Indication
+
3.2.2 Flow monitoring
If the energy productivity measurement option is deactivated, the temperature difference between collector and storage tank is checked.
If it exceeds the amount of (60K + dTmax), it is then interpreted as an error because in the case of normal system dimensioning and a pump switched on such large differences cannot take place.
If the energy productivity measurement option is activated, the flow amount when the pump is switched on is checked. If for 15 minutes no flow is recognised it is evaluated as an error.
Error message is automatically reset after eliminating the failure.
Meaning
Missing circulation in solar circuit
3.2.3 Collector protection / Re-cooling
|
| This function can be switched on/off in the “Basic settings” |
|
| menu. |
|
| High temperatures can destroy antifreeze liquids.Therefore, |
|
| the maximum collector temperature should be restricted. |
|
| When all storages have been loaded to the limit, the solar |
|
| pump is switched off. If the collector temperature rises |
|
| above“T collector max”, the solar pump is switched on, |
|
| until the collector temperature drops by 10K. Part of the |
|
| energy is lost in the pipes, the rest is loaded in the storage, |
|
| which results in increasing the storage temperature above |
|
| the adjusted maximum storage temperature. For security |
|
| reasons the function will be interrupted if the storage |
|
| reaches 95ºC. |
|
| If the storage temperature is bigger TStmax+2K and the |
|
| collector temperature is 10K belowTSt, then the |
|
| function is activated.The redundant storage energy will be |
|
| released through the collector in order to assure reserves |
|
| for the next loading cycle. |
|
| The |
|
| cooling till…” in the “Basic settings” menu, point 3, or |
|
| when the collector temperature >= the storage |
|
| temperature – 2K. |
|
| The |
|
| collector protection function is on. |
|
| Correspondingvaluesin menu |
|
| |
“Basic SETTINGS” | “Programming” | |
|
|
|
0 | 1 | |
1 |
| |
2 | 1 |
|
3 | 40ºC |
|
3.2.4 Systemprotection function
The system protection function switches the system off if the “maximum collector temperature” is exceeded by 10K. As soon as the temperature drops below the “maximum collector temperature”, the system is started up again.This function has higher priority and is always active, regardless of whether the collector protection is on or off.