551B,C

Table 31—Fan Performance 551B 060, 551C 060 — Horizontal Discharge Units;

High-Static Motor (Belt Drive)*

AIRFLOW

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

CFM

 

0.2

 

 

0.4

 

 

0.6

 

 

 

0.8

 

 

1.0

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

1500

724

0.33

295

837

0.45

402

937

0.59

524

 

1028

0.74

660

1111

0.91

808

1600

757

0.39

343

866

0.51

455

962

0.65

580

 

1050

0.81

719

1132

0.98

870

1700

790

0.45

398

894

0.58

514

988

0.72

643

 

1074

0.88

784

1154

1.06

938

1800

823

0.52

458

924

0.65

579

1015

0.80

712

 

1099

0.96

857

1177

1.14

1013

1900

857

0.59

525

955

0.73

650

1043

0.89

787

 

1125

1.05

936

1201

1.23

1096

2000

892

0.67

599

986

0.82

729

1072

0.98

870

 

1151

1.15

1022

1226

1.33

1185

2100

927

0.77

680

1017

0.92

815

1101

1.08

960

 

1178

1.26

1116

1251

1.44

1283

2200

962

0.87

769

1050

1.02

909

1131

1.19

1059

 

1206

1.37

1218

1277

1.56

1389

2300

997

0.97

865

1082

1.14

1010

1161

1.31

1165

 

1235

1.50

1329

1304

1.69

1503

2400

1033

1.09

970

1115

1.26

1120

1192

1.44

1279

 

1264

1.63

1448

1332

1.83

1625

2500

1069

1.22

1084

1149

1.39

1239

1223

1.58

1403

 

1293

1.77

1576

1360

1.98

1757

 

 

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

CFM

 

1.2

 

 

1.4

 

 

1.6

 

 

 

1.8

 

 

2.0

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

1500

1188

1.09

970

1261

1.29

1143

1330

1.49

1327

 

1395

1.71

1523

1457

1.95

1729

1600

1208

1.16

1033

1279

1.36

1208

1347

1.57

1394

 

1412

1.79

1590

1474

2.02

1797

1700

1229

1.24

1103

1299

1.44

1280

1366

1.65

1468

 

1429

1.88

1665

1490

2.11

1873

1800

1250

1.33

1181

1319

1.53

1360

1385

1.74

1549

 

1448

1.97

1748

1508

2.20

1957

1900

1273

1.43

1266

1341

1.63

1447

1405

1.84

1638

 

1467

2.07

1839

1527

2.31

2050

2000

1296

1.53

1359

1363

1.74

1542

1427

1.95

1736

 

1488

2.18

1939

1546

2.42

2151

2100

1320

1.64

1459

1386

1.85

1646

1448

2.07

1842

 

1508

2.30

2047

1566

2.55

2262

2200

1345

1.77

1568

1409

1.98

1758

1471

2.20

1956

 

1530

2.44

2164

1587

2.68

2380

2300

1371

1.90

1686

1434

2.11

1878

1494

2.34

2080

 

1553

2.58

2290

1609

2.83

2509

2400

1397

2.04

1812

1459

2.26

2008

1518

2.49

2213

 

1576

2.73

2425

2500

1424

2.19

1948

1484

2.42

2147

1543

2.65

2355

 

1599

2.89

2571

NOTES:

 

 

 

 

 

 

 

 

LEGEND

 

 

 

 

 

 

1. Bold cells indicate field-supplied drive is required.

 

 

Bhp — Brake Horsepower

 

 

 

 

2. Maximum continuous bhp is 2.90.

 

 

 

 

Watts — Input Watts to Motor

 

 

 

 

3. See general fan performance notes.

 

 

 

 

*Motor drive range: 1300 to 1685 rpm. All other rpms require field-supplied

 

 

 

 

 

 

 

 

drive.

 

 

 

 

 

 

Table 32—Fan Performance 551C 072 — Horizontal Discharge Units; Standard Motor (Belt Drive)*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

CFM

 

0.2

 

 

0.4

 

 

0.6

 

 

 

0.8

 

 

1.0

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

1800

822

0.51

455

927

0.66

589

1018

0.82

728

 

1100

0.98

873

1174

1.15

1024

1900

855

0.59

520

957

0.74

659

1046

0.91

805

 

1127

1.08

956

1200

1.25

1113

2000

889

0.66

591

988

0.83

737

1075

1.00

888

 

1154

1.18

1045

1226

1.36

1208

2100

923

0.75

668

1019

0.92

821

1104

1.10

979

 

1182

1.29

1142

1253

1.48

1310

2200

957

0.85

753

1051

1.03

912

1134

1.21

1077

 

1210

1.40

1245

1280

1.60

1419

2300

992

0.95

845

1083

1.14

1011

1164

1.33

1182

 

1239

1.53

1357

1308

1.73

1537

2400

1026

1.06

945

1115

1.26

1118

1195

1.46

1295

 

1268

1.66

1476

1336

1.87

1662

2500

1061

1.19

1053

1148

1.39

1233

1226

1.59

1416

 

1297

1.81

1604

1364

2.02

1796

2600

1097

1.32

1169

1181

1.53

1356

1257

1.74

1546

 

1327

1.96

1740

1393

2.18

1938

2700

1132

1.46

1294

1214

1.67

1487

1289

1.90

1684

 

1358

2.12

1885

1422

2.35

2089

2800

1168

1.61

1428

1247

1.83

1629

1320

2.06

1832

 

1388

2.30

2039

2900

1204

1.77

1572

1281

2.00

1779

1353

2.24

1989

 

3000

1240

1.94

1725

1315

2.18

1939

 

 

 

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

CFM

 

1.2

 

 

1.4

 

 

1.6

 

 

 

1.8

 

 

2.0

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

1800

1244

1.33

1182

1308

1.51

1345

1369

1.70

1513

 

1427

1.90

1687

1483

2.10

1867

1900

1268

1.44

1275

1332

1.63

1443

1393

1.82

1617

 

1450

2.02

1796

1505

2.23

1979

2000

1294

1.55

1376

1357

1.74

1549

1417

1.95

1727

 

1474

2.15

1911

1528

2.36

2100

2100

1320

1.67

1483

1382

1.87

1662

1441

2.08

1845

 

1498

2.29

2034

2200

1346

1.80

1598

1408

2.01

1782

1466

2.22

1971

 

2300

1372

1.94

1721

1434

2.15

1911

1491

2.37

2105

 

2400

1400

2.09

1852

1460

2.31

2047

 

2500

1427

2.24

1992

 

2600

 

2700

 

2800

 

2900

 

3000

 

NOTES:

 

 

 

 

 

 

 

 

LEGEND

 

 

 

 

 

 

1. Bold cells indicate field-supplied drive is required.

 

 

Bhp — Brake Horsepower

 

 

 

 

2. Maximum continuous bhp is 2.40.

 

 

 

 

Watts — Input Watts to Motor

 

 

 

 

3. See general fan performance notes.

 

 

 

 

*Motor drive range: 1120 to 1585 rpm. All other rpms require field-supplied

 

 

 

 

 

 

 

 

drive.

 

 

 

 

 

 

46

Image 46
Contents Installation Instructions Field Fabricate Ductwork Install External Trap for Condensate DrainProvide Unit Support Rig and Place UnitRoof Curb Details Unit Leveling Tolerances 551C Unit Operating Dimensions Weight551B 551B 036-072 Base Unit Dimensions 551C 024-060 Base Unit Dimensions Heat Anticipator Settings Field Power SupplyField Control Wiring Make Electrical ConnectionsPhysical Data 551B Base Unit 551BPhysical Data 551C Base Unit 551CPower Wiring Connections Electrical Data-551C FLA MCA LRA Type OutletPerf ect Voltage FLA Crheater 008,009 23.4 30.1 40.8 Electrical Data-551B FLA MCA LRA414 508 Ton 004+005 19.9 24.3 55.2 76.3 86.9 168 34.9 173 002 13.6 A00 or Adjust Factory-Installed Options Typical Perfect Humidity t Adaptive Dehumidification System Outdoor-Air Damper With Hood Attached Outdoor-Air Damper Position SettingEconoMi$er IV Component Locations Optional EconoMi$er Temperature F Supply Air Temperature SAT SensorSupply Air Sensor Temperature Resistance Values Outdoor Air Lockout SensorEconoMi$er IV Sensor Usage EconoMi$er IV Control Modes Outdoor Dry Bulb ChangeoverDifferential Dry Bulb Control Outdoor Enthalpy Changeover Differential Enthalphy ControlMinimum Position Control Exhaust Set Point AdjustmentIndoor Air Quality IAQ Sensor Input Damper MovementOutside Air Temperature Changeover Set Points Return Air Temperature or Enthalpy Sensor Mounting LocationCO2 Sensor Configuration EconoMi$er IV ControlDehumidification of Fresh Air with DCV Control Adjust Evaporator-Fan SpeedCO2Sensor Standard Settings Belt Drive MotorsUnit Motor Pulley Turns Open Evaporator-Fan Motor Data Standard Motor Evaporator-Fan Motor Data High-Static Motors024, 036 060 74/84 072 Evaporator-Fan Motor EfficiencyMotor 551B Efficiency Airflow957 522 1000 598 173 718 267 Rpm Bhp Watts 900 566 142 690 228879 9031400 737 355 842 481 932 610 Rpm Bhp Watts 1200 666 252 778 361 873 476 956 5941300 701 809 418 902 540 983 665 875 551 962 6891700 866 478 966 608 Rpm Bhp Watts 1500 790 353 897 471 991 6001600 828 412 931 536 1022 670 1800 905 551 1001 6871495 1858 1700 1462 20671472 1761 1600 1463 1766 1520 1964 18002400 1145 1174 1223 1346 1296 1526 2200 1063 929 1147 1089 1224 1256 1295 14312300 1104 1046 1185 1212 1260 1386 2500 1185 1311 1262 14902000 984 727 1078 892 Rpm Bhp Watts 1800 907 558 1006 708 1092 8601900 945 638 1042 796 2100 1024 823 1115 9972300 1103 1044 1189 1234 1266 1425 2100 1024 823 1115 997 1195 1173 1268 13502200 1063 929 1152 1111 1230 1294 2400 1143 1168 1227 13671100 612 195 735 Rpm Bhp Watts 900 554 134 6811000 583 163 707 9191400 706 324 Rpm Bhp Watts 1200 643 233 762 3441300 674 276 1500 738 379719 Rpm Bhp Watts 1500 724 295 837 402 937 524 1028 6601600 757 343 866 455 962 580 1700 790 398 894 514 988 6431508 1957 1900 1474 1797 17001490 1873 1800 1467 1839 1527 2050 2000Rpm Bhp Watts 1500 1188 970 1261 1143 2400 1033 970 1115 1120 1192 1279 1264 14482500 1069 1084 1149 1239 1223 1403 1293 1576 1600 1208 1033 12792600 1097 1169 1181 1356 1257 1546 2400 1026 945 1115 1118 1195 1295 1268 14762500 1061 1053 1148 1233 1226 1416 1297 1604 2700 1132 1294 1214 1487 1289 1684Unit Preparation Internal WiringRefrigerant Service Ports Return-Air FiltersHeating Safety ReliefCooling Ventilation Continuous FanCleaning Evaporator CoilLubrication Refrigerant Charge Condenser-Fan AdjustmentEconoMi$er IV Adjustment No ChargeCooling Charging Chart Standard 551B Replacement Parts 551C 3 TON Charging Chart 551C 5 TON Charging Chart Unit Troubleshooting Economi$er IV TroubleshootingCooling Service Analysis EconoMi$er IV Troubleshooting CompletionProblem Cause Remedy EconoMi$er IV Input/Output Logic Inputs OutputsEconoMi$er IV Functional View Preliminary Information Catalog No. II551B---C---36---1
Related manuals
Manual 170 pages 34.1 Kb Manual 52 pages 34.7 Kb

551C, 551B specifications

The Bryant 551B and 551C are two highly efficient air conditioning units designed to provide optimal comfort in residential settings. Known for their reliability and performance, these models are part of Bryant's esteemed line of heating and cooling solutions.

One of the standout features of the Bryant 551B is its two-stage cooling system, which allows for better humidity control and increased comfort. This ensures that homeowners can enjoy consistent temperatures while reducing energy consumption. The unit operates quietly, thanks to its noise-reducing technology, making it an ideal choice for bedrooms and living spaces.

On the other hand, the Bryant 551C builds upon this foundation with its variable-speed compressor. This technology allows the unit to adjust its cooling output according to the specific needs of the home. This results in seamless operation and even greater energy efficiency. Both models also incorporate Bryant's advanced control capabilities, which allow users to monitor and adjust settings remotely via smart devices, adding a layer of convenience and modernity to home climate control.

With an emphasis on durability, both the 551B and 551C feature a galvanized steel cabinet that protects against weather-related damage. The powder coat finish further enhances their resistance to rust and corrosion, ensuring a long lifespan and minimal maintenance.

Another significant characteristic of these units is their excellent Seasonal Energy Efficiency Ratio (SEER) ratings. The 551B boasts a SEER rating of up to 16, while the 551C takes it even further with ratings exceeding 20. This efficiency not only translates to lower energy bills for homeowners but also contributes to a reduced carbon footprint, making these units environmentally friendly options.

Both models are also designed to operate with eco-friendly refrigerants, aligning with modern energy standards and regulations aimed at reducing greenhouse gas emissions.

In summary, the Bryant 551B and 551C are exemplary choices for homeowners looking for reliable, efficient, and high-performing air conditioning solutions. With features such as two-stage and variable-speed compressors, advanced smart technology, and robust construction, these models stand out in the competitive HVAC market. They promise a comfortable indoor environment along with significant energy savings, making them a wise investment for the future.