3.0 Commissioning of solar controller
3.1.7 Menu“Manual operation”
For commissioning, service and test purposes the solar primary system can be manually operated. For this purpose the switch outputs may be disconnected or connected. During manual operation there is no automatic regulation of the system.To avoid inadmissible operating states this mode of operation changes into “Indication” after ca.
8 hours and the automatic regulation is activated again.
Indication | Description | Valuerange |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Switching on / off switch output A1 (solar circulation pump) by hand | 0 = off |
|
|
|
|
|
|
|
| 1 = on |
|
|
|
|
|
|
| Switching on / off switch output A2 (pump2 / valve1) by hand | 0 = off |
|
|
|
|
|
|
|
| 1 = on |
|
|
|
|
|
|
| Switching on / off switch output A3 (cooling, thermostat or 2nd temperature | 0 = off |
|
|
|
|
|
|
| difference controller function) by hand | 1 = on |