Desa CGP10TA AIR for Combustion Ventilation, Determining FRESH-AIR Flow for Heater Location

Page 5

OWNER’S MANUAL

AIR FOR

COMBUSTION AND

VENTILATION

Continued

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

Use this worksheet to determine if you have a confined or unconfined space.

Space: Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.

1.Determine the volume of the space (length x width x height).

Length x Width x Height = ________________ cu. ft. (volume of space)

Example: Space size 18 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2304 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.

2.Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.

_______________ (volume of space) ÷ 50 cu. ft. = (Maximum Btu/Hr the space can support)

Example: 2304 cu. ft. (volume of space) ÷ 50 cu. ft. = 46.1 or 46,100 (maximum Btu/Hr the space can support)

3.Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

 

_________________ Btu/Hr

 

 

 

 

Gas water heater*

 

_________________ Btu/Hr

Example:

 

 

 

Gas furnace

 

_________________ Btu/Hr

Gas water heater

 

40,000

Btu/Hr

Vented gas heater

 

_________________ Btu/Hr

Vent-free heater

+

10,000

Btu/Hr

Gas fireplace logs

 

_________________ Btu/Hr

 

=

 

 

 

Total

50,000

Btu/Hr

Other gas appliances* +

_________________ Btu/Hr

 

 

 

 

Total

=

_________________ Btu/Hr

 

 

 

 

*Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

_________________ Btu/Hr (maximum the space can support)

_________________ Btu/Hr (actual amount of Btu/Hr used)

Example: 46,100 Btu/Hr (maximum the space can support) 50,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoin- ing room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 6.

B.Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 6.

C.Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the National Fuel Gas Code, ANS Z223.1, Section 5.3 or applicable local codes.

Continued

104268

5

Image 5
Contents What to do if YOU Smell GAS CGP10TA CGP10TLAVENT-FREE PROPANE/LP GAS Heater Safety InformationProduct Identification Product FeaturesLocal Codes UnpackingProviding Adequate Ventilation AIR for Combustion and VentilationUnusually Tight Construction Confined and Unconfined SpacesDetermining if You Have a Confined or Unconfined Space AIR for Combustion VentilationDetermining FRESH-AIR Flow for Heater Location Ventilation Air From Outdoors Ventilation AIRVentilation Air From Inside Building Installation Installing Bottom Mounting Screw Installing Two Mounting ScrewsPlacing Heater On Mounting Screws Removing Front Panel Of HeaterExternal Regulator With Vent Pointing Down Connecting to GAS SupplyChecking GAS Connections Pressure Testing Gas Supply Piping SystemPressure Testing Heater Gas Connections Lighting Instructions For Your Safety Read Before LightingOperating Heater Inspecting Burner Service Publications Hints Cleaning and MaintenanceAccessory Technical ServiceObserved Problem Possible Cause Remedy TroubleshootingMaintenance, Gas leak. See Warning statement at Parts not Under Warranty Replacement Parts CentralParts Under Warranty CGP10TA CGP10TLA Illustrated Parts BreakdownKEY Part Number Description QTY Parts ListWarranty Information

CGP10TLA, CGP10TA specifications

Desa CGP10TA and CGP10TLA are advanced generator models known for their reliability and performance in various applications. These generators are designed to cater to both residential and light commercial needs, providing an efficient power solution anytime and anywhere.

One of the most notable features of the CGP10TA and CGP10TLA is their robust engine performance. These generators are powered by a high-quality, air-cooled four-stroke engine that ensures durability and long operational life. Their engines are optimized for fuel efficiency, enabling users to minimize operational costs while maximizing usability.

The CGP10TA and CGP10TLA models come equipped with automatic voltage regulation (AVR) technology. This feature guarantees stable voltage output, which is essential for sensitive electronic devices. By maintaining consistent voltage levels, the generators protect appliances from potential damage caused by power surges or fluctuations, thereby enhancing user confidence.

Safety is another priority in the design of these generators. Both models include essential safety features such as low-oil shutdown, which automatically turns off the engine when oil levels drop below a certain threshold. This safeguard helps prevent engine damage and prolongs the generator's lifespan, making it a wise choice for conscientious users.

Portability is a standout characteristic of the Desa CGP10TA and CGP10TLA generators. Each unit is designed with a lightweight frame, convenient carrying handles, and rubber wheels, allowing for easy transportation to various locations. Whether you need backup power during a storm, for camping, or to support outdoor events, these generators are versatile and user-friendly.

Moreover, these generators are engineered for quiet operation. Their noise-reduction technologies ensure a peaceful environment, making them suitable for residential areas and outdoor gatherings where excessive noise could be disruptive. Users can enjoy reliable power without the worry of disturbing neighbors or losing the tranquility of nature.

In terms of connectivity, both models include multiple AC and DC outlets, making it easy to power various devices simultaneously. Whether it's lights, power tools, or electronics, these generators can handle the load with ease, providing versatility for any power needs.

In conclusion, the Desa CGP10TA and CGP10TLA generators represent a blend of performance, safety, and convenience. With their advanced engine technology, automatic voltage regulation, safety features, portability, and quiet operation, they stand out as excellent choices for anyone in need of reliable, efficient, and user-friendly power solutions.