Rheem Indirect Water Heater warranty Section IV Installation, Water connections

Page 9

Section IV: Installation

water connections

All piping between the boiler and the indirect water heater should be new copper with a minimum size of 3/4” ID for models STID30, STID40, and STID50. Use 1” minimum copper for models STID80 and STID120. Elbows should be minimized. A flow check valve must be installed on the return line.

All piping to the inlet (cold) and outlet (hot) domestic water connections should be new copper with a minimum size of 1/2” ID for models STID30, STID40, and STID50. Use 3/4” ID minimum for models STID80 and STID120.

All piping should conform to local codes and ordinances. At a minimum, refer to ILHR 84 code if local codes are not in place. It is recommended that all piping be adequately insulated with approved material to ensure minimum heat loss. If a re-circulation line is used for domestic water, be certain that all lines are well insulated and the circulator is temperature controlled. Install isolation valves to permit proper servicing. It is also recommended to install a union on the domestic outlet to facilitate replacement of the hot outlet / anode nipple on models STID30, STID40, and STID50.

See Figures 6 and 7 for proper water connection installation.

 

 

BOILER

3/4"

3/4"

SYSTEM

SUPPLY

DOMESTIC

COLD

CIRCULATOR

HOT OUT

INLET

PUMP

INDIRECT

WATER HEATER

FROM BOILER 1" NPT

TO

CHECK

BOILER

1" NPT

VALVE

BOILER

BOILER

SYSTEM

RETURN

BOILER

SYSTEM

SUPPLY

CIRCULATOR

PUMP

Figure 6: STID30, STID40, STID50 water connections

1 1/2"

 

 

 

 

DOMESTIC

 

 

HOT OUT

 

 

 

INDIRECT

 

 

WATER HEATER

 

 

FROM

 

 

BOILER

NOTICE: Indirect water heater may be connected to a steam

1" NPT

 

boiler provided that all piping to and from

1"

 

the boiler are below the water line of the boiler.

COLD

 

INLET

TO

Boiler must also be protected by a low water

 

BOILER

 

1" NPT

cut off safety device.

BOILER

BOILER

SYSTEM

CHECKRETURN VALVE

Figure 7: STID80, STID120 water connections

Page 9

Image 9
Contents Indirect Water Heater Table of Contents NPT Section I SpecificationsSTID30 Section II General Information Temperature controlLocation Water treatment/filtrationTemperature and pressure relief value t&P Anode rodsBack-flow preventor closed loop system Boiler and circulator sizing Section III Pre-InstallationGrundfos UP 15-42F performance curve Water connections Section IV InstallationRheem Indirect Water Heater with Low-Mass Boiler Indirect Circulator Electrical connectionsWater piping Section V MaintenanceRelief valve Flush the tank352%/0 $86 62/87,21 Section VI TroubleshootingDescription Applicable Models Section VIi parts listLimited Warranty Exclusive Warranty Limitation of Liability