3441300 674 276 1500 738 379719 Rpm Bhp Watts 1500 724 295 837 402 937 524 1028 6601600 757 343 866 455 962 580 1700 790 398 894 514 988 6431508 1957 1900 1474 1797 17001490 1873 1800 1467 1839 1527 2050 2000Rpm Bhp Watts 1500 1188 970 1261 1143 2400 1033 970 1115 1120 1192 1279 1264 14482500 1069 1084 1149 1239 1223 1403 1293 1576 1600 1208 1033 12792600 1097 1169 1181 1356 1257 1546 2400 1026 945 1115 1118 1195 1295 1268 14762500 1061 1053 1148 1233 1226 1416 1297 1604 2700 1132 1294 1214 1487 1289 1684Unit Preparation Internal WiringRefrigerant Service Ports Return-Air FiltersHeating Safety ReliefCooling Ventilation Continuous FanCleaning Evaporator CoilLubrication Refrigerant Charge Condenser-Fan AdjustmentEconoMi$er IV Adjustment No ChargeCooling Charging Chart Standard 551B Replacement Parts 551C 3 TON Charging Chart 551C 5 TON Charging Chart Unit Troubleshooting Economi$er IV TroubleshootingEconoMi$er IV Troubleshooting Completion Cooling Service AnalysisProblem Cause Remedy EconoMi$er IV Input/Output Logic Inputs OutputsEconoMi$er IV Functional View Preliminary Information Catalog No. II551B---C---36---1
Related manuals
Manual 170 pages 34.1 Kb Manual 52 pages 34.7 Kb

551C, 551B specifications

The Bryant 551B and 551C are two highly efficient air conditioning units designed to provide optimal comfort in residential settings. Known for their reliability and performance, these models are part of Bryant's esteemed line of heating and cooling solutions.

One of the standout features of the Bryant 551B is its two-stage cooling system, which allows for better humidity control and increased comfort. This ensures that homeowners can enjoy consistent temperatures while reducing energy consumption. The unit operates quietly, thanks to its noise-reducing technology, making it an ideal choice for bedrooms and living spaces.

On the other hand, the Bryant 551C builds upon this foundation with its variable-speed compressor. This technology allows the unit to adjust its cooling output according to the specific needs of the home. This results in seamless operation and even greater energy efficiency. Both models also incorporate Bryant's advanced control capabilities, which allow users to monitor and adjust settings remotely via smart devices, adding a layer of convenience and modernity to home climate control.

With an emphasis on durability, both the 551B and 551C feature a galvanized steel cabinet that protects against weather-related damage. The powder coat finish further enhances their resistance to rust and corrosion, ensuring a long lifespan and minimal maintenance.

Another significant characteristic of these units is their excellent Seasonal Energy Efficiency Ratio (SEER) ratings. The 551B boasts a SEER rating of up to 16, while the 551C takes it even further with ratings exceeding 20. This efficiency not only translates to lower energy bills for homeowners but also contributes to a reduced carbon footprint, making these units environmentally friendly options.

Both models are also designed to operate with eco-friendly refrigerants, aligning with modern energy standards and regulations aimed at reducing greenhouse gas emissions.

In summary, the Bryant 551B and 551C are exemplary choices for homeowners looking for reliable, efficient, and high-performing air conditioning solutions. With features such as two-stage and variable-speed compressors, advanced smart technology, and robust construction, these models stand out in the competitive HVAC market. They promise a comfortable indoor environment along with significant energy savings, making them a wise investment for the future.