Section III: Pre-Installation (cont..)

UP 15-42F/FR

Closed Systems , 60 Hz

Figure 4: GRUNDFOS UP 15-42F performance curve

UP 26-64F

Closed Systems , 60 Hz

Figure 5: GRUNDFOS UP 26-64F performance curve

NOTICE: Zone valves on the heat source supply to the indirect water heater are not recommended and will drastically reduce performance.

System performance can also vary based on the heating capacity of the boiler. If the minimum coil output (assume coil output = boiler output) listed in Tables 2 and 3 is not met, the output (first hour rating) of the indirect water heater will not be met at the selected flow rate.

To approximate the reduction in first hour rating as a result of low boiler capacity, use the following formula:

New first hour rating = (First hour rating) * (Actual boiler output)/(Minimum coil output)

For example, the first hour rating of a STID50 at a 77°F rise with an 8 GPM heat source flow rate using a boiler having a DOE heating capacity (output) of 60,000 BTU/Hr would be:

New first hour rating = (160 gal) * (60,000 BTU/Hr)/(77,000 BTU/Hr) = 125 gal

Page 8

Image 8
Contents Indirect Water Heater Table of Contents Section I Specifications NPTSTID30 Temperature control Section II General InformationLocation Water treatment/filtrationBack-flow preventor closed loop system Temperature and pressure relief value t&PAnode rods Section III Pre-Installation Boiler and circulator sizingGrundfos UP 15-42F performance curve Section IV Installation Water connectionsRheem Indirect Water Heater with Low-Mass Boiler Electrical connections Indirect CirculatorSection V Maintenance Water pipingRelief valve Flush the tankSection VI Troubleshooting 352%/0 $86 62/87,21Section VIi parts list Description Applicable ModelsLimited Warranty Exclusive Warranty Limitation of Liability